22 Device Description
WAGO-I/O-SYSTEM 750 XTR
750-1415/040-000 8DI 24VDC 3ms 2-Wire XTR
Manual
Version 1.3.0
3.6
Technical Data
3.6.1
Device Data
Table 7: Technical Data – Device
Width
12 mm
Height (from upper edge of DIN-rail)
67 mm
Depth
100 mm
Weight
45 g
Degree of protection
IP20
3.6.2
Power Supply
Table 8: Technical Data – Power Supply
Current consumption,
system voltage
max.
6 mA
Current consumption, power jumper
contact
typ.
(24 VDC)
2 mA
Voltage supply via power jumper
contacts
under laboratory conditions
for ambient operating temperature
−40 °C … +55 °C
for ambient operating temperature
+55 °C … +70 °C
24 VDC (power supply via SELV/PELV
power supply unit)
18 V … 31,2 V (17,4 V … 31,2 V)
*)
18 V … 28,8 V (17,4 V … 28,8 V)
*)
18 V … 26,4 V (17,4 V … 26,4 V)
*)
Current
max.
via power jumper contacts
.
10 A
Rated surge voltage
1 kV
*)
Including residual ripple of 15 %
3.6.3
Communication
Table 9: Technical Data – Communication
Data width
8 bits