Use of Extension Cords
When a long extension cord is used to connect an appliance or tool to
the generator, a voltage loss occurs—the longer the cord, the greater
the voltage loss. This results in less voltage being supplied to the
appliance or tool and increases the amount of current draw or reduces
performance. A heavier cord with a larger wire size will reduce the
voltage loss.
Damaged extension cords can cause electrical shock, resulting in
serious injury or death. DO NOT use worn, bare, or frayed cords.
Replace damaged cords immediately.
Use the chart below as a guide for selecting proper cable size.
Use only extension cords rated for outdoor use and equipped with a
third-wire ground.
NOTICE:
Operating equipment at low voltage can cause it to overheat.
Current
Load in Watts
Maximum Cable Length in Feet
(Amps)
120V
240V
#10
#12
#14
#16
2.5
300
600
1000.
600
375
250
5
600
1200
500
300
200
125
7.5
900
1800
350
200
125
100
10
1200
2400
250
150
100
-
15
1800
3600
150
100
65
-
20
2400
4800
125
75
50
-
WARNING