CONNECTOR PIPE INSTALLATION

1.  The smooth end of the stovepipe fits over the 

cast iron flue collar at top rear of stove (fig. 5).

 

a).  Crimped end of pipe must be away from 
stove.

 

b).  Hand form lower end (fig. 6) of stove pipe 
to oval shape (fig. 7) and slide over flue outlet 
collar as shown in figure 5.

 

c).  Secure stove pipe to flue collar with  
at least three (3) sheet metal screws and seal 
with stove cement. 

2.  Horizontal pipe runs must slope upwards  

towards the chimney at least 1/4” per foot of 
horizontal run.

3.  You must have at least 18 inches of clearance 

between any horizontal piping and the ceiling.

4.  The pipe cannot extend into the chimney flue 

(figure 8).

5.  Secure pipe/elbow sections with three (3) 

sheet metal screws at each joint to make the 
piping rigid. 

Screws may be no more than a maxi-

mum of 3˝/76mm apart.

6.  It is recommended that no more than two (2) 

90 degree bends be used in the stovepipe in-
stallation. The use of more than two 90 degree  
bends may decrease the amount of draw and 
possibly cause smoke spillage. Where pos-
sible, use only corrugated (nonadjustable) 
elbows. These provide a better seal.

7.  The connector pipe must not pass through 

an attic or roof space, trusses, closet, or any 
concealed space, or floor, ceiling, wall or com-
bustible construction. (See Chimney Connector 

NOTE: CONNECTOR PIPE IS 

NOT INCLUDED

.  

TO PURCHASE PIPE, VISIT YOUR LOCAL 
HARDWARE, HOME OR BUILDING CEN-
TER. SEE “LOCATING STOVE” PAGE 4 FOR  
ADDITIONAL SPECIFICATIONS.

CAUTION: KEEP FURNISHINGS AND OTHER  
COMBUSTIBLE MATERIALS AWAY FROM THE 
STOVE.

Fig. 5 –  Flue Outlet Collar

Fig. 6 –  Hand-form pipe to oval shape – Fig. 7

CORRECT WRONG  WRONG

Fig. 8 – Stovepipe/Flue Connections

Systems & clearances, page 10.) A UL 103 HT 
Listed chimney system 

must 

be used from the 

first penetration of ceiling or wall to the chimney 
cap. Use chimney components from a single 
manufacturer. Do not mix brands.

WARNING: DO NOT USE SINGLE WALL CON-
NECTOR PIPE AS A CHIMNEY - A HOUSE FIRE 
COULD RESULT.

Summary of Contents for PB65XL

Page 1: ...S STOVE FAILURE TO FOLLOW INSTRUC TIONS MAY RESULT IN PROPERTY DAMAGE BODILY INJURY OR EVEN DEATH THIS STOVE IS NOT A UL LISTED STOVE NOTE IT IS RECOMMENDED INSTALLATION BE COMPLETED BY A QUALIFIED HEATING EQUIPMENT INSTALLER DO NOT INSTALL IN A MOBILE HOME REFER TO MARKINGS ON STOVE LABELS FOR ADDITIONAL INFORMATION SAFETY NOTICE IF THIS STOVE IS NOT PROPERLY INSTALLED A HOUSE BUILDING FIRE MAY R...

Page 2: ... system listed to UL 103 HT Residential Type and Building Heating Appli ance Chimney Use a 6 152mm diameter chim ney that is high enough to give a good draft See specifics in Chimney Connections instructions 11 Be sure that your chimney is safely constructed and in good repair Have the chimney inspected by the fire department or a qualified inspector Your insurance company should be able to recommend...

Page 3: ... HEAT ING AND COOLING CONTRACTOR MUST BE CONSULTED IF YOU HAVE QUESTIONS REGARDING THE INSTALLATION OF THIS SOLID FUEL BURNING APPLIANCE 18 This stove has a painted surface which is durable but it will not stand rough handling or abuse When installing your stove use care in handling 19 Clean exterior with soap and warm water when stove is not hot Do not use any acids or scouring soap as these solv...

Page 4: ...ht section of stove pipe fig 1 exiting the stove before the stove is used a Drill two 1 4 holes centered on either side of the pipe section 6 from the top end of the pipe figure 1 b Remove the handle from the damper then slide the damper into the pipe c Align the damper with the holes drilled in step 9a and insert the handle through the holes and the damper NOTE THIS DAMPER IS NECESSARY FORTHE PROPE...

Page 5: ...D ADDITIONAL FLOOR PROTECTION REQUIRED BACKWALL 54 TOP VIEW 36 18 18 18 36 63 18 SIDEWALL COMBUSTIBLE CONSTRUCTION ACCORDING TO NFPA 211 COMBUSTIBLE CONSTRUCTION ACCORDING TO NFPA 211 6 152mm i d ma nu fa cured chimney system listed to UL 103 HT Maximum 64 square inches 4 Use 6 152mm diameter minimum 24 MSG Black or 26 MSG Blue round stove pipe DO NOT USE GALVANIZED duct pipe Secure pipe sections ...

Page 6: ...e than two 2 90 degree bends be used in the stovepipe in stallation The use of more than two 90 degree bends may decrease the amount of draw and possibly cause smoke spillage Where pos sible use only corrugated nonadjustable elbows These provide a better seal 7 The connector pipe must not pass through an attic or roof space trusses closet or any concealed space or floor ceiling wall or com bustible...

Page 7: ...e trees terrain and chimney temperature can have an adverse effect on the draft The manufacturer cannot be held responsible for external factors leading to less than optimal drafting Should you have a problem with inadequate draft you should contact a licensed heating and cooling contractor for assistance in solving the problem IMPORTANT Installation Points 1 Size chimney flue to stove collar This ...

Page 8: ...rmation on line See www duravent com www selkirkinc com or www mtlfab com VENTING TO EXISTING FIREPLACE In some instances people desire to convert an ex isting fireplace for stove use Usually safe connection to an existing masonry chimney requires more work than using a prefabricated chimney The existing fireplace must be closed and sealed at the damper with high temperature caulk ceramic wool or fu...

Page 9: ...sitioning the center of the stove pipe entry into the chimney 24 below the ceiling should insure proper clearance for a 6 stovepipe 2 Install a metal or fire clay 5 8 minimum thickness thimble Make sure the thimble is flush with the inner surface of the chimney liner and does not protrude into the flue see figure 8 on page 6 3 Secure the thimble with refractory mortar The thimble should be surrounded ...

Page 10: ...s separated from combustibles by a minimum of 6 152mm of glass fiber insulation Opening shall be covered and thimble supported with a sheet steel support minimum 24 gauge in thickness D Chimney Section Pass through Solid insulated listed factory built chimney length with an inside diameter 2 51mm larger than the chimney connector and having 1 25 4mm or more of insulation serving as a pass through f...

Page 11: ... be air dried sea soned for a minimum of 6 months Logs greater than 6 in diameter should be split Wood should be stored in a dry well ventilated area The humidity content for usable firewood must be less than 20 of the weight of the log Attempts to use wet or unseasoned wood will cause ignition problems rapid creosote build up with possible chimney fire incomplete combustion low heat yield Chestnut ...

Page 12: ...e Dispose of ashes properly See Safety Instructions 14 page 2 CHIMNEY DRAFT Draft is a function of the chim ney not the stove do not expect the stove to draw Smoke spillage into the house or excessive buildup of condensation or creosote in the chimney are warnings that the chimney is NOT functioning properly Correct the problem before using the stove Following are some possible causes for improper...

Page 13: ...T CONTROL AND FLUE PIPE DAMPER 2 GET OUT OF THE HOUSE 3 CALL THE FIRE DEPARTMENT SOOT Formation need for Removal CAUTION RISK OF FIRE When coal is burned the products of combustion combine with moisture to form a soot residue which accumu lates in the flue lining When ignited this soot makes an extremely hot fire The chimney connector and chimney should be inspected at least once every two months du...

Page 14: ... identify parts Contact us at 616 396 1911 to order parts Part No Description Qty 1 Cook Lid 1 2 Lid Lifter 1 3 Collar Top 1 4 Top Plate 1 5 Upper Chamber 1 6 Feed Chamber 1 7 Feed Door 1 8 Spin Draft 1 9 Spring Handle 1 10 Burn Chamber 1 11 Shaker Door 1 Part No Description Qty 12 Shaker Grate 1 13 Lower Chamber 1 14 Base 1 15 Leg 4 16 Ash Door 1 17 Slide Draft 1 18 Slide Draft Knob 1 19 Ash Draw...

Page 15: ...protector a Use formulas in step 1 above to calculate R value of proposed material s b For multiple layers add R values of each layer to determine overall R value 3 If the overall R value of the floor protector system is equal to or greater than the floor protector specifications given the alternate is acceptable Definitions Thermal conductance C BTU W hr ft2 F m2 K Thermal conductivity k Btu inch W B...

Page 16: ...s and must be treated with respect Stay warm and in good health Respectfully yours Proprietor Vogelzang International Corporation 400 West 17th Street Holland Michigan 49423 www vogelzang com Phone 1 616 396 1911 Fax 1 616 396 1971 COMPANY TESTIMONY FOR GOD SO LOVED THE WORLD THAT HE GAVE HIS ONLY BEGOTTEN SON THAT WHOEVER BELIEVES IN HIM SHALL NOT PERISH BUT HAVE ETERNAL LIFE JOHN 3 16 MADE IN CH...

Reviews: