background image

Supplied By www.heating spares.co  Tel. 0161 620 6677

26

UNICA BHE

fig. 37

7.4.2

GAS VALVE MINIMUM SETTING

Locate and gently turn the HTG trimmer till the
minimum value fan speed (max) is obtained and
check that it corresponds with the appropriate CO

2

value (Minimum) for the respective appliance. If
the CO

2

 reading is correct, rotate the HTG trim-

mer until the correct value is obtained for the re-
spective appliance (see fan speed table) and pro-
ceed to 7.4.3. However, if the CO

2

 reading is in-

correct, the minimum gas pressure must be ad-
justed as follows:

using a suitable screwdriver, very slowly turn the
minimum adjustment screw (see fig. 38) – clock-
wise to increase, counter clockwise to decrease
- until the correct value is displayed on the CO

2

analyser (allow time for the analyser to stabilise).

7.4.3

COMPLETION

On completion of the combustion analysis check
and/or any gas valve adjustment, set the HTG
trimmer to the corresponding value as detailed in
the fan speed table. Refit the 3-selector knobs and
move the mode selector to the OFF position.
Remove the test probe from the test point and refit
the sealing screw/s and/or cap.

IMPORTANT
A GAS TIGHTNESS CHECK MUST BE CAR-
RIED OUT IF ANY GAS CARRYING COMPO-
NENTS HAVE BEEN REMOVED, REPLACED
OR DISTURBED.

7.5

COMBUSTION ANALYSIS TEST

A combustion analysis check can easily be car-
ried out on the appliance via the test points located
on the top of the appliance (see 7.4).

Insert the flue gas analyser probe into the flue
gas test point (see fig. 35).

Operate the boiler in CO mode and compare the
values with those shown in section 2 (Nat. Gas)
or section 10 (LPG). If different adjust the gas
valve according to 7.4.1, 7.4.2, & 7.4.3.

7.6

CHECKING THE EXPANSION VESSEL

Carry out the component removal procedure as
described in 6.4. You must ensure that the boiler
is completely drained of water. Using a suitable
pressure gauge, remove dust cap on expansion
vessel and check the charge pressure.  The cor-
rect charge pressure should be 1.0 bar ± 0.1 bar.
If the charge pressure is less, use a suitable pump
to increase the charge.

NOTE

You must ensure the drain valve is in the open
position whilst re-charging takes place. Replace
the dust cap and carry out the relevant commis-
sioning procedure (section 5).

7.7

EXTERNAL FAULTS

Before carrying out any faultfinding or component
replacement, ensure the fault is not attributable to
any aspect of the installation.

7.7.1

INSTALLATION FAULTS

 Symptom

Possible cause

 No display/ignition

Check wiring/check electrical
supply

 No hot water

Check pipe-work

 No heating

Check external controls

 Fault code

Possible cause

 10

Check gas supply, check flue
system, check polarity

7.8

ELECTRICAL CHECKS

Any electrical checks must be carried out by a
suitably qualified person.

7.8.1

EARTH CONTINUITY TEST

Isolate the appliance from the electrical supply,
and using a suitable multi-meter carry out a resist-
ance test. Connect test leads between an appli-
ance earth point and the earth wire of the appliance
supply cable. The resistance should be less than
1 OHM. If the resistance is greater than 1 OHM
check all earth wires and connectors for continuity
and integrity.

7.8.2

SHORT CIRCUIT CHECK

Isolate the appliance from the electrical supply,
and using a suitable multi-meter, carry out a short
circuit test between the Live & Neutral connec-
tions at the appliance terminal strip (fig.17). Re-
peat above test on the Live & Earth connections
at the appliance terminal strip (fig.16).

NOTE

Should it be found that the fuse has failed but no
fault is indicated, a detailed continuity check will
be required to trace the fault. A visual inspection of
components may also assist in locating the fault.

7.8.3

POLARITY CHECK

With the appliance connected to the electrical
supply and using a suitable multimeter, carry out
the following voltage tests:

connect test leads between the Live & Neutral
connections at the appliance terminal strip (fig.16).
The meter should read approximately 230V ac.
If so proceed to next stage. If not, see 7.8.4.

connect test leads between the Live & Earth
connections at the appliance terminal strip (fig.16).
The meter should read approximately 230V ac.
If so proceed to next stage. If not, see 7.8.4.

connect test leads between the Neutral & Earth
connections at the appliance terminal strip (fig.16).
The meter should read approximately 0 – 15Vac.
If so polarity is correct. If not, see 7.8.4.

