-2-
Start-up:
If the control lever is blocked (manual blocking, dirt, dust) the electronic system will fail! Now, there is the risk
of total discharge of the battery. On the other hand, the battery charge can be utilized completely in an
extreme case of emergency (positioning light, lighting etc.).
1. Application as pure protection against total discharge:
Disconnection:
a.) Automatically in case of total discharge (low voltage) e. g. below 10.7 V after 10 seconds.
b.) Automatically in case of overvoltage e. g. above 15.5 V after 10 seconds.
c.) Manual disconnection is possible by means of the control lever (main switch function). In this
case, restart is also to be effected manually.
Restart:
d.) Automatically after total discharge and battery recovery / battery charging e. g. over 12.5 V
e.) Automatically after overvoltage and decreasing voltage e. g.below 15 V
f.) Manually by actuation of the change lever „EMERGENCY“. If the battery voltage will again be
decreasing due to consumer load, the unit will be disconnected again! This procedure should not
be repeated unnecessarily often to maintain the longevity of the battery.
2. Additional application as main switch,
Remote control by means of switch ON / OFF in the living area:
This type of switching allows an effective remote control of the unit by means of a switch being located in the living area.
Since the load of the switch is very low (0.002 A), an execution as microswitch is sufficient.
If the switch is in position "OFF", the entire electronic system will be completely disconnected. The own electricity
consumption being anyhow very low is ceased.