Check that all the fixtures are on and functioning properly.
Flickering or fixtures that aren't powered on could present a
connection problem at the fixture or lamp. If a failed lamp is
suspected, try replacing it with another that is working in a
different location. This will help you to troubleshoot where the
problem is.
www.voltlighting.com
Quick Start Step 11
Quick Start Step 12
Using a volt meter, measure the voltage at the fixtures by
removing the lamp and using the probes in the bulb receptacle.
Be sure that all the other lamps are installed at the time of
testing. For integrated fixtures, test voltage at the closest
connection point to the lighting fixture. A good range is typically
between 10.8 -15 volts for LED lighting fixtures.