background image

Page 8

 / BX42E-SN 

 

VGZ-005 / 20120202.0

www.vogelzang.com

CONNECTOR  PIPE INSTALLATION

Figure 9 – Stovepipe/Flue Connections

 CORRECT 

WRONG 

WRONG

Connector pipe is used to make the connection 

from the final positioning of your stove to an approved 
chimney. Connector pipe is 

NOT

 included as part of 

the stove. Connector pipe must be 6˝/152mm diameter 
minimum of 24 MSG (minimum standard gauge) black 
or 26 MSG blue steel stove pipe. Any connector pipe 
used must be in good condition. Replace if necessary 
before using stove. Connector pipe is not rated to pro-
vide close contact to combustible materials and must 
have proper clearance from combustible materials 
as shown in the clearance diagrams on the previous 
pages. Connector pipe should never be used in place 
of a chimney. If proper clearances are not observed a 
house fire could result.

Installation Instructions

1.  The smooth end of the stovepipe fits over the stove 

flue collar. Secure with three (3) sheet metal screws. 
The first section of connector pipe must be single 
walled to properly attach to the stove collar. Install 
additional pipe and elbow with the crimped end 
towards the stove. This will allow any condensation 
in the flue to run back into the firebox.

2.  Hor izontal pipe r uns must slope upwards  

towards the chimney at least 1/4˝(6.4mm) per foot 
of horizontal run.

3.  You must have at least 18˝/457mm of clearance 

between any horizontal piping and the ceiling.

4.  The pipe cannot extend into the chimney flue  

(figure 9).

5.  Secure pipe/elbow sections with three sheet metal 

screws at each joint to make the piping rigid.

6.  It is recommended that no more than two (2) 

90° bends be used in the stovepipe installa-
tion. The use of more than two 90° bends may 
decrease the amount of draw and possibly 
cause smoke spillage. Where possible, use only  
corrugated (non adjustable) elbows. These  
provide a better seal.

7.  The connector pipe must not pass through an  

attic or roof space, trusses, closet, or any concealed 
space, floor, ceiling, wall, or combustible construc-
tion. (See Chimney Connector Systems & Clear-
ances, page 17.) A UL 103 HT Listed chimney must 
be used from the first penetration of ceiling or wall 
to the chimney cap. 

CAUTION: NEVER USE SINGLE WALL CON-
NECTOR PIPE AS A CHIMNEY - A HOUSE FIRE 
COULD RESULT. 

NOTE: CONNECTOR PIPE IS 

NOT INCLUDED

.  

TO PURCHASE, VISIT YOUR LOCAL HARD-
WARE, HOME, OR BUILDING CENTER.  
SEE “LOCATING STOVE” PAGE 6 & 7 FOR  
ADDITIONAL SPECIFICATIONS.

Summary of Contents for DELUXE BOXWOOD BX42E

Page 1: ...ichigan 49423 www vogelzang com Phone 1 616 396 1911 Fax 1 616 396 1971 DELUXE BOXWOOD STOVE Model BX42E Owners Manual save this manual for future reference NOTE THIS STOVE IS NOT A UL LISTED STOVE READ ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS STOVE FAILURE TO FOLLOW INSTRUC TIONS MAY RESULT IN PROPERTY DAMAGE BODILY INJURY OR EVEN DEATH REFER TO MARKINGS ON STOVE LABELS FOR ...

Page 2: ...sonry or an Underwriters Laboratories Listed UL 103 HT Residential Type and Building Heating Appliance Chimney Use a 6 152mm diameter chimney that is high enough to give a good draft See specifics in Chimney Connections instructions 10 Be sure that your chimney is safely constructed and in good repair Have the chimney inspected by the fire department or a qualified inspector Your insurance company sh...

Page 3: ...UNLESS SPECIFICALLY APPROVED FOR SUCH INSTALLATIONS 30 A WOOD BURNING STOVE MUST NEVER BE INSTALLED IN A HALLWAY OR NEAR A STAIR CASE as it may block egress in the event of a fire 31 DO NOT INSTALL IN A SLEEPING ROOM SAFETY INSTRUCTIONS continued DO NOT INSTALLTHIS UNIT IN AN ALCOVE OR INSIDE A FIREPLACE 32 Install at least one smoke detector on each floor of your home Detectors should be located aw...

Page 4: ...erating Instructions House Fire Hazards Operating Precautions Warnings 12 Wood Types Sizes 12 Starting a Fire 12 Adding Fuel 13 Service Hints Creosote Formation Prevention Need for Removal 13 Stove Joints 14 Gasket Replacement 14 Parts Deluxe Boxwood 15 Floor Protector Calculations 16 Chimney Connection Systems Clearances 17 NOTE A PROFESSIONAL LICENSED HEAT ING AND COOLING CONTRACTOR MUST BE CONS...

Page 5: ... Flooring Protection 52 x 74 as specified see page 3 Chimney Connection 6 black steel 24 ga min straight or elbow as required 1 2 Sheet Metal Screws Chimney Existing 6 Lined Ma sonry Chimney or 6 Inside Dia listed Type HT chimney Furnace Cement manufacturer recommends Rutland Code 78 or equivalent NOTICE Vogelzang International Corp grants no warranty stated or implied for the installation or maint...

Page 6: ...th ods see page 16 Floor protector must extend at least 18 beyond the front of the hearth to the sides and beyond the rear of the stove The area under a horizontal run of the chimney connector must also be protected extending two 2 inched beyond the outer dimension of the horizontal connector The minimum sized floor protector for this stove is 52 x 74 Consult local building codes and fire protection...

