21
COOLIUS A30
6.2 Output test
It is possible to activate the devices connected to the CPU/Power mainboard (board A).
NOTE:
Both quick couplers must be installed!
Use the
COOLIUS SELECT
to select the output that must be activated.
Press
ENTER
to activate the selected OUTPUT.
NOTE:
In order to avoid the exit of refrigerant from the vacuum pump outlet or from the Oil/UV bottles, the
activation of VP, UV, NO and of all the combinations containing at least one of them, are possible only when
the pressure is lower than 1100 mb.
• CP
Compressor and Compressor fan
• VP
Vacuum pump
The HP and LP gauges must show 0 (Zero) bar!
• EO
Drain oil valve
• UV
Dye tracer valve
The HP and LP gauges must show 0 (Zero) bar!
• NO
New oil valve
The HP and LP gauges must show 0 (Zero) bar!
• RF
Refrigerant valve
• XP
Recovery valve
• LP
Separation valve
• A1
Aggregate valve
• A2
Aggregate valve 2
• A3
Aggregate valve 3
• A4
Aggregate valve 4
• CP+XP
• VP+LP+A2
The HP and LP gauges must show 0 (Zero) bar!
• CP+XP+LP
• VP+LP+A2
The HP and LP gauges must show 0 (Zero) bar!