background image

VST5000W5028W

Wireless Survey Tools 

User Guide

August 30

th

, 2010

Summary of Contents for VST5000W5028W

Page 1: ...VST5000W5028W Wireless Survey Tools User Guide August 30th 2010...

Page 2: ...nal Strength Indicator Please note that it is normal for the value to fluctuate slightly up to 10 20 The final reading value is representative of the median averaged values displayed Any value from 10...

Page 3: ...plications such as going through stair ways but the design and optimization of the thermostat antenna is designed for optimal horizontal distance penetration and not a vertical one As such be prepared...

Page 4: ...at at least one thermostat is within 50 feet 15 M of the VWG for every cluster of 10 thermostats installed Always install the VWG closest to the center of all associated wireless thermostats Always lo...

Page 5: ...installed If possible perform the survey during occupied hours where other electronic devices such as computers wireless laptop cell phones PDA s wireless telephones microwave ovens light ballasts etc...

Page 6: ...ge radius of the coordinator VWG or Jace Driver at it s proposed location It s possible that another location may improve your network performance or that you may require an additional coordinator VWG...

Page 7: ...t t Fig 11 5 Then find the potential coverage radiuses through a few of the thermostats furthest away from the coordinator VWG or Jace Driver covered radius fig 10 6 Once the most difficult connectivi...

Page 8: ...from a parent device This ZigBee address is a value which is NOT initially exposed or available for the integrator to see Devices nodes controllers can calculate and assign addresses for their surrou...

Page 9: ...te ZigBee addresses to the other devices in building B Within Range Jac t t t t t t t t t t t t t t Jace Building A Building B Fig 12 5H stands for 5 hops maximum ANY given device node controller shou...

Page 10: ...and will force the node controller to try to re join a A A B B A B Jace Coordinator Proposed location Maximum linear distance covered by a single Jace Coordinator 20 20 20 20 20 Fig 14 5 Leave survey...

Page 11: ...the information contained therein is solely at the risk of the user Documentation may include technical or other inaccuracies or typographical errors Vykon reserves the right to make changes to this...

Page 12: ...VYKON 3951 Westerre Parkway Suite 350 I Richmond VA 23233 I USA Phone 804 747 4771 I Fax 804 747 5204 contact tridium com I www vykon com 028 0318 R0...