Page 7: ...ng codes or fire protection ordinances NOTE ANY WALL CONTAINING COMBUSTI BLEMATERIALSUCHASWOODENSTUDSOR DRYWALLANDFACEDWITHBRICKORSTONE MUST BE CONSIDERED A COMBUSTIBLE SURFACE 6 DO NOT INSTALL THIS STOVE IN A MOBILE HOME MANUFACTURED HOME TRAILER OR TENT NO EXCEPTIONS HUD Federal Stan dard 24 CFR Ch XX Figure 7 Minimum Clearance Dimensions from Combustible Surfaces 7 The clearances provided are m...

Page 8: ...h the crimped end towards the stove This will allow any condensation in the flue to run back into the firebox 2 Horizontal pipe runs must slope upwards towards the chimney at least 1 4 6 4mm per foot of horizontal run 3 You must have at least 18 457mm of clearance between any horizontal piping and the ceiling 4 The pipe cannot extend into the chimney flue figure 9 5 Secure pipe elbow sections with th...

Page 9: ...verse effect on the draft The manufacturer cannot be held responsible for external factors leading to less than optimal drafting Should you have a problem with inadequate draft you should contact a licensed heating and cooling con tractor for assistance in solving the problem IMPORTANT Installation Points 1 Size chimney flue to stove collar This stove requires a minimum of a 6 152mm diameter flue 2...

Page 10: ...c com or www mtlfab com VENTING TO EXISTING FIREPLACE In some instances people desire to convert an ex isting fireplace for stove use Usually safe connection to an existing masonry chimney requires more work than using a prefabricated chimney The existing fireplace must be closed and sealed at the damper with high temperature caulk ceramic wool or furnace cement Prior to installation clean and inspe...

Page 11: ... installer 1 An entry hole must be cut through the masonry and tile liner with minimal damage to the liner At least 8 of liner must remain below the entry position When locating the stove and stovepipe all minimum clear ances must be observed from combustible surfaces including mantels combustible trimwork ceilings and walls Positioning the center of the stove pipe entry into the chimney 24 below ...

Page 12: ... fire is burning briskly Use care not to smother the kindling fire when adding wood Close the door and secure tightly 6 Adjust the collar draft damper and door spin draft control The more closed the spin draft is set the lower and slower the fire will burn The more open the faster and hotter the fire will burn Do not over fire the stove continued on next page CAUTION HOUSE FIRE HAZARDS s 4 34 2 7 2 02 ...

Page 13: ...ORS OR STOVE GLOWS RED IMMEDIATELY CLOSE THE DOOR DAMPER AND SPIN DRAFTTO RE DUCETHE AIR SUPPLY AND SLOW DOWNTHE FIRE TOO MUCH WOOD OR BURNING NON RECOMMENDED MATERIALS SUCH AS TRASH OR FLAMMABLE LIQUIDS MAY CAUSE OVER FIRING continued on next page CAUTION DO NOT OVER FIRE APPLIANCE CAUTION SLOW BURNING FIRES AND EX TENDED USE MAY CAUSE EXCESSIVE CREO SOTE BUILDUP IGNITION OF CREOSOTE BUILDUP OR O...

Page 14: ...w Smoke spillage into the house or excessive buildup of condensation or creosote in the chimney are warnings that the chimney is NOT functioning properly Correct the problem before using the stove Following are some possible causes for improper draft 1 The connector stovepipe may be pushed into the chimney too far stopping the draft 2 If the chimney temperature is too cool water will condense in t...

Page 15: ... identify parts Contact us at 616 396 1911 to order parts Part No Description Qty 42 01 Leg 4 42 02 Bottom 1 42 03 Side 2 42 04 Back 1 42 05 Front 1 42 06 Door 1 42 07 Top 1 42 08 Damper Slide Draft 1 42 09 Lid 2 42 10 Lid Support 1 42 11 Hearth 1 42 12 Damper Collar Assembly 1 42 13 Handle Assembly 1 42 14 Lid Lifter L 1 1 42 15 42 16 S Hook used to hang lid lifter 1 42 17 Spin Draft 1 42 18 Door...

Page 16: ...tector a Use formulas in step 1 above to calculate R value of proposed material s b For multiple layers add R values of each layer to determine overall R value 3 If the overall R value of the floor protector system is equal to or greater than the floor protector specifications given the alternate is acceptable Definitions Thermal conductance C BTU W hr ft2 F m2 K Thermal conductivity k Btu inch W Btu ...

Page 17: ...ls separated from combustibles by a minimum of 6 152mm of glass fiber insulation Opening shall be covered and thimble supported with a sheet steel support minimum 24 gauge in thickness D Chimney Section Pass through Solid insulated listed factory built chimney length with an inside diameter 2 51mm larger than the chimney connector and having 1 25 4mm or more of insulation serving as a pass through ...

Page 18: ... be treated with respect Stay warm and in good health Respectfully yours Proprietor COMPANY TESTIMONY Vogelzang International Corporation 400 West 17th Street Holland Michigan 49423 www vogelzang com Phone 1 616 396 1911 Fax 1 616 396 1971 FOR GOD SO LOVED THE WORLD THAT HE GAVE HIS ONLY BEGOTTEN SON THAT WHOEVER BELIEVES IN HIM SHALL NOT PERISH BUT HAVE ETERNAL LIFE JOHN 3 16 MADE IN CHINA SteveV...

Reviews: