2787-2147 (/0000-00x0)
Properties
Product manual | Version: 1.2.2
23
Power Supply Pro 2
Property
Value
Specifications of the conductors used
≥ +75°C / +167°F (ambient air temperature: ≤
+60°C / 140°F)
≥ +90°C / 194°F (ambient air temperature: >
+60°C / 140°F)
Required tools (conductor termination)
Operating tool, with a partially insulated shaft,
type 2 (see section
8
3.9.6 Communication
Table 26: Technical Data – Communication
Property
Value
Data timeliness of the communication interface
200 ms
3.9.7 MTBF/Lifespan
Table 27: Technical Data – MTBF/Lifespan
Property
At
Load
T
amb
Value
MTBF, typ. (SN 29500) (IEC 61709)
24 VDC SELV
100 %
25 °C
950000 h
24 VDC SELV
100 %
40 °C
580000 h
3.9.8 Environmental Conditions
Table 28: Technical Data ‒ Environmental Conditions
Property
Value
Surrounding air temperature, operation
−25 … +70 °C
Surrounding air temperature, restricted operation
1)
−40 … −25 °C
Surrounding air temperature, storage
−40 … +85 °C
Derating (temperature-dependent)
2)
−1 %/V (> +40 °C and < 100 VAC)
−3 %/K (> +55 °C and < 230 VAC)
−3 %/K (> +60 °C and ≥ 230 VAC)
Derating (location-dependent)
2)
−10.7 %/1000 m (> +50 °C; 3600 m or higher)
−11.2 %/1000 m (> +55 °C; 2100 m or higher)
Derating (voltage-dependent)
2)
−5 %/V (UOUT > 24 VDC)
Relative humidity
5 … 96 % (no condensation permissible)
Elevation above sea level, max.
5000 m
Overvoltage category
III (≤ 2000 m)
II (> 2000 m)
Vibration according to IEC 60068-2-6
5 … 150 Hz / 1g
Shock according to IEC 60068-2-27
15 g / 11 ms
Pollution degree according to IEC/EN 60664-1
2
Resistance to harmful gas
3)
Resistant to flowing mixed gas per ISA S71.04,
G3 Group A
1)
Without mechanical actuation of buttons, female connectors etc., for example
2)
See section
8
3)
Only applies to 2787-2147/0000-0070
Note
Observe the following for long-term storage:
For long-term storage, power must be applied to equipment with built-in capacitors for
five minutes at least every two years.