WAGO I/O System 750 XTR
Device Description 17
750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR
Manual
Version 1.0.0
Use supply modules for ground (earth)!
The I/O module has no power jumper contacts for receiving and transmitting the
earth potential. Use a supply module when an earth potential is needed for the
subsequent I/O modules.
The field voltage and the system voltage are electrically isolated from each other.
With consideration of the power jumper contacts, the individual modules can be
arranged in any combination when configuring the fieldbus node.
An arrangement in groups within the group of potentials is not necessary.
Mixed operation
Mixed operation (standard/XTR modules) within a node is possible when groups
of modules are electrically isolated on the field side (i.e., electrically isolated
power supply).
Increased interference!
For standard-compliant application in substation instrumentation and control,
telecontrol systems, railway technology or shipbuilding certified operation,
field-side power supply filter 750-624/040-001 or power supply filter
750-626/040-000 are generally to be used for XTR module groups.
The I/O module can be operated with all fieldbus couplers/controllers of the
WAGO I/O System 750 XTR.
Observe the instructions for mixed operation when used in mixed operation
behind standard fieldbus couplers/controllers.