7.8.4

REVERSED POLARITY OR SUPPLY FAULT

Repeat the above tests at the appliance isolator,
if testing reveals correct polarity and/or supply at
the isolator, re-check wiring and connections be-
tween the isolator and the appliance. If tests on the
isolator also reveal reversed polarity or a supply
fault, consult the local electricity supplier for
advice.

7.8.5

RESISTANCE TO EARTH CHECK

Isolate the appliance from the electrical supply, and
using a suitable multi-meter carry out a resistance
test. Connect test leads between the Live & Earth
connections at the appliance terminal strip (fig. 16).
If the meter reads other than infinity there is a fault
that must be isolated, carry out a detailed continuity
check to identify the location of the fault.

Maximum

screw

Minimum

screw

Compensation

pipe connection

Summary of Contents for Unica BHE

Page 1: ...SE INSTRUCTIONS TO BE RETAINED BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK...

Page 2: ...5 Pre operation checks 17 5 6 Initiallighting 17 5 7 Checking gas pressure combustion analysis 17 5 8 Final flushing of the heating system 18 5 9 Setting the boiler operating temperature 18 5 10 Setti...

Page 3: ...ith an annular co axial combustion air intake that can be rotated horizontally through 360 degrees for various horizontal or vertical applications The Unica BHE can also be used with the Vokera twin f...

Page 4: ...stic hot water to be pre heated DHW temperature selector Move the selector clockwise to increase the hot water outlet temperature or counter clockwise to reduce the temperature Heating temperature sel...

Page 5: ...irement When the appliance reaches the desired tempera ture the burner will shut down and the boiler will perform a three minute anti cycle timer delay When the request for heat has been satisfied the...

Page 6: ...ht kg 2 6 Clearances UNICA BHE Range Sides Left 12mm Right 25mm Top 150mm from casing or 25mm above flue elbow whichever is applicable Bottom 150mm Front 600mm 2 7 Connections UNICA BHE Range Flow ret...

Page 7: ...he car port into the building 1200 mm M Vertically from a terminal on the same wall 1500 mm N Horizontally from a terminal on the same wall 300 mm P From a structure to the side of the vertical termin...

Page 8: ...5440 PART 1 FLUES BS 5440 PART 2 FLUES VENTILATION BS 5449 PART 1 FORCED CIRCULATION HOT WATER SYSTEMS BS 5546 INSTALLATION OF GAS HOT WATER SUPPLIES FOR DOMESTIC PURPOSES BS 6798 INSTALLATION OF BOI...

Page 9: ...r see fig 5A The cold feed from the make up vessel or tank must be fitted with an approved non return valve and stopcock for isolation purposes The feed pipe should be connected to the return pipe as...

Page 10: ...g must be considered If installed less than 2m above a pavement or platform to which people have access including balconies or flat roofs the terminal must be protected by a guard of durable material...

Page 11: ...fitted in accordance with I S 813 and local Building Regulations The Institute of Gas Engineers publication IGE UP 7 Guide for Gas Installations in Timber Frame Buildings gives specific advice on this...

Page 12: ...iance has been decided using the template supplied carefully mark the position of the wall mounting bracket see fig 8 and flue hole if applicable If you intend to run the pipe work vertically behind t...

Page 13: ...A 524 45 degreebends pair N A 525 500mmextension 500mm 526 1000mmextension 1000mm 527 2000mextension 2000mm 528 Telescopic extension 350 730mm 529 Wall bracket pack 5 208mm Using the template provide...

Page 14: ...move any burrs and check that all seals are lo cated properly You must ensure that the entire flue system is properly supported and connected Seal the flue assembly to the wall using cement or a suita...

Page 15: ...n that of a concentric flue system It can be used for horizontal or vertical applications however the twin flue system must be converted to the dedi cated concentric flue kit for termination It is ess...

Page 16: ...onto the concentric to twin converter ensuring that the exhaust pipe connects to the exhaust connection on the con centric to twin converter If necessary cut the plain ends male of the twin flue pipe...

Page 17: ...GAS fig 16 The appliance is supplied with a 15mm service valve connect a 15mm pipe to the inlet of the valve and tighten both nuts NOTE Itwillbenecessarytocalculatethediameterofthe gas supply pipe to...

Page 18: ...HE AP PLIANCE The supply cable from the isolator to the appliance must be 3 core flexible sized 0 75mm to BS 6500 or equivalent Wiring to the appliance must be rated for operation in contact with sur...

Page 19: ...er and system from the lowest points Open the drain valve full bore to remove any installation debris from the boiler prior to lighting Refill the boiler and heating system as described in 5 3 5 5 PRE...

Page 20: ...rate restrictor that limits the maximum flow rate that can be drawn through the appliance The restrictor eliminates the need to manually adjust the DHW flow rate However if it is felt necessary to fur...

Page 21: ...romanydebrisorobstruction Check and clean if necessary the condense trap to ensure correct operation 6 3 REPLACEMENTOFCOMPONENTS Although it is anticipated that this appliance will give years of relia...

Page 22: ...t component removal procedure as de scribed in 6 4 Unclip and remove the air chamber front cover Unclip the return thermistor from the return inlet pipe Disconnect thermistor electrical plug Replace i...

Page 23: ...crews A for electrode and remove Remove the retaining nut C for condense sensor D and remove 6 15 BURNER fig 30 Carry out component removal procedure as described in 6 4 Unclip and remove the air cham...

Page 24: ...C and condense connections on the heatexchanger Locateandremovethe4 screws thatsecuretheheatexchangertothecombustion chamber D Movetheheatexchangertotheright and disconnect it from the flue collector...

Page 25: ...TUATOR fig 35B Carry out component removal procedure as de scribed in 6 4 Remove the locking pin F that secures the actuator G to the heating manifold Disconnect the electrical plug from the actuator...

Page 26: ...l other functions are disabled minimumpoweroperatingperiod anti cycle set point etc Once enabled the CO function will remain active for a 15 minute pe riod oruntilthefunctionismanuallydeactivated FROS...

Page 27: ...led on the appliance data badge 7 3 1 CHECKING ADJUSTINGTHEAPPLIANCEFAN SPEEDS Move the selector switch to the OFF position and remove the 3 selector knobs 7 3 2 ABSOLUTE MAX FAN SPEED Locate the MAX...

Page 28: ...eck wiring check electrical supply No hot water Check pipe work No heating Check external controls Fault code Possible cause 10 Check gas supply check flue system check polarity 7 8 ELECTRICALCHECKS A...

Page 29: ...W ON hysterisis C SP 3 Anti cycle delay 3 min Pump over run 30 sec Low output min output Min 25 CO function max temp C 95 CO re light temp C 75 CO function time 15 min Flow NTC max temp C 95 High limi...

Page 30: ...ntact Vokera technical fordetailedinstructiononspecificOT controls vokera external sensor 8 3 OTHERDEVICES Contactthecontrolsmanufacturerand orVokera technical department should you require more speci...

Page 31: ...onnection to PCB low voltage F O H T Flow over heat thermostat F T Fume thermostat G Cable connector M3 M5 Terminal strip for supply in clock room thermostat M2 M4 Terminal strip for condense pump low...

Page 32: ...028557 26 Instrumental panel 20011082 27 Knob assembly R10028559 31 Instrumental panel 20011393 40 Door panel R10030136 64 Frame assembly R10028809 65 Case cover 20011392 67 Wiring box R01005468 78 Hi...

Page 33: ...R5041 248 Washer R5208 265 Washer R5236 266 Washer R5237 290 Clip R2165 292 O ring R7999 351 Nut R1823 353 Nut R1824 636 Detector 20004978 24 201 26 40 200 7 201 265 30 200 201 2 292 4 202 636 22 31...

Page 34: ...19 Glass stopper assembly R10026328 27 Plug R10023805 35 Air gas conveyor R10028420 39 Pipe 20000769 46 Gas diaphragm R10027161 67 Washer 62 R10026322 69 Tryton R10028425 72 Mixer R10024295 79 Flame...

Page 35: ...ing exchanger assembly R01005366 7 Conveyor R10028623 12 Flue drain connection R10028421 27 Nut screw R10020625 475 Washer 125 R10026323 482 Washer R10026366 487 Washer 60 R10026345 552 Washer 60 R100...

Page 36: ...ance from the electrical supply and remove the appliance casing as described in 4 7 1 Set the flue gas analyser to read CO2 and inserttheprobeintotheflueanalysistestpoint A B fig 35 Restore the electr...

Page 37: ...ted according to the respective appliance specifica tion as detailed on the appliance data badge 10 7 1 CHECKING ADJUSTINGTHEAPPLIANCEFAN SPEEDS Move the selector switch to the OFF position and remove...

Page 38: ...ns and or BS5546 BS6798 Yes ALL INSTALLATIONS If required by the manufacturer record the following CO2 OR CO ppm OR CO CO2 Ratio The heating and hot water system complies with the appropriate Building...

Page 39: ...CORGI ID Number Comments Signature SERVICE 7 Date Energy Efficiency Checklist completed Yes No Engineer Name Company Name Telephone Number CORGI ID Number Comments Signature SERVICE 9 Date Energy Effi...

Page 40: ...ies vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 099 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reserve th...

Reviews: