Operation
G 100 / G 120
48
wc_tx001687gb.fm
4.14
Manual Start-Up
Explanation
Before starting the generator set for the first time, thoroughly review the “Before
starting” checklist in the previous section. Proceed with generator starting only after
checking each item in that section.
Thoroughly read and make sure you understand the engine operator’s manual
supplied with the generator. Follow the steps below in the order listed.
Start-up
procedure
Follow the procedure below to start the generator.
1. Make sure the engine start switch
(f)
is in the off “O” position.
2. Check position of the voltage selector
(v)
and make sure it is set for the desired
voltage output. Lock the switch in place.
3. Turn main line circuit breaker
(a)
to off “O”.
4. Turn convenience receptacle circuit breakers
(h,k)
to off “O”.
5. Move engine start switch to “REMOTE START” to check operation of engine
control module. The LCD panel should momentarily display
INITIALIZING
followed by
READY
and engine information. Check fuel level and battery
values.
Note:
The warning light
(p)
will flash if the fuel level is below 15%. This will not pre-
vent the engine from starting.
6. Press the emergency stop button
(p)
. The LCD panel should read
EMERGENCY STOP
. Pull out the emergency stop button after verifying the
display, and return the engine start switch to off “O”.
7. Start engine by moving the engine start switch to the “START/RUN” position.
8. After displaying
INITIALIZING
and
NOT IN AUTO
sequence, the LCD display
will read
START DELAY
followed by
CRANKING
as the engine begins its crank
cycle. The normal cycle is for the engine to crank for 12 seconds, then rest for
12 seconds. This cycle will repeat three (3) times.
9. If the engine does not start within this time, the engine control module will shut
down the engine and
OVERCRANK
will be displayed on the LCD panel.
CAUTION
Possibility of injury or equipment damage. Failure to match phase rotation and
voltage may cause equipment connected to the generator to operate incorrectly.
f
When using the generator as a standby or substitute power supply, make sure
the voltage and phase rotation of the line connections match those of the utility
lines or of any other power source normally used.
CAUTION
Possibility of accidental equipment start-up. If the contacts on any remote switch
linked to the generator are closed, the generator could start unexpectedly when the
engine start switch is moved to the REMOTE START position.
f
Before placing the engine start switch
(f)
in the REMOTE START position, verify
that the contacts on any remote switch linked to the generator set are OPEN.
Summary of Contents for 0620649
Page 1: ...5000185616 04 0911 5 0 0 0 1 8 5 6 1 6 Operator s Manual Mobile Generator G 100 G 120 EN ...
Page 5: ...G 100 G 120 Foreword wc_tx000994gb fm 5 ...
Page 6: ...Foreword G 100 G 120 6 wc_tx000994gb fm ...
Page 10: ...10 wc_bo5000185616_04TOC fm Table of Contents G 100 G 120 ...
Page 33: ...G 100 G 120 Lifting and Transporting wc_tx001191gb fm 33 Notes ...
Page 90: ...Technical Data G 100 G 120 90 wc_td000298gb fm Notes ...
Page 96: ......
Page 97: ......