The general capacity should have been determined prior to
purchasing the transformer. Circuit loads should not exceed 80%
of capacity. As a general rule, total light fixture wattage should
not exceed 80% of the transformer capacity. To determine the
total wattage, simply add up the wattage of all fixture lamps.
This number should be 20% less than the transformer's wattage
capacity. If you need help with this, please call customer service
at
813-978-3700.
If you are over capacity, your installation may
require a secondary or larger transformer.