20 Device Description
WAGO-I/O-SYSTEM 750 XTR
750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR
Manual
Version 1.3.0
3.2.3
CAGE CLAMP
®
Connectors
Figure 4: CAGE CLAMP
®
Connectors
Table 5: Legend for Figure “CAGE CLAMP
®
Connectors”
Channel Designation Connector Function
1
+AO 1
1
Analog output 1
+Sense AO 1
2
Positive sense connection for analog
output 1
−
Sense AO 1
3
Negative sense connection for analog
output 1
Common
(ground)
4
Common (ground) for analog output
2
+AO 2
5
Analog output 2
+Sense AO 2
6
Positive sense connection for analog
output 2
−
Sense AO 2
7
Negative sense connection for analog
output 2
Common
(ground)
8
Common (ground) for analog output
Use shielded signal lines!
Only use shielded signal lines for analog signals and I/O modules which are
equipped with shield clamps. Only then can you ensure that the accuracy and
interference immunity specified for the respective I/O module can be achieved
even in the presence of interference acting on the signal cable.
For further information about shielding, see system manual WAGO-I/O-SYSTEM
750 XTR, section “Connect Devices” > … > “Shielding.”