
3.6.2 General Purpose Input Output Module MCB 101
MCB 101 is used for extension of the number of digital and analog inputs
and outputs of the VLT Automation VT Drive.
Contents: MCB 101 must be fitted into slot B in the VLT Auto-
mation VT Drive.
•
MCB 101 option module
•
Extended LCP frame
•
Terminal cover
Galvanic Isolation in the MCB 101
Digital/analog inputs are galvanically isolated from other inputs/outputs on the MCB 101 and in the control card of the drive. Digital/analog outputs in
the MCB 101 are galvanically isolated from other inputs/outputs on the MCB 101, but not from these on the control card of the drive.
If the digital inputs 7, 8 or 9 are to be switched by use of the internal 24 V power supply (terminal 9) the connection between terminal 1 and 5 which is
illustrated in the drawing has to be established.
Illustration 3.20: Principle Diagram
3 VLT Automation VT Drive Selection
Automation VT Drive FC322 Design Guide
80
MG.20.X1.22 - VLT
®
is a registered Danfoss trademark
3
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx