VOKERA AriaPRO 004 M User Instructions Download Page 32

Flow switch status

111

This code displays the Flow Switch status:

0. Water not “owing

1. Water “owing  

-

-

Heat climatic curve 

number

112

This code is use to select the heat climatic curve number:

0. No predefined climatic curve (Installer has to draw CC)

1-12. Refers to Control panel manuals for climatic curve details.  

0

12

0

Heat water set-point

113

This code is use to set the fixed heating water set-point.  

20°C

60°C

45°C

Eco heat temperature 

reduction

114

This code is use to set the temperature reduction value for fixed heating water 

set-point when the unit is in ECO mode.  

1°C

20°C

5°C

Cool water set-point

115

This code is use to set the fixed cooling water set-point.  

4°C

25°C

7°C

Eco cool temperature 

reduction

116

This code is use to set the temperature reduction value for fixed cooling water 

set-point when the unit is in ECO mode.  

1°C

10°C

5°C

Cool climatic number

117

This code is use to select the cool climatic curve number:

0. No predefined climatic curve (Installer has to draw CC)

1 - 2. Refers to Control panel manuals for climatic curve details  

0

2

0

Min outdoor air tempera-

ture heating

118

This code is use to select the minimum outdoor temperature of the heating 

climatic curve, depending on the country where the system is installed.  

20°C

+10°C

-7°C

Max outdoor air tempera-

ture heating

119

This code is use to select the maximum outdoor temperature of the heating 

climatic curve.  

10°C

30°C

20°C

Min water temperature 

heating

120

This code is use to select the minimum water temperature of the heating climatic 

curve.  

20°C

60°C

40°C

Max water temperature 

heating

121

This code is use to select the maximum water temperature of the heating climatic 

curve.  

20°C

60°C

55°C

Max outdoor air tempera-

ture cooling

122

This code is use to select the maximum outdoor temperature of the cooling 

climatic curve, depending on the country where the system is installed.  

24°C

46°c

40°C

Min outdoor air tempera-

ture cooling

123

This code is use to select the minimum outdoor temperature of the cooling 

climatic curve.  

0°C

30°C

22°C

Min water temperature 

cooling

124

This code is use to select the minimum water temperature of the cooling climatic 

curve.  

4°C

20°C

4°C

Max water temperature 

cooling

125

This code is use to select the maximum water temperature of the cooling climatic 

curve.  

4°C

20°C

12°C

Gmc oat thermistor

126

This code is use to define if GMC OAT thermistor is installed or not

1. GMC thermistor installed

2. GMC thermistor not installed  

1

2

2

To sensor value

127

This code displays the outdoor air temperature value read by the TO sensor.  

-

-

-

Lock

Te sensor value

128

This code displays the refrigerant temperature value read by the TE sensor.  

-

-

-

Lock

Ts sensor value

129

This code displays the suction temperature value read by the TS sensor.  

-

-

-

Lock

Td sensor value

130

This code displays the discharge temperature value read by the TD sensor.  

-

-

-

Lock

Cdu mode

131

This code displays the actual Heat Pump operating mode:

1. Off

2. Cool

3 Heat

4. Fail

5. Defrost  

-

-

-

Lock

Max compressor fre-

quency

132

This code displays the maximum compressor frequency calculated by GMC 

control board.  

-

-

-

Lock

Requested frequency

133

This code displays the requested frequency by the system control.  

-

-

-

Lock

Real frequency

134

This code displays the real compressor frequency  

-

-

-

Lock

Compressor runtime

135

This code displays the working on hours of the compressor.  

-

-

-

Lock

Cdu capacity

136

This code displays the nominal heat pump capacity [kW].  

-

-

-

Lock

Ewt sensor value

137

This code displays the Entering Water Temperature read by the EWT sensor.  

-

-

-

Lock

Lwt sensor value

138

This code displays the Leaving Water Temperature read by the LWT sensor.  

-

-

-

Lock

Tr sensor value

139

This code displays the refrigerant temperature value read by the TR sensor.  

-

-

-

Lock

System mode

140

This code displays the operating mode requested by the System Control:

0. Off

1. Stand by

2. Cooling

3. Heating

4. N.A.

5. N.A.

6. Rating Heating

7. Rating Cooling

8. Freeze Protection

9. Defrost

10. High Temperature Protection

11. Time guard

12. System Fail  

-

-

-

Lock

Def module

141

This code displays the list of the all fault codes detected by the outdoor unit. If no 

fault are occurring, no codes will be displayed.  

-

-

-

Lock

Gmc software version

142

This code displays the GMC Software Version  

-

-

-

Lock

Gmc software release

143

This code displays the GMC Software Release  

-

-

-

Lock

Water pump runtime

144

This code displays the working on hours of the water pump.  

-

-

-

Lock

Current water set-point

145

This code displays the current water set-point defined by the system control.  

-

-

-

Lock

Dry contact off

146

This code is use to set the different OFF logics:

1. Standard OFF

2. Controlled Off Cycle (only if HP is controlled by dry contact)  

1

2

1

Alarm / satisfied air room 

temperature

147

This code is use to select the output connected at PIN 5 on terminal strip:

1. Alarm signal

2. Signal of reached air temperature set-point  

1

2

1

External heat source oat 

limit

148

This code is use to set the OAT threshold value under which only the external heat 

source will be operative as per algorithm. (Stop HP)  

-20°C

65°C

-20°C

Temperature list

149

This code is use to set which temperature the Control panel shall display in 

temperature zone.

1. Indoor air temperature

2. Leaving water temperature (from LWT sensor)

3. Entering water temperature (from EWT sensor)

4. Refrigerant temperature (from TR sensor)  

1

7

1

Auxiliary oat limit

150

This code is use to set the OAT threshold value under which both the heat pump 

and the external heat source will be operative as per algorithm.  

-20°C

30°C

0°C

Auxiliary delay

151

This code is use to set the delay time after which, when (temperature set in code 

148) < OAT < (temperature set in code 150), the external heat source will switch 

on . The counting of the time starts when the activation of the EHS is required 

as per algor  

1 Min

60 Min

10 Min

Auxiliary hysteresis

152

This code is use to set the hysteresis temperature needed to activate the external 

heat source.  

1°C

20°C

5°C

Sanitary hot water in off 

mode

153

This code is use to define if, when system mode is off, the sanitary hot water logic 

can be activated:

1. Yes, SHW logic is always actives

2. No, SHW logic can be activated only in Heat or Cool mode  

1

2

1

  

 
 

 32

  

Summary of Contents for AriaPRO 004 M

Page 1: ...ctions Installation Servicing Instructions THESEINSTRUCTIONS TOBERETAINED BYUSER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioni...

Page 2: ...2...

Page 3: ...modify or tamper with this equipment as doing so might cause dangerous situation for which the manufacturer waives all liability In the installation and or maintenance operations please adopt the appr...

Page 4: ...ance Climate control Titolo_fittizio The AriaPRO range units are designed for the production of refrigerated water for air conditioning heated water for heating and sanitary hot water for homes reside...

Page 5: ...4 4 Energy class 7 B Generalities Sound pressure in heating 1 dB A 42 44 47 48 Sound pressure in cooling 7 dB A 44 45 48 49 Compressor Rotary DC Inverter Tecnology R410a refrigerant charge kg 1 195 1...

Page 6: ...hot water production may be limited according to the settings of the safety devices in the equipment For technical activities please refer to the technical tag mounted on board the machine It is forbi...

Page 7: ...44 1 8 2 16 2 52 2 88 3 24 10 20 30 40 50 60 70 80 90 A B AriaPro 006 M AriaPro 004 M AriaPro 008 M AriaPro 012 M 015 M 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 0 2 0 3 0 4 0 5 0 1 0 0 Dimensions Ti...

Page 8: ...2 1 49CF 2 1 50CF 3 2 1 51CF 2 1 3 L N PE 1TS 1TO 1TD 1TE 1PMV 004 M Power Wiring of the manufacturer Field wiring CM Compressor motor FM Fan engine RV Reversing valve 4 way TS Probe temperature low p...

Page 9: ...1 2 31CF 1 2 32CF 7 6 5 4 3 2 1 33CF 1 2 3 4 5 6 34CF 7 6 5 4 3 2 1 35CF 1 2 3 4 36CF 1 2 3 4 5 6 37CF 1 2 3 4 5 3TB C W G Y 23 24 1 2TB N 18 10 11 12 5TB 21 22 3 6 7 8 2 4TB 4 5 16 13 14 15 N 38CF 1...

Page 10: ...10 J4 1 2 03 J3 1 2 08 J1 1 1FM 1CM R S C 40CF 1 2 3 7CM 1 2 3 1R 41CF 2 1 8CM 2 1 2T 1 2 P25 P24 P23 P22 P21 P20 P35 P34 P19 P18 P04 P05 P06 1P C BOARD P11 P08 1MCC 1530 42CF 1 2 3 43CF 1 2 3 P33 P32...

Page 11: ...1 2 31CF 1 2 32CF 7 6 5 4 3 2 1 33CF 1 2 3 4 5 6 34CF 7 6 5 4 3 2 1 35CF 1 2 3 4 36CF 1 2 3 4 5 6 37CF 1 2 3 4 5 3TB C W G Y 23 24 1 2TB N 18 10 11 12 5TB 21 22 3 6 7 8 2 4TB 4 5 16 13 14 15 N 38CF 1...

Page 12: ...1 50Hz 1FM 6CM R S C 40CF 1 2 3 7CM 1 2 3 1R 41CF 2 1 8CM 2 1 2T 1 2 P25 P24 P23 P22 P21 P20 P35 P34 P19 P18 P04 P05 P06 1P C BOARD P11 P08 1MCC 1530 42CF 1 2 3 43CF 1 2 3 P33 P32 2R 44CF 2 1 9CM 2 1...

Page 13: ...J6B 1 J6B 2 J6B 1 J6B 2 J18 1 J18 2 J11 7 J11 6 J11 5 J11 4 J11 3 J11 2 J11 1 10 58CF 1 2 3 4 5 6 J16 1 J16 2 59CF 1 2 3 4 5 J5 1 11 J16 3 J5 2 J16 4 J5 3 12 J16 5 J5 4 J16 6 3TB J5 5 C 60CF 7 6 5 4...

Page 14: ...PE 1F 1 2 L 1RV N 39CF 1 2 3 40CF 1 2 3 4 5 CN01 CN02 CN03 1P C BOARD 2P C BOARD 7CM 1 2 3 41CF 1 2 3 P08 42CF 1 2 3 4 5 43CF 1 2 3 4 5 1PVM 44CF 1 2 3 4 5 6 2TB P09 8CM 1 2 3 45CF 1 2 3 P12 P13 46CF...

Page 15: ...1 J6B 2 J6B 1 J6B 2 J18 1 J18 2 J11 7 J11 6 J11 5 J11 4 J11 3 J11 2 J11 1 10 68CF 1 2 3 4 5 6 J16 1 J16 2 69CF 1 2 3 4 5 J5 1 11 J16 3 J5 2 J16 4 J5 3 12 J16 5 J5 4 J16 6 4TB J5 5 C 70CF 7 6 5 4 3 2 1...

Page 16: ...SW801 CN704 BLUE SW800 RY704 P04 CN701 WHITE P05 CONTROL P C BOARD MCC 1571 P06 CN04 WHITE P07 CN200 F03 T10A 250V F01 T25A 250V CN201 P01 L F P02 CN202 P09 1TB 2TB 1 2 3 J4 1 2 10 J3 1 2 03 J1 1 2 08...

Page 17: ...F 1 2 31CF 1 2 32CF 7 6 5 4 3 2 1 33CF 1 2 3 4 5 6 34CF 7 6 5 4 3 2 1 35CF 1 2 3 4 36CF 1 2 3 4 5 6 37CF 1 2 3 4 5 4TB C W G Y 23 24 1 3TB N 18 10 11 12 6TB 21 3 6 7 8 2 5TB 4 5 16 13 14 15 N 38CF 1 2...

Page 18: ...entially hazardous packaging materials within the reach of children Scope of supply Also supplied Installer manual External probe Barcode labels Control panel Strain relief size 015M only List of spar...

Page 19: ...discomfort That the airflow from the unit is opposed by a contrary wind The units must Be placed on a level surface able to support their weight Be placed on a sufficiently rigid floor slab that does...

Page 20: ...ing agents or subject to special regulations require the use of water disconnectors Failure to install filters flow meter and anti vibrating mounts can cause obstruction breakage and noise issues for...

Page 21: ...Ground the unit thoroughly At the end of the connections fasten the cables with the appropriate cable glands and replace the terminal boxes covers Do not use gas and water pipes to ground the unit Co...

Page 22: ...aximum length of the connecting cable must be taken into account Use a shielded cable for the connection The connection cable must not be spliced if splicing is necessary it shall be tinned and adequa...

Page 23: ...r s oil to warm up Position the remote switch if present in the on position Start the equipment according to the directions in the control panel section Checks during and after the first commissioning...

Page 24: ...indoors can generate toxic gases if they come into contact with naked flames or high temperature bodies in case of leaks please air the rooms thoroughly Do not charge the refrigerating circuits with a...

Page 25: ...d time START TIME Activates the programming menu displaying the beginning of the six periods of time scheduled PERIOD Activates the programming menu displaying the six periods of time scheduled DAYS A...

Page 26: ...nge parameter Activate the arrow keys Set the current value Push the OK key to confirm Setting of room temperature Push the mode key Select the desired operation mode Activate the arrow keys Set the d...

Page 27: ...you press the OK key the settings shall be saved and the value of the parameter shall start blinking with the possibility of changing it later on If you press the Mode key the settings shall be saved...

Page 28: ...50 55 60 65 7 8 9 10 11 12 1 2 0 5 10 15 20 15 20 25 30 35 40 45 C C x y x 2 Customised Climate Curves Parameters 112 and 117 set at zero make it possible to load a customised curve in the control Th...

Page 29: ...etition of the abnormal operation requires an accurate check of the unit s components Before resetting it is necessary to remove the cause of the anomaly Abnormal operations are notified by the Contro...

Page 30: ...ompressor disorder etc Discharge temp error Power supply error Heat sink overheat error Gas leak detection 4 way valve reverse error High pressure protective operation Fan system error Driving element...

Page 31: ...he arrow for Sleep 12 C 38 C 26 C Away heat t 19 AWAY Temperature set point in Heating mode C and the arrow for Away 12 C 38 C 15 C Away cool t 20 AWAY Temperature set point in Cooling Mode C and the...

Page 32: ...k Max compressor fre quency 132 This code displays the maximum compressor frequency calculated by GMC control board Lock Requested frequency 133 This code displays the requested frequency by the syste...

Page 33: ...al wp logic 156 This code is use to select the output connected at PIN 11 on terminal strip In case an additional water pump option is active this code is use to select its operating logic vs the SHW...

Page 34: ...34...

Page 35: ...35...

Page 36: ...enquiries vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited res...

Reviews: