Vogelzang International BK150E Owner'S Manual Download Page 12

Page 12 

/ BK150E

 

Vogelzang International Corp.

 

VGZ-024 / 20120410.2

OPERATINg INSTRUCTIONS continued …

10. 

NEVER OVER FIRE this barrel stove by building 
excessively hot fires as a house/building fire may 
result.

11.

 Inspect stove pipe and barrel every 60 days. 

Replace immediately if there is rusting or smoke 
leaking into the room.

12.  If barrel stove begins to glow or turn red, you are 

over firing the barrel stove. Immediately adjust spin 
draft to the 

closed position and turn 6” cast iron 

damper to a fully 

closed position. This will limit the 

amount of air being allowed into the barrel and will 
reduce the burn rate of the fire.

ADDING FUEL

Add small amounts of fuel each hour or so  

instead of piling large quantities of fuel at one 
time. This will insure a more complete combustion  
process and less buildup of tars, soot, or creosote will 
occur in the chimney.
1.  Always open draft damper before opening the feed 

door.

2.  When adding fuel be careful not to smother the fire.
3.  Close the feed door and secure tightly.
4.  Adjust the damper and spin draft control.
5.  Empty ashes regularly. Do not allow ashes to pile 

up higher than lower edge of the spin draft. 

6.  Properly dispose of hot ashes (see Safety  

Instructions, item #14 on page 2.)

7.  Do not over fire the stove (see step #12 above).

OPERATING SAFETY PRECAUTIONS

NEVER OVER FIRE THIS STOVE BY BUILD-
ING EXCESSIVELY HOT FIRES AS A HOUSE/
BUILDING FIRE mAY RESULT. YOU ARE OVER 
FIRING THE STOVE IF STOVE OR STOVEPIPE 
BEGINS TO GLOw OR TURN RED.

NEVER BUILD EXTREmELY LARGE FIRES IN 
THIS TYPE OF STOVE AS DAmAGE TO THE 
STOVE OR SmOKE LEAKAGE mAY RESULT.

STOVE IS HOT wHILE IN OPERATION. KEEP 
CHILDREN, CLOTHING, AND FURNITURE  
AwAY FROm HOT STOVE. CONTACT mAY 
CAUSE SKIN BURNS. DO NOT TOUCH THE 
STOVE AFTER FIRING UNTIL IT HAS COOLED.

PROVIDE AIR INTO THE ROOm FOR PROPER 
COmBUSTION.

INSPECT STOVE AND PIPE EVERY 60 DAYS. 
REPLACE ImmEDIATELY IF STOVEPIPE IS 
RUSTING OR LEAKING SmOKE INTO THE 
ROOm.

CAUTION: SLOw BURNING FIRES AND EX-
TENDED USE mAY CAUSE EXCESSIVE CREO-
SOTE BUILDUP. IGNITION OF CREOSOTE 
BUILDUP OR OVER FIRING mAY CAUSE A 
CHImNEY FIRE. CHImNEY FIRES BURN EX-
TREmELY HOT AND mAY IGNITE SURROUND-
ING mATERIALS. IN CASE OF A CHImNEY FIRE 
ImmEDIATELY LEAVE THE BUILDING AND 
CALL THE FIRE DEPARTmENT FROm A SAFE 
LOCATION.

CREOSOTE – FORmATION AND NEED FOR 
REmOVAL

CAUTION: RISK OF FIRE when wood is burned 
slowly, it produces tar and other organic va-
pors, which combine with expelled moisture to 
form creosote. The creosote vapors condense 
in the relatively cool chimney flue of a slow-
burning fire. As a result, creosote residue ac-
cumulates on the flue lining. when ignited this 
creosote makes an extremely hot fire.

The chimney connector, heat transfer barrel 
and chimney should be inspected at least once 
every two months during the heating season to 
determine if a creosote buildup has occurred.

If creosote has accumulated (3mm or more) 
it should be removed to reduce the risk of a 
chimney fire.

Failure to remove creosote may result in ignition 

and may cause a house/building fire. Creosote may be 
removed using a chimney brush or other commonly 
available materials from your local hardware retailer.

Chimney fires burn very hot. If the unit or chimney 

connector should glow red,  reduce the fire by clos-
ing the inlet air control and immediately call the fire 
department.

CAUTION: A CHImNEY FIRE mAY CAUSE IGNI-
TION OF wALL STUDS OR RAFTERS wHICH 
wERE ASSUmED TO BE A SAFE DISTANCE 
FROm THE CHImNEY. IF A CHImNEY FIRE 
HAS OCCURRED, HAVE YOUR CHImNEY IN-
SPECTED BY A qUALIFIED EXPERT BEFORE 
USING AGAIN.

A fire in the firebox may be smothered by pouring 

a large quantity of coarse salt, baking soda, or cool 
ashes on top of the fire.

PREVENTING CREOSOTE BUILDUP

1.  Creosote will inevitably form in your chimney and 

connector pipe.  Following these steps will help 
reduce the rate of build up.

Summary of Contents for BK150E

Page 1: ... 17th Street Holland Michigan 49423 www vogelzang com Phone 1 616 396 1911 Fax 1 616 396 1971 Deluxe BARREL stove KIT Model BK150E Owners Manual save this manual for future reference Do NOT install this stove in a mobile home Manufactured Home tent or trailer NO EXCEPTIONS NOTE This stove is NOT a UL listed stove NOTE A professional licensed heat ing and cooling contractor should be consulted if y...

Page 2: ...ve to a chimney and vent the outside Never vent to another room or in side a building DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE 10 Do NOT connect a Wood burning stove to an aluminum Type B gas vent This is not safe Use approved masonry or an Underwriters Laborato ries Listed UL 103 HT Residential Type and Building Heating Appliance Chimney Use a 6 152mm diameter chimney ...

Page 3: ... discoloration will occur if the stove is over fired 19 Clean stove frequently as soot creosote and ash may accumulate 20 Alert all persons to the hazards of high surfacetemperatures while stove is in operation especially young children Keep away from a hot stove to avoid burns or clothing ignition 21 DO NOT leave small children unsupervised when they are in the same room as the stove If small chi...

Page 4: ...otection Install on non combustible soil or con crete floor Non combustible floor protection must be pro vided under any connector pipe extending 2 on either side Chimney Connector Pipe round 6 dia minimum 24 MSG black or 26 MSG blue steel stove pipe straight and or elbow s as required 1 2 Sheet Metal Screws Chimney Existing 6 Lined Ma sonry Chimney or 6 Inside Dia listed Type HT chimney Furnace C...

Page 5: ...ll stove pipe elbows and thimble as required utilizing either a recently cleaned and inspected code approved 6 masonry chimney with flue liner or a 6 i d maximum 64 square inch listed chimney 4 Use 6 round black stove pipe Do Not use gal vanized pipe Secure pipe sections with three 3 sheet metal screws in each stove pipe and or elbow joint to firmly hold the pipe sections together Screws should be...

Page 6: ...ey flue figure 6 5 Secure pipe elbow sections with three sheet metal screws at each joint to make the piping rigid Screws should be spaced no more than a maximum of 3 76mm apart 6 It is recommended that no more than two 2 90 bends be used in the stovepipe installa tion The use of more than two 90 bends may decrease the amount of draw and possibly cause smoke spillage Where possible use only corrug...

Page 7: ...y available at stove stores and are economi cal to rent or purchase Factors such as wind barometric pressure trees terrain and chimney temperature can have an adverse effect on the draft The manufacturer cannot be held responsible for external factors leading to less than optimal drafting Should you have a problem with inadequate draft you should contact a licensed heating and cooling contractor f...

Page 8: ... chimney manufacturers information on line See www duravent com www selkirkinc com or www mtlfab com Venting to Existing Fireplace In some instances people desire to convert an ex isting fireplace for stove use Usually safe connection to an existing masonry chimney requires more work than using a prefabricated chimney The existing fireplace must be closed and sealed at the damper with high tempera...

Page 9: ...nces must be observed from combustible surfaces including mantels combustible trim work ceilings and walls Positioning the center of the stove pipe entry into the chimney 24 below the ceiling should insure proper clearance for a 6 stovepipe 2 Install a fire clay 5 8 minimum thickness thimble Make sure the thimble is flush with the inner surface of the chimney liner and does not protrude into the f...

Page 10: ...ess having two 1 25 4mm air channels separated from combustibles by a minimum of 6 152mm of glass fiber insulation Opening shall be covered and thimble supported with a sheet steel support minimum 24 gauge in thickness D Chimney Section Pass through Solid insulated listed factory built chimney length with an inside diameter 2 51mm larger than the chimney connec tor and having 1 25 4mm or more of i...

Page 11: ...7 NEVER build extremely large fires in this type of barrel stove as damage to the barrel stove or smok ing may result 8 If you have too much draft then regulate the draft with the 6 cast iron stove pipe damper in the damper collar 9 DO NOT TOUCH the barrel stove after firing until it has cooled continued on next page CAUTION HOUSE FIRE HAZARDS Do not store wood on floor protec tor underneath stove...

Page 12: ...on Inspect stove and pipe every 60 days Replace immediately if stovepipe is rusting or leaking smoke into the room CAUTION Slow burning fires and ex tended use may cause excessive creo sote buildup Ignition of creosote buildup or over firing may cause a chimney fire Chimney fires burn ex tremely hot and may ignite surround ing materials In case of a chimney fire immediately LEAVE THE BUILDING AND ...

Page 13: ...pected by a qualified expert before using again ASH DISPOSAL Do not allow ashes to accumu late higher than the optional grate Dispose of properly See Safety Instructions 14 page 2 Chimney Draft Draft is a function of the chim ney not the stove do not expect the stove to draw Smoke spillage into the house or excessive buildup of condensation or creosote in the chimney are warnings that the chimney ...

Page 14: ...parts list provided to identify parts Contact us at 616 396 1911 to order parts Ref Part No No Description Qty 1 DC100 Damper Collar 1 2 150 2 Leg Assembly 2 3 150 3 Door Pin 2 4 150 4 Door Latch 1 5 150 5 Cool Touch Ball Knob 1 6 150 6 Door Bracket 1 7 150 7 Hardware Bag 1 11 150 11 Door Frame 1 12 150 12 Door 1 13 GK 14 Door Gasket 1 14 GK 14 Spin Dial Door Gasket 1 15 150 15 Spin Dial 2 16 150 ...

Page 15: ...vice performed by description The chimney connector and chimney should be inspected at the beginning of and at least twice a month during the heating season to determine if a creosote buildup has occurred Use this chart to record inspection maintenance service to help schedule necessary service ...

Page 16: ...and must be treated with respect Stay warm and in good health Respectfully yours Proprietor Vogelzang International Corporation 400 West 17th Street Holland Michigan 49423 www vogelzang com Phone 1 616 396 1911 Fax 1 616 396 1971 Company Testimony For God so loved the world that he gave his only begotten Son that whoever believes in Him shall not perish but have eternal life John 3 16 MADE IN CHIN...

Reviews: