4.3 Timed/un-timed configuration. 

 

The timed/un-timed configuration can be changed from the configuration selected by the DIL switch setting. 

 

Timed/un-timed configuration is shown in the time area as t: 1 for timed operation and as t: 0 for un-timed operation. 

 

1.

 

Press MENU until Set icon and t: are displayed. 

2.

 

Current timed/un-timed configuration as set by DIL switch will be flashing. 

3.

 

Adjust timed/un-timed configuration using 

S

 and 

T

4.

 

Press OK to accept timed/un-timed configuration and advance to next item. 

 

4.4 Timer period day mode (timed mode only). 

 

Day mode is shown in the time area as d 1 for 1 day mode, d5:2 for 5/2 day mode and d 7 for 7 day mode. Likewise the day icons show as none for 1 day 

mode, alternating MoTuWeThFr and SaSu for 5:2 day mode and MoTuWeThFrSaSu for 7 day mode. 

 

1.

 

Press MENU until Set icon and d, in the time area, are displayed. 

2.

 

Day mode configuration will be flashing. 

3.

 

Adjust day mode configuration using 

S

 and 

T

4.

 

Press OK to accept day mode configuration and advance to next item. 

 

4.5 Temperature display mode (floor sensor only control mode). 

 

Temperature display mode is shown in the time area as F: 0 for °C display and as F: 1 for 0-13 scale display. 

 

1.

 

Press MENU until Set icon and F, in the time area, are displayed. 

2.

 

Temperature display mode configuration will be flashing. 

3.

 

Adjust temperature display mode configuration using 

S

 and 

T

4.

 

Press OK to accept temperature display mode configuration and advance to next item. 

 

4.6 Set PIN code. 

 

1.

 

Press MENU until Set icon, PADLOCK icon and 0000 are displayed. 

2.

 

The first 0 will be displayed flashing. 

3.

 

Adjust PIN digit 1 using 

S

 and 

T

4.

 

Press OK to accept digit 1. The second 0 will be displayed flashing. 

5.

 

Adjust PIN digit 2 using 

S

 and 

T

6.

 

Press OK to accept digit 2. The third 0 will be displayed flashing. 

7.

 

Adjust PIN digit 3 using 

S

 and 

T

8.

 

Press OK to accept digit 3. The fourth 0 will be displayed flashing. 

9.

 

Adjust PIN digit 4 using 

S

 and 

T

10.

 

Press OK to accept digit 4 and advance to next item in configuration menu. 

 

4.7 Reset to defaults. 

 

The control can be reset back to its default factory settings (including timer day mode, timer periods, control temperatures, default time and date etc) by using 

the reset function. 

 

To maintain safety the control will revert to the DIL switch settings, as set by the installer, for sensor configuration, timed/un-timed operation and the 

maximum floor temperature. 

 

1.

 

Press MENU until Set icon and dFLt in the time area are displayed. 

2.

 

Press OK to enable reset to defaults. 

3.

 

dFLt will be flashing. 

4.

 

Press OK to confirm reset to defaults and return to normal operation. 

 

5. User Settings 

 

The MENU button is used to access User Settings for change by the user. The button is pressed until the appropriate icons for the item to be changed are 

shown on the display. 

 

If the user stops programming part way through a process then after 1 minute the control will automatically return to normal operation. Settings changed up 

to that point will have been saved. 

 

The menu button will only present settings that are relevant to the timed mode of operation when that mode has been selected. 

 

The MENU button presents the settings in the following order: 

 

 

Enter PIN (PIN enabled only) 

 

Set tamper lock on or off (PIN not enabled only) 

 

Floor temperature display (room and floor sensor mode only) 

 

Set comfort temperature (timed mode only) 

 

Set savings temperature (timed mode only) 

 

Set minimum floor temperature (floor/room and floor sensor modes only) 

 

Set timer periods (timed mode only) 

 

Set time (timed mode only) 

 

Set date (timed mode only) 

 

Energy usage display 

 

Energy usage counter clearing 

 

 

Summary of Contents for Vysa-Therm 3000

Page 1: ...ng to open the control When timed operation is chosen the control uses a real time clock and timer periods to change the temperature between the comfort temperature and the savings temperature When un timed operation is chosen the control is set to the required temperature using S and T and controls to this temperature until it is manually adjusted OWNERS MANUAL Vysa Therm 3000 Electrical and elec...

Page 2: ...to meet your own requirements 5 1 Enter PIN security code PIN Enabled 5 2 Set the tamper lock PIN not enabled 5 3 Floor temperature display Room and floor sensor only 5 4 Set timer periods Timer operation only 5 4 1 Set timer periods 1 day mode 5 4 2 Set timer periods 5 2 day mode 5 4 3 Set timer periods 7 day mode 5 5 Set comfort temperature 5 6 Set savings temperature 5 7 Set minimum floor tempe...

Page 3: ...d 2 savings temperature starts 12 00 Timer period 3 comfort temperature starts 12 00 Timer period 4 savings temperature starts 23 00 2 3 Temperatures Default sensor mode is floor sensor only control from DIL switches Default temperature display mode is C Frost temperature is fixed as 5 C this is the floor or air temperature Savings temperature floor sensor only mode 20 C floor temperature Savings ...

Page 4: ...day mode the days are grouped into weekdays and weekends and one set of timer periods apply to all week days Monday Tuesday Wednesday Thursday and Friday whilst another set of timer periods apply to all weekend days Saturday and Sunday In 7 day mode each day has its own set of timer periods and each can be different All timer period configurations offer 4 timer periods per day 3 4 Maximum floor te...

Page 5: ...der Engineer Settings To access Engineer Settings press and hold the OK button then press the MENU button also Then press the MENU button until the appropriate icons for the item to be changed are shown on the display the variable being changed will be shown flashing ready for adjustment If the user stops programming part way through a process then after 1 minute the control will automatically ret...

Page 6: ...igit 1 using S and T 4 Press OK to accept digit 1 The second 0 will be displayed flashing 5 Adjust PIN digit 2 using S and T 6 Press OK to accept digit 2 The third 0 will be displayed flashing 7 Adjust PIN digit 3 using S and T 8 Press OK to accept digit 3 The fourth 0 will be displayed flashing 9 Adjust PIN digit 4 using S and T 10 Press OK to accept digit 4 and advance to next item in configurat...

Page 7: ... to 24 00 Timer period 4 timer period 3 to 24 00 This range of times gives flexibility to programming in particular if timer period 2 and timer period 3 are set as the same time then effectively there is only one comfort period for that day beginning at timer period 1 and ending at timer period 4 5 4 1 Set timer periods 1 day mode In 1 day mode the day icons are not used when setting timer periods...

Page 8: ...ntil Set and MOON and THERMOMETER icons are displayed If floor sensor only operation then the FLOOR THERMOMETER icon is displayed 2 Savings temperature will be flashing 3 Adjust temperature using S and T 4 Press OK to accept savings temperature and return to normal operation 5 7 Set minimum floor temperature floor sensor enabled only 1 Press MENU until Set and FLOOR THERMOMETER and Min icons are d...

Page 9: ...ng 5 Adjust PIN digit 2 using S and T 6 Press OK to accept digit 2 The third 0 will be displayed flashing 7 Adjust PIN digit 3 using S and T 8 Press OK to accept digit 3 The fourth 0 will be displayed flashing 9 Adjust PIN digit 4 using S and T 10 Press OK to accept digit 4 If the PIN entered is incorrect the control will return to normal operation but if the PIN is correct then the user adjustmen...

Page 10: ... operate the heater whatever the temperature When this mode is set only OFF is shown in the time display To set off mode press the O I button twice and OFF is displayed flashing in the time area Press OK to accept this mode To clear frost protection or off modes just press the O I button and normal control will resume 6 5 Constant comfort or savings temperature control timed mode only The control ...

Page 11: ... drain only occurs when the control is disconnected from the 240V mains supply with the battery in situ Its purpose is to maintain the time and date settings correctly until the control is installed or during power cuts At all other times when the 240 V mains supply is connected there is no current drain to cause the battery life to deteriorate We recommend changing the Coin Battery when the bad b...

Page 12: ...ation stored in non volatile EEPROM memory Connections 7 by 4 0 mm rising clamp screw terminal Live in Neutral in Live to load Neutral to load Earth no internal connection floor sensor signal floor sensor return Keypad buttons 6 silicon rubber S T OK MENU 24h O I LCD custom 16mm x 30mm 60 segment reflective no backlight see appendix DIL switch setting of operating modes by installer Switch 1 floor...

Reviews: