2021
4
150mm Free Standing Wood fire Flue Kit
Installation Instructions
WARNING: FLUE KITS MUST BE MANUFACTURED IN ACCORDANCE WITH AS/NZS 2918:2001 AND
TESTED TO APPENDIX F. TO ENSURE SAFETY THIS FLUE KIT MUST BE INSTALLED AS
OUTLINED IN THESE INSTRUCTIONS AND THE APPROPRIATE REQUIREMENTS OF
THE RELEVANT BUILDING CODE OR CODES. WOOD FIRE AND FLUE CLEARANCES
FROM COMBUSTIBLE WALLS MUST BE IN ACCORDANCE WITH WOOD FIRE
MANUFACTURER’S SPECIFICATIONS AND AS/NZS 2918:2001.
The Wagener Fairburn uses a 150mm diameter flue. It is imperative that the connection between the flue and
the flue flange is sealed using a suitable flue sealant/fire cement. If an offset bend is required it should be as
steep as possible to enable ease of cleaning. Extra flue height may be required to compensate for any lack of
draw through a bend. The performance of the Wagener Fairburn depends more on the flue than on any other
single component as it is the draw on the flue that drives the Fairburn.
We recommend 4.8 metres of
flue for optimum performance.
The top of the flue system should be at least 1000mm above the roof or at least 600mm higher than any
obstacle or ridge within 3 metres of the flue. The flue pipe shall extend not less than 4.6M ABOVE the floor
protector. However a total minimum vertical height of 4.8 metres is recommended for optimum
performance. Joints between sections of the flue pipes are push fitted so that the upper section enters the
bottom section and must be SEALED using a suitable flue sealant/fire cement.
Each section should be secured
to prevent separation using three monel steel rivets.
PLEASE FOLLOW STEP BY STEP INSTRUCTIONS ON PAGE 5
Clean flue pipes before lighting the fire
. Stainless Steel pipe should be wiped clean using a soft cloth and
methylated spirits to remove finger marks and oils used to manufacture the flue pipe. Hi-Therm flue pipe can
be touched up if required using only STOVE BRIGHT aerosol paint.
Please leave all installation and operating instructions with the owner
ANTI DOWN
DRAUGHT COWL
250MM
OUTER
CASING
PERLIN
FLASHING
Inner casing
200mm above
roof line
150MM
FLUE PIPE
200MM
INNER
CASING
CEILING
PLATE
CERAMIC
CEILING
SPACER
TIMBER
NOGGING
150mm
Flue Pipe
Flue Flange
4.8 Metres to top of flue pipe
Warranty
Sparky CAs
firebox is
covered by a 5 year warranty
(Please refer to Installation &
Operating Instructions for full
details).
Wagener Stoves have over
40 years experience in the
heating industry and have been
members of the NZ Home
Heating Association for over
30 years.
Other Products
Manufactured by
Wagener Stoves
Wagener Stoves also design and
manufacture “Lion” Wetbacks, the
CookTop Wagener Stove, Butler
Multi High Performance Hot Water
Heaters, Traditional Style Slow
Combustion Wagener Fairburn
Cookers, Wagener Sparky and
Wagener Leon.
WAGENER STOVES "LION"
LTD
5 Allen Bell Drive, Kaitaia 0410
New Zealand
Phone: 09 408 2469
www.wagenerstoves.co.nz
At Wagener Stoves we are continually
improving our products and therefore
specifications and designs may change
without prior notice
2019
N E
W Z
E A L A N D M A D
E
3m
3m
3m
1m (min)
0.6m
or less
More than 3m
*increase flue
height as
needed to be
clear by 3m
Roof line
COMBINATION
BRACKET
CASING
COVER
Ash Hearth
Floor Protector
WARNING: FLUE KITS MUST BE MANUFACTURED IN
ACCORDANCE WITH AS/NZS 2918:2001 AND TESTED TO
APPENDIX F. TO ENSURE SAFETY THIS FLUE KIT MUST BE
INSTALLED AS OUTLINED IN THESE INSTRUCTIONS AND
THE APPROPRIATE REQUIREMENTS OF THE RELEVANT
BUILDING CODE OR CODES. WOOD FIRE AND FLUE
CLEARANCES FROM COMBUSTIBLE WALLS MUST BE IN
ACCORDANCE WITH WOOD FIRE MANUFACTURER’S
SPECIFICATIONS AND AS/NZS 2918:2001.
The Wagener Fairburn uses a 150mm diameter flue. It is imperative that
the connection between the flue and the flue flange is sealed using a
suitable flue sealant/fire cement. If an offset bend is required it should
be as steep as possible to enable ease of cleaning. Extra flue height may
be required to compensate for any lack of draw through a bend. The
performance of the Wagener Fairburn depends more on the flue than
on any other single component as it is the draw on the flue that drives
the Fairburn.
We recommend 4.8 metres of flue for optimum
performance.
The top of the flue system should be at least 1000mm above the roof
or at least 600mm higher than any obstacle or ridge within 3 metres of
the flue. The flue pipe shall extend not less than 4.6M ABOVE the floor
protector. However a total minimum vertical height of 4.8 metres is
recommended for optimum performance. Joints between sections of the
flue pipes are push fitted so that the upper section enters the bottom
section and must be SEALED using a suitable flue sealant/fire cement.
Each section should be secured to prevent separation using three monel
steel rivets.
2021
4
150mm Free Standing Wood fire Flue Kit
Installation Instructions
WARNING: FLUE KITS MUST BE MANUFACTURED IN ACCORDANCE WITH AS/NZS 2918:2001 AND
TESTED TO APPENDIX F. TO ENSURE SAFETY THIS FLUE KIT MUST BE INSTALLED AS
OUTLINED IN THESE INSTRUCTIONS AND THE APPROPRIATE REQUIREMENTS OF
THE RELEVANT BUILDING CODE OR CODES. WOOD FIRE AND FLUE CLEARANCES
FROM COMBUSTIBLE WALLS MUST BE IN ACCORDANCE WITH WOOD FIRE
MANUFACTURER’S SPECIFICATIONS AND AS/NZS 2918:2001.
The Wagener Fairburn uses a 150mm diameter flue. It is imperative that the connection between the flue and
the flue flange is sealed using a suitable flue sealant/fire cement. If an offset bend is required it should be as
steep as possible to enable ease of cleaning. Extra flue height may be required to compensate for any lack of
draw through a bend. The performance of the Wagener Fairburn depends more on the flue than on any other
single component as it is the draw on the flue that drives the Fairburn.
We recommend 4.8 metres of
flue for optimum performance.
The top of the flue system should be at least 1000mm above the roof or at least 600mm higher than any
obstacle or ridge within 3 metres of the flue. The flue pipe shall extend not less than 4.6M ABOVE the floor
protector. However a total minimum vertical height of 4.8 metres is recommended for optimum
performance. Joints between sections of the flue pipes are push fitted so that the upper section enters the
bottom section and must be SEALED using a suitable flue sealant/fire cement.
Each section should be secured
to prevent separation using three monel steel rivets.
PLEASE FOLLOW STEP BY STEP INSTRUCTIONS ON PAGE 5
Clean flue pipes before lighting the fire
. Stainless Steel pipe should be wiped clean using a soft cloth and
methylated spirits to remove finger marks and oils used to manufacture the flue pipe. Hi-Therm flue pipe can
be touched up if required using only STOVE BRIGHT aerosol paint.
Please leave all installation and operating instructions with the owner
PLEASE FOLLOW STEP BY STEP INSTRUCTIONS ON
PAGE 5
Clean flue pipes before lighting the fire.
Stainless Steel pipe
should be wiped clean using a soft cloth and methylated spirits
to remove finger marks and oils used to manufacture the flue
pipe. Hi-Therm flue pipe can be touched up if required using only
STOVE BRIGHT aerosol paint.
Please leave all installation and operating instructions
with the owner.