background image

Description

The Vivo® power supply Bil/Popi/Buri KNX is a KNX de-

vice for rail mounting which produces and monitors the 

30 Vdc voltage required to operate the bus system. The 

device has an integrated choke which provides the de-

coupling between the power supply and the information 

on the bus line. On a KNX bus line can be connected 

up to 64 KNX bus devices. The output is protected from 

overload and short circuit. The device can support short 

interruptions of the mains voltage (max 200 ms).

Functions

•  30 Vdc SELV power supply for a KNX bus line with 

max 64 connected devices (Bil KNX)

•  Reset of the connected bus line with an internal de-

dicated pushbutton

Main characteristics

•  Housing in plastic material

• 

Mounting on 35 mm rail (according to EN 60715)

•  Protection degree IP20 (installed device)

• 

Classification climatic 3K5 and mechanical 3M2 (ac

-

cording to EN 50491-2)

•  Pollution degree 2 (according to IEC 60664-1) 

•  4 modular units (1 UM = 18 mm)

•  Dimensions 72 x 90 x 62 mm (WxHxD)

• 

Weight 225 g

Environmental conditions
• 

Operating temperature: - 5 ... + 45°C

• 

Storage temperature: - 25 ... + 55°C

• 

Transport temperature: - 25 ... + 70°C

• 

Relative humidity: 95% not condensing

Warning! Incorrect disposal of this product 

may cause serious damage to the envi-

ronment and human health. Please be infor-

med about the correct disposal procedures 

for waste collecting and processing provi-

ded by local authorities.

Technical data

Power supply
• 

Voltage 230/110 Vac, 50/60 Hz

•  Power consumption 22 W (power losses < 3 W)

Outputs
• 

Bus line voltage: 30 Vdc +1/-2 Vdc SELV

•  Rated current (total outputs): 640-320-160 mA

•  Buffer time: 200 ms

•  Bus line connection: KNX ternminal block (black/red) 

included in delivery

Switching, display and connection elements

The device is equipped with a reset pushbutton, ter-

minal blocks for mains voltage 230/110 Vac, KNX bus 

line. 

Planning

Planning a KNX bus installation, the use of a 640 mA 

power supply unit requires to take into account the fol-

lowing guidelines:
•  the maximum number of bus devices connected is 

64;

• 

the maximum length of a line segment is 350 m, me

-

1) Terminal blocks for power supply 110-230 Vac 50/60 Hz

2) Status LED

3) Reset pushbutton (internal)

4) Terminal block for KNX bus line

asured along the line between the power supply and 

the furthest bus device;

•  the maximum distance between two bus devices 

cannot exceed 700 m;

•  the maximum length of a bus line is 1000 m, keeping 

into account all segments.

At the same bus line can be connected not more than 

two power supplies. A second power supply may be 

necessary when the installation in distribution boards 

requires a particular concentration of the bus devices 

(tipically more than 30 units installed within 10 m). In 

this case a power supply has to be installed near the 

group of devices. Between two power supplies installed 

on the same bus line a minimum distance of 200 m is 

required, measured along the line.

Mounting

The device has degree of protection IP20, and is the-

refore suitable for use in dry interior rooms. The hou-

sing is made for rail mounting according to EN 60715 

in boards or cabinets for electrical distribution. The in-

stallation is in horizontal position, the correct position 

is when the terminals for KNX bus line and auxiliary 

Warning! In order to supply the KNX bus li-

nes use only a KNX bus power supply (e.g. 

Vivo Cursa KNX). The use of other power 

supplies can compromise the communica-

tion and damage the devices connected to 

the bus.

output are located at the bottom and the terminals  

(     , L, N) for connecting the mains power supply 

230/110 Vac are located at the top. For the installation 

of the device on the rail proceed as follows:
•  with the aid of a tool bring the locking device in the 

fully lowered position (a);

• 

place the upper edge of the rear inner profile on the 

upper edge of the rail (b);

•  rotate the device towards the rail (c);

•  push the locking device upward until it stops (d).

Before removing the device, be sure terminals for bus 

and have been extracted from his slots. Use a screwdri-

ver to slide down the locking device and remove the 

device from the rail.

a

b

d

Note.

  When  mounting  the  device  in  boards 

and cabinets it shall be provided the necessary 

ventilation so that the temperature can be kept 

within the operating range of the device.

Electrical connections

Main supply 230/110 Vac
The connection to the 230/110 main supply Vac is 

made with screw terminals (    , L, N) located on the 

front. Characteristics of the KNX terminal block:
•  spring clamping of conductors

•  4 seats for conductors for each polarity

•  terminal suitable for KNX bus cable with single-wire 

conductors and diameter between 0.6 and 0.8 mm

• 

recommended wire stripping approx. 5 mm

• 

color codification: red = + (positive) bus conductor, 

black = - (negative) bus conductor

Configuration and commissioning

Configuration
The  device  does  not  require  any  configuration  with 

ETS

®

 (Engineering Tool Software) tool. The application 

software are available in order to add to an ETS project 

an Bil/Popi/Buri KNX power supply.
Commissioning
For the commissioning of the device turn on the mains 

power supply 230/110 Vac to which the device is con-

nected. The green LED marked “ON” indicates the de-

vice operating.

Reset

The device has a reset pushbutton. After a reset, the 

bus line is not powered for 20 seconds and the bus de-

vices connected are restored to their original condition. 

During this interval of time the reset LED (red) is turned 

permanently on.

Marks

•  KNX

•  CE: the device complies with the Low Voltage Direc-

tive (2006/95/EC) and the Electromagnetic Compa

-

tibility Directive (2004/108/EC). Tests carried out ac-

cording to EN 50491-2:2010, EN 50491-3:2009, EN 

50491-4-1:2012, EN 50491-5-1:2010, EN 50491-5-

2:2010, EN 50428:2005 + A1:2007 + A2:2009

Maintenance

The device is maintenance-free. To clean use a dry 

cloth. It must be avoided the use of solvents or other 

aggressive substances.

Disposal

At the end of its useful life the product 

described  in  this  datasheet  is  classified 

as waste from electronic equipment in 

accordance with the European Directive 

2002/96/EC (RAEE), and cannot be dispo-

sed together with the municipal undifferen-

tiated solid waste.

Warnings

• 

Installation, electrical connection, configuration and 

commissioning of the device can only be carried out 

by qualified personnel in compliance with the appli

-

cable technical standards and laws of the respective 

countries

•  The power supply line to which the device is con-

nected must be equipped with an easily accessible 

disconnecting device with minimum separation di-

stance between contacts of 3 mm 

•  Opening the housing of the device causes the imme-

diate end of the warranty period

•  In case of tampering, the compliance with the es-

sential requirements of the applicable directives, 

for which the device has been certified, is no longer 

guaranteed 

•  Vivo® KNX defective devices must be returned to 

the manufacturer at the following address: Vivo 

Suisse Sagl, 

Viale dei Faggi 20

, CH 6900 Lugano

Other information

•  The instruction sheet must be delivered to the end cu-

stomer with the project documentation

•  For further information on the product, please con-

tact the Vivo® technical support at the e-mail ad-

dress: [email protected] or visit the 

website www.vivoknx.com

•  Each Vivo® device has a unique serial number on 

the label. The serial number can be used by instal-

lers or system integrators for documentation purpo-

ses and has to be added in each communication 

addressed to the Vivo technical support in case of 

malfunctioning of the device

•  Vivo® is a registered trademark of Vivo Suisse Sagl

•  KNX

®

 and ETS

®

 are registered trademarks of KNX 

Association cvba, Brussels

© Vivo Suisse Sagl 2017. The company reserves the right to make 

changes to this documentation without notice.

upper front of the device. Characteristics of the terminal 

blocks:
•  screw clamping of conductors

• 

maximum cross section of conductor 2.5 mm²

•  recommended wire stripping approx. 6 mm

• 

torque max 0.5 Nm

KNX bus line
The connection to the KNX bus line is made with the 

terminal block (black/red) included in delivery and in-

serted into the slot located on the left bottom part of the 

i

Warning! The electrical connection of the 

device can be carried out only by qualified 

personnel. The incorrect installation may 

result in electric shock or fire. Before ma

-

king the electrical connections, make sure 

the power supply has been turned off.

!

!

c

!

Power supply KNX 160/320/640mA

Code:K.BUR.01A.20N.WO 

K.POP.01A.20N.WO - K.BIL.01A.20N.WO

Instructions

EN

TP1

S

Its a registred brand of

Vivo Suisse Sagl
HQ

Viale dei Faggi 20
CH-6900 Lugano

Tel. +41919800044

[email protected]

www.vivoknx.com

Code

Description

K.BUR.01A.20N.WO

Buri KNX - 160 mA

K.POP.01A.20N.WO

Popi KNX - 320 mA

K.BIL.01A.20N.WO

Bil KNX - 640 mA

Summary of Contents for Bil KNX

Page 1: ...160 320 640mA Code K BUR 01A 20N WO K POP 01A 20N WO K BIL 01A 20N WO Instructions EN TP1 S Its a registred brand of Vivo Suisse Sagl HQ Viale dei Faggi 20 CH 6900 Lugano Tel 41919800044 info vivoknx com www vivoknx com ...

Page 2: ...on K BUR 01A 20N WO Buri KNX 160 mA K POP 01A 20N WO Popi KNX 320 mA K BIL 01A 20N WO Bil KNX 640 mA Description The Vivo power supply Bil Popi Buri KNX is a KNX de vice for rail mounting which produces and monitors the 30 Vdc voltage required to operate the bus system The device has an integrated choke which provides the de coupling between the power supply and the information on the bus line On ...

Page 3: ... slots Use a screwdri ver to slide down the locking device and remove the device from the rail a b c asured along the line between the power supply and the furthest bus device the maximum distance between two bus devices cannot exceed 700 m the maximum length of a bus line is 1000 m keeping into account all segments At the same bus line can be connected not more than two power supplies A second po...

Page 4: ... black red included in delivery and in serted into the slot located on the left bottom part of the i d Note When mounting the device in boards and cabinets it shall be provided the necessary ventilation so that the temperature can be kept within the operating range of the device Electrical connections Main supply 230 110 Vac The connection to the 230 110 main supply Vac is made with screw terminal...

Page 5: ...ock or fire Before ma king the electrical connections make sure the power supply has been turned off Warning Incorrect disposal of this product may cause serious damage to the envi ronment and human health Please be infor med about the correct disposal procedures for waste collecting and processing provi ded by local authorities Reset The device has a reset pushbutton After a reset the bus line is...

Reviews: