Vibration monitoring table
Important note for installation purposes
According to the requirements of standard UNI EN 14986 Design of fans operating in potentially explosive
atmospheres; the Vortice C series appliances have a continuous operating curve within the Static
Pressure = 0 (Pa) and maximum Static Pressure; there are therefore no limits to operation under load for these
appliances.
The sensor/s for measuring vibrations must be positioned according to the following drawing:
Condition/Threshold
Fan category
ISO 14694
Assembly on
rigid support
mm/s
Assembly on
flexible support
mm/s
peak
r.m.s.
peak
r.m.s.
Start-up of
appliance/equipment
BV-3
6.4
4.5
8.8
6.3
Alarm
BV-3
10.2
7.1
16.5
11.8
Shutdown
BV-3
12.7
9.0
17.8
12.3
24
ENGLISH
Warning:
this symbol indicates that care must
be taken to avoid injury to the user
!
Summary of Contents for C ATEX
Page 128: ...Tipična uporaba Slika 1 3 Vgradnja Slika 4 10 128 SLOVENSKO ...
Page 166: ...166 II 2 Gb E xe IIC T3 IP54 D E xtb IIIC IP65 ...
Page 168: ...168 3 1 10 4 ...
Page 169: ...169 UE 34 2014 14986 2017 ...
Page 170: ...170 1 1 ...
Page 171: ...171 2014 34 UE 2014 34 UE ...
Page 173: ...173 ...
Page 174: ...174 ...
Page 175: ...175 2014 34 UE 2014 34 UE 12 11 12 11 ...
Page 177: ...177 3 3 9 4 4 5 5 6 6 ...
Page 178: ...178 7 7 8 8 9 9 10 10 16 11 11 12 12 ...
Page 179: ...179 Note ...