5) The three values for the max. cable cross-section are for single core, flexible wire and flexible wire with sleeve, respectively.
PK37
PK55
PK75
P1K1
P1K5
P2K2
P3K0
P4K0
P5K5
P7K5
Typical Shaft Output (hp [kW])
0.5
[0.37]
0.75
[0.55]
1
[0.75]
1.5 [1.1]
2 [1.5]
3 [2.2]
4 [3]
5 [4]
7.5 [5.5] 10 [7.5]
Enclosure IP20/IP21
A2
A2
A2
A2
A2
A2
A2
A2
A3
A3
Enclosure IP20 (FC 301 only)
A1
A1
A1
A1
A1
Enclosure IP55, IP66
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A5
A5
Output current
High overload 160% for 1 min.
Shaft output [hp, kW]
0.5
[0.37]
0.75
[0.55]
1
[0.75]
1.5 [1.1]
2 [1.5]
3 [2.2]
4 [3]
5 [4]
7.5 [5.5] 10 [7.5]
Continuous (3x380–440 V) [A]
1.3
1.8
2.4
3
4.1
5.6
7.2
10
13
16
Intermittent (3x380–440 V) [A]
2.1
2.9
3.8
4.8
6.6
9.0
11.5
16
20.8
25.6
Continuous (3x441–500 V) [A]
1.2
1.6
2.1
2.7
3.4
4.8
6.3
8.2
11
14.5
Intermittent (3x441–500 V) [A]
1.9
2.6
3.4
4.3
5.4
7.7
10.1
13.1
17.6
23.2
Continuous kVA (400 V AC) [kVA]
0.9
1.3
1.7
2.1
2.8
3.9
5.0
6.9
9.0
11.0
Continuous kVA (460 V AC) [kVA]
0.9
1.3
1.7
2.4
2.7
3.8
5.0
6.5
8.8
11.6
Max. input current
Continuous (3x380–440 V) [A]
1.2
1.6
2.2
2.7
3.7
5.0
6.5
9.0
11.7
14.4
Intermittent (3x380–440 V) [A]
1.9
2.6
3.5
4.3
5.9
8.0
10.4
14.4
18.7
23.0
Continuous (3x441–500 V) [A]
1.0
1.4
1.9
2.7
3.1
4.3
5.7
7.4
9.9
13.0
Intermittent (3x441–500 V) [A]
1.6
2.2
3.0
4.3
5.0
6.9
9.1
11.8
15.8
20.8
Additional specifications
IP20, IP21 max. cable-cross section
5)
(line power, motor, brake and load
sharing) [mm
2
(AWG)]
2)
4,4,4 (12,12,12)
(min. 0.2(24))
IP55, IP66 max. cable cross-section
5)
(line power, motor, brake and load
sharing) [mm
2
(AWG)]
4,4,4 (12,12,12)
Max. cable cross-section
5)
with
disconnect
6,4,4 (10,12,12)
Estimated power loss
at rated max. load [W]
4)
35
42
46
58
62
88
116
124
187
255
Weight, enclosure IP20 (lb [kg])
10.36
[4.7]
10.36
[4.7]
10.58
[4.8]
10.58
[4.8]
10.8
[4.9]
10.8
[4.9]
10.8 [4.9]
10.8
[4.9]
14.55
[6.6]
14.55
[6.6]
Enclosure IP55, IP66
13.5
13.5
13.5
13.5
13.5
13.5
13.5
13.5
14.2
14.2
Efficiency
4)
0.93
0.95
0.96
0.96
0.97
0.97
0.97
0.97
0.97
0.97
0.5–10 hp [0.37–7.5 kW] only available as 160% high overload.
Table 10.4 Line Power Supply 3x380–500 V AC (FC 302), 3x380–480 V AC (FC 301)
Specifications
VLT
®
AutomationDrive Instruction
Manual
10-4
MG33AM22 - VLT
®
is a registered Danfoss trademark
10
10