background image

Vysa-Therm™ 3000: 000807  

Vysal Limited. Unit 3 Lovett Farm, Little Somerford, Wiltshire, SN15 5BP. Tel : 01666 822059 Fax: 01666 822422 

Email: [email protected]     Web: www.floor-heating.co.uk  

7.2 Error displays. 

 

If unexpected conditions are detected by the control then an error code will be displayed. 

 

7.2.1 E2, thermostat overheats. 

 

If the room sensor detects a temperature of greater than 40°C then the control will turn off the heater output and display E2 until the fault is corrected. 

 

7.2.2 E4, floor sensor short circuit. 

 

If the control detects a floor sensor short circuit then the control will turn off the heater output and display E4 until the fault is corrected. 

 

7.2.3 E5, floor sensor open circuit. 

 

If the control detects a floor sensor open circuit then the control will turn off the heater output and display E5 until the fault is corrected. 

 

7.3 LCD Display 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8. Battery replacement. 

 

The battery is a high capacity 3 Volt Lithium Coin Battery with an expected lifetime of about 10 years under normal circumstances.  

 

Current drain only occurs when the control is disconnected from the 240V mains supply with the battery in-situ. Its purpose is to maintain the time and date 

settings correctly until the control is installed or during power cuts. At all other times when the 240 V mains supply is connected there is no current drain to 

cause the battery life to deteriorate.  

 

We recommend changing the Coin Battery when the bad battery symbol is displayed. The only loss of performance that will occur when the battery life has 

ended is the loss of time and date settings during a power cut. Otherwise there will be no effect. 

 

Please note that the control will ‘lose’ its time and date settings during battery replacement and the user will have to reset time and date after the new battery 

is fitted. 

 

Simply remove the front of the control to reveal the battery and then remove the ‘dead’ battery. Fit a new CR 2032 type battery and replace the front of the 

control. Then set the time and date as described under sections 5.8 and 5.9 above. 

 

timer

periods

frost

bad

battery

constant

operation

temperature

(bars for floor)

comfort

 

(day)

savings

(night) time date

child

lock

heater

on

manual

temperature

Max

Min

1
2

4

3

Set

MoTuWeThFrSaSu

24h

use

Hrs

Master

day icon 

Summary of Contents for Vysa-Therm 3000

Page 1: ...ng to open the control When timed operation is chosen the control uses a real time clock and timer periods to change the temperature between the comfort temperature and the savings temperature When un timed operation is chosen the control is set to the required temperature using S and T and controls to this temperature until it is manually adjusted OWNERS MANUAL Vysa Therm 3000 Electrical and elec...

Page 2: ...to meet your own requirements 5 1 Enter PIN security code PIN Enabled 5 2 Set the tamper lock PIN not enabled 5 3 Floor temperature display Room and floor sensor only 5 4 Set timer periods Timer operation only 5 4 1 Set timer periods 1 day mode 5 4 2 Set timer periods 5 2 day mode 5 4 3 Set timer periods 7 day mode 5 5 Set comfort temperature 5 6 Set savings temperature 5 7 Set minimum floor tempe...

Page 3: ...d 2 savings temperature starts 12 00 Timer period 3 comfort temperature starts 12 00 Timer period 4 savings temperature starts 23 00 2 3 Temperatures Default sensor mode is floor sensor only control from DIL switches Default temperature display mode is C Frost temperature is fixed as 5 C this is the floor or air temperature Savings temperature floor sensor only mode 20 C floor temperature Savings ...

Page 4: ...day mode the days are grouped into weekdays and weekends and one set of timer periods apply to all week days Monday Tuesday Wednesday Thursday and Friday whilst another set of timer periods apply to all weekend days Saturday and Sunday In 7 day mode each day has its own set of timer periods and each can be different All timer period configurations offer 4 timer periods per day 3 4 Maximum floor te...

Page 5: ...der Engineer Settings To access Engineer Settings press and hold the OK button then press the MENU button also Then press the MENU button until the appropriate icons for the item to be changed are shown on the display the variable being changed will be shown flashing ready for adjustment If the user stops programming part way through a process then after 1 minute the control will automatically ret...

Page 6: ...igit 1 using S and T 4 Press OK to accept digit 1 The second 0 will be displayed flashing 5 Adjust PIN digit 2 using S and T 6 Press OK to accept digit 2 The third 0 will be displayed flashing 7 Adjust PIN digit 3 using S and T 8 Press OK to accept digit 3 The fourth 0 will be displayed flashing 9 Adjust PIN digit 4 using S and T 10 Press OK to accept digit 4 and advance to next item in configurat...

Page 7: ... to 24 00 Timer period 4 timer period 3 to 24 00 This range of times gives flexibility to programming in particular if timer period 2 and timer period 3 are set as the same time then effectively there is only one comfort period for that day beginning at timer period 1 and ending at timer period 4 5 4 1 Set timer periods 1 day mode In 1 day mode the day icons are not used when setting timer periods...

Page 8: ...ntil Set and MOON and THERMOMETER icons are displayed If floor sensor only operation then the FLOOR THERMOMETER icon is displayed 2 Savings temperature will be flashing 3 Adjust temperature using S and T 4 Press OK to accept savings temperature and return to normal operation 5 7 Set minimum floor temperature floor sensor enabled only 1 Press MENU until Set and FLOOR THERMOMETER and Min icons are d...

Page 9: ...ng 5 Adjust PIN digit 2 using S and T 6 Press OK to accept digit 2 The third 0 will be displayed flashing 7 Adjust PIN digit 3 using S and T 8 Press OK to accept digit 3 The fourth 0 will be displayed flashing 9 Adjust PIN digit 4 using S and T 10 Press OK to accept digit 4 If the PIN entered is incorrect the control will return to normal operation but if the PIN is correct then the user adjustmen...

Page 10: ... operate the heater whatever the temperature When this mode is set only OFF is shown in the time display To set off mode press the O I button twice and OFF is displayed flashing in the time area Press OK to accept this mode To clear frost protection or off modes just press the O I button and normal control will resume 6 5 Constant comfort or savings temperature control timed mode only The control ...

Page 11: ... drain only occurs when the control is disconnected from the 240V mains supply with the battery in situ Its purpose is to maintain the time and date settings correctly until the control is installed or during power cuts At all other times when the 240 V mains supply is connected there is no current drain to cause the battery life to deteriorate We recommend changing the Coin Battery when the bad b...

Page 12: ...ation stored in non volatile EEPROM memory Connections 7 by 4 0 mm rising clamp screw terminal Live in Neutral in Live to load Neutral to load Earth no internal connection floor sensor signal floor sensor return Keypad buttons 6 silicon rubber S T OK MENU 24h O I LCD custom 16mm x 30mm 60 segment reflective no backlight see appendix DIL switch setting of operating modes by installer Switch 1 floor...

Reviews: