34 Process Image
WAGO-I/O-SYSTEM 750 XTR
750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR
Manual
Version 1.3.0
Table 24: Status Byte S0
Status Byte S0
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reg_Com
ERR_1
ERR24V
TEMP_1
LOAD_1
COM_1
OVR_1
UNR_1
UNR_1
Undershooting underrange limiting value channel 1
Results from the limiting value monitoring before the comparison of the
process data in the calibrated range. If the configured limiting value is
undershot, this bit is set.
0:
Underrange limiting value is not undershot.
1:
Underrange limiting value is undershot.
OVR_1
Exceeding of overrange limiting value channel 1
Results from the limiting value monitoring before the comparison of the
process data in the calibrated range. If the configured limiting value is
exceeded, this bit is set.
0:
Overrange limiting value is not exceeded.
1:
Overrange limiting value is exceeded.
COM_1
Output driver error 1 (COM) channel 1, common mode overrange.
This bit is set if the 24 V field power falls below 20 V.
0:
No output driver error 1 (COM)
1:
Output driver error 1 (COM) present.
LOAD_1
Output driver error 2 (LOAD) channel 1, load error.
This bit is set if there is a short circuit during voltage output or if there is an
open circuit during current output.
0:
No output driver error 1 (LAST).
1:
Output driver error 2 (LAST) present.
TEMP_1
Output driver error 3 (TEMP) channel 1, overtemperature.
This bit is set if the permissible temperature of the output driver is exceeded.
0:
No output driver error 3 (TEMP)
1:
Output driver error 3 (TEMP) present.
ERR24V
Error 24V field voltage.
This bit indicates an invalid state of the field-side power supply. In mode
6 … 18 V, the undervoltage detection threshold is somewhat higher inherently
(at approx. 20.5 V). The module still outputs the required voltage value when
this threshold is indicated, but the value does not exceed the value that is still
technically possible. Loosely speaking the input voltage must be approx. 2 V
higher than the required output voltage.
0:
24 V field voltage OK.
1:
24 V field voltage too low.
ERR_1
Group error channel 1
If one of the channel-related status bits is activated, this bit is also set to 1.
0:
No group error.
1:
Group error present.
Reg_Com
0: