G 3.3A
Operation
wc_tx000150gb.fm
23
4.10 To Run
See Graphic: wc_gr000679 and wc_gr000665
4.10.1
Disconnect all loads from the generator and place main circuit breaker
lever in open position (O).
4.10.2
Open fuel valve by moving lever to the right (a1).
4.10.3
If engine is cold, move choke lever to closed position (b1). If engine is
hot, set choke to open position (b2).
4.10.4
Turn engine switch to "ON" (c1) and pull starter rope (d).
Note:
If the oil level in the engine is low, the engine will not start. If this
happens, check oil level and add oil as needed.
4.10.5
Open choke as engine warms (b2).
4.10.6
Place main circuit breaker in closed position (l). Allow engine to warm
up a few minutes before attaching loads. On models ending with an
“AE” check the function of the earth-leakage circuit breaker. See
Earth-leakage Circuit Breaker.
4.11 To Stop
See Graphic: wc_gr000679 and wc_gr000665
4.11.1
Turn off and disconnect all tools and appliances attached to the
generator.
4.11.2
Place main circuit breaker in open position (O).
4.11.3
Turn the engine switch to "OFF" (c2).
4.11.4
Close fuel valve by moving lever to the left (a2).
Note:
To stop engine quickly in an emergency, turn engine switch to
"OFF".