Vogelzang International BK150E Owner'S Manual Download Page 8

Page 8 

/ BK150E

 

Vogelzang International Corp.

 

VGZ-024 / 20120410.2

Fig. 9 - Chimney Construction Through Roof

Fig. 10 - Chimney Connection to Firebox  

Through Noncombustible (Masonry) Wall

ChImNEY CONNECTIONS continued …

mANUFACTURED CHImNEY

R E F E R  TO   C H I m N E Y   A N D   C H I m N E Y 
CONNECTOR mAKER’S INSTRUCTIONS 
FOR INSTALLATION AND USE.

continued on next page

Use only a 6˝ diameter manufactured chimney sys-

tem listed to UL 103 HT. Chimney made to this listing 
is High Temperature rated to 2100 degrees Fahrenheit. 
Use chimney from only one manufacturer. Never mix 
brands. Carefully follow the chimney manufacturer’s 
stated requirements and clearances. Use the chimney 
manufacturer’s attic guards, roof supports, flashing and 
fire stops when passing through a ceiling. Use a listed 

thimble when passing through a combustible wall. Do 
not use makeshift compromises during installation. 

wARNING: DO NOT USE SINGLE wALL CON-
NECTOR PIPE AS A CHImNEY - A HOUSE FIRE 
COULD RESULT.

When using a pre-existing chimney, have it’s condi-

tion and installation inspected before using. Make sure 
that the chimney meets all of the UL rating require-
ments listed above. Be aware that not all manufactured  
chimney is of the UL 103 HT type.

NOTE: It is recommended that you contact a  

licensed heating and cooling contractor (consult your 
local yellow pages) for chimney installation.

Manufactured chimney with the proper required UL 

listing is available from most home centers, hardware 
stores, and HVAC supply stores.

If you have access to the internet, you may wish 

to view chimney manufacturers’ information on-line. 
See, www.duravent.com, www.selkirkinc.com, or www.
mtlfab.com.

VENTING TO EXISTING FIREPLACE

In some instances, people desire to convert an ex-

isting fireplace for stove use. Usually, safe connection to 
an existing masonry chimney requires more work than 
using a prefabricated chimney. The existing fireplace 
must be closed and sealed at the damper with high-
temperature caulk, ceramic wool, or furnace cement. 
Prior to installation, clean and inspect the existing flue 
and smoke shelf. Installation should be designed so 
the system can be dismantled for periodic cleaning and 
inspection. Before conversion, make sure the existing 
chimney is structurally sound, the chimney incorporates 
a flue liner and make sure it is in good condition. (A flue 
liner consists of clay tile that protects the brickwork of 
a chimney. If a chimney does not have a liner, or it is 
damaged, have it relined by a professional. 

DO NOT 

USE a chimney that is unlined or damaged!) If you 
have any question regarding the condition of the chim-
ney, consult a qualified licensed contractor, qualified 
engineer, competent mason, certified Chimney Sweep, 
or a knowledgeable inspector. Consult your insurance 
company if you cannot find a qualified expert.

CAUTION: NOT ALL FIREPLACE CHImNEYS 
ARE SUITABLE FOR CONVERSION TO ACCOm-
mODATE CONNECTION TO A wOOD STOVE. 
CHECK wITH A qUALIFIED EXPERT.

Many prefabricated fireplaces are of the “zero-

clearance fireplace” category. These consist of 
multi layered metal construction. They are designed 
with enough insulation and/or air cooling on the 
base, back and sides so they can be safely in-
stalled in direct contact with combustible floors and 
walls. Although many prefabricated fireplaces carry  

Summary of Contents for BK150E

Page 1: ... 17th Street Holland Michigan 49423 www vogelzang com Phone 1 616 396 1911 Fax 1 616 396 1971 Deluxe BARREL stove KIT Model BK150E Owners Manual save this manual for future reference Do NOT install this stove in a mobile home Manufactured Home tent or trailer NO EXCEPTIONS NOTE This stove is NOT a UL listed stove NOTE A professional licensed heat ing and cooling contractor should be consulted if y...

Page 2: ...ve to a chimney and vent the outside Never vent to another room or in side a building DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE 10 Do NOT connect a Wood burning stove to an aluminum Type B gas vent This is not safe Use approved masonry or an Underwriters Laborato ries Listed UL 103 HT Residential Type and Building Heating Appliance Chimney Use a 6 152mm diameter chimney ...

Page 3: ... discoloration will occur if the stove is over fired 19 Clean stove frequently as soot creosote and ash may accumulate 20 Alert all persons to the hazards of high surfacetemperatures while stove is in operation especially young children Keep away from a hot stove to avoid burns or clothing ignition 21 DO NOT leave small children unsupervised when they are in the same room as the stove If small chi...

Page 4: ...otection Install on non combustible soil or con crete floor Non combustible floor protection must be pro vided under any connector pipe extending 2 on either side Chimney Connector Pipe round 6 dia minimum 24 MSG black or 26 MSG blue steel stove pipe straight and or elbow s as required 1 2 Sheet Metal Screws Chimney Existing 6 Lined Ma sonry Chimney or 6 Inside Dia listed Type HT chimney Furnace C...

Page 5: ...ll stove pipe elbows and thimble as required utilizing either a recently cleaned and inspected code approved 6 masonry chimney with flue liner or a 6 i d maximum 64 square inch listed chimney 4 Use 6 round black stove pipe Do Not use gal vanized pipe Secure pipe sections with three 3 sheet metal screws in each stove pipe and or elbow joint to firmly hold the pipe sections together Screws should be...

Page 6: ...ey flue figure 6 5 Secure pipe elbow sections with three sheet metal screws at each joint to make the piping rigid Screws should be spaced no more than a maximum of 3 76mm apart 6 It is recommended that no more than two 2 90 bends be used in the stovepipe installa tion The use of more than two 90 bends may decrease the amount of draw and possibly cause smoke spillage Where possible use only corrug...

Page 7: ...y available at stove stores and are economi cal to rent or purchase Factors such as wind barometric pressure trees terrain and chimney temperature can have an adverse effect on the draft The manufacturer cannot be held responsible for external factors leading to less than optimal drafting Should you have a problem with inadequate draft you should contact a licensed heating and cooling contractor f...

Page 8: ... chimney manufacturers information on line See www duravent com www selkirkinc com or www mtlfab com Venting to Existing Fireplace In some instances people desire to convert an ex isting fireplace for stove use Usually safe connection to an existing masonry chimney requires more work than using a prefabricated chimney The existing fireplace must be closed and sealed at the damper with high tempera...

Page 9: ...nces must be observed from combustible surfaces including mantels combustible trim work ceilings and walls Positioning the center of the stove pipe entry into the chimney 24 below the ceiling should insure proper clearance for a 6 stovepipe 2 Install a fire clay 5 8 minimum thickness thimble Make sure the thimble is flush with the inner surface of the chimney liner and does not protrude into the f...

Page 10: ...ess having two 1 25 4mm air channels separated from combustibles by a minimum of 6 152mm of glass fiber insulation Opening shall be covered and thimble supported with a sheet steel support minimum 24 gauge in thickness D Chimney Section Pass through Solid insulated listed factory built chimney length with an inside diameter 2 51mm larger than the chimney connec tor and having 1 25 4mm or more of i...

Page 11: ...7 NEVER build extremely large fires in this type of barrel stove as damage to the barrel stove or smok ing may result 8 If you have too much draft then regulate the draft with the 6 cast iron stove pipe damper in the damper collar 9 DO NOT TOUCH the barrel stove after firing until it has cooled continued on next page CAUTION HOUSE FIRE HAZARDS Do not store wood on floor protec tor underneath stove...

Page 12: ...on Inspect stove and pipe every 60 days Replace immediately if stovepipe is rusting or leaking smoke into the room CAUTION Slow burning fires and ex tended use may cause excessive creo sote buildup Ignition of creosote buildup or over firing may cause a chimney fire Chimney fires burn ex tremely hot and may ignite surround ing materials In case of a chimney fire immediately LEAVE THE BUILDING AND ...

Page 13: ...pected by a qualified expert before using again ASH DISPOSAL Do not allow ashes to accumu late higher than the optional grate Dispose of properly See Safety Instructions 14 page 2 Chimney Draft Draft is a function of the chim ney not the stove do not expect the stove to draw Smoke spillage into the house or excessive buildup of condensation or creosote in the chimney are warnings that the chimney ...

Page 14: ...parts list provided to identify parts Contact us at 616 396 1911 to order parts Ref Part No No Description Qty 1 DC100 Damper Collar 1 2 150 2 Leg Assembly 2 3 150 3 Door Pin 2 4 150 4 Door Latch 1 5 150 5 Cool Touch Ball Knob 1 6 150 6 Door Bracket 1 7 150 7 Hardware Bag 1 11 150 11 Door Frame 1 12 150 12 Door 1 13 GK 14 Door Gasket 1 14 GK 14 Spin Dial Door Gasket 1 15 150 15 Spin Dial 2 16 150 ...

Page 15: ...vice performed by description The chimney connector and chimney should be inspected at the beginning of and at least twice a month during the heating season to determine if a creosote buildup has occurred Use this chart to record inspection maintenance service to help schedule necessary service ...

Page 16: ...and must be treated with respect Stay warm and in good health Respectfully yours Proprietor Vogelzang International Corporation 400 West 17th Street Holland Michigan 49423 www vogelzang com Phone 1 616 396 1911 Fax 1 616 396 1971 Company Testimony For God so loved the world that he gave his only begotten Son that whoever believes in Him shall not perish but have eternal life John 3 16 MADE IN CHIN...

Reviews: