background image

The cooling fan delay setting will 

delay the fan from coming on in 

cool mode and keep it running 

after the compressor shuts off 

for a short time to save energy in 

some systems.

Cooling Fan

Delay

OFF

You can set the cooling fan 

delay to OFF, 15, 30, 60 or 90 

seconds. If 15, 30, 60, or 90 is 

selected the fan will not turn 

on for that many seconds 

when there is a call for cool 

and will run for that many 

seconds after satisfying a call 

for cool.

COOL 
FAN DL

IAQ Mode 

Cycle

This feature will configure the fan 

to run a selected number of cycles 

per hour.

Note: This mode can be enabled 

or disabled at anytime during 

normal operation by selecting IAQ 

mode with the fan key.

Select OFF, 1, 2, 3 or 4 with the  

         or         keys.

This sets the number of cycles 

per hour that the IAQ fan mode 

will operate.

OFF

IAQ 
MODE
CYCLE

Tech Setup Steps

Adjustment Options

Default

LCD Will Show

Technician Setup Menu

For Dual Fuel applications (Gas/

Fossil fuel Auxiliary Heat), turn 

this setting ON to LOCKOUT the 

Heat Pump (Y) when Auxiliary 

Heat (W2) is on. If desired - This 

can also be used with Electric 

Auxiliary.

You can configure the system 

switch for the particular 

application.

Heat - Off - Cool, Heat - Off, Cool - 

Off, Heat - Off - Cool - Auto

Note: EM. Heat will show if in 

heat pump mode.

System Set

Use the         or         key until 

the desired application is 

flashing.

AUTO=

(Auto Changeover)

You can configure the thermostat 

to operate a 3 stage heat pump 

system.

2H 2C = 2 heat, 2 cool

3H 2C = 3 heat, 2 cool

This feature is shown only if the 

HEAT PUMP technician setup 

step is ON.

Stages of 

Heat

Use the         or          key to 

change between 2 or 3 

stages of heat. 2 heat will 

use Y1 as first stage and W2 

as auxiliary.

3 heat will use Y1 as the first 

stage, Y2 as the second stage 

and W2 as the auxiliary.

Dual Fuel 

Auxiliary for 

Heat Pump

Will only appear if 

Heat Pump setting is 

turned ON

OFF

 Will allow Y(1st stage of 

Heat) and W2 (Aux Heat) to   

run together if called for.

ON

 Will de-energize Y termi-

nal 45 seconds after a call for 

Auxiliary Heat (W2).

Heat Pump

When turned on the thermostat 

will operate a heat pump.

1. EM. Heat will show as an option 

in the system switch.

2. Y will be first stage of heat 

& cool, W/E will be emergency 

heat relay & W2 will be auxiliary 

heat relay.

OFF configures the thermostat 

for non heat pump systems.

ON configures the thermostat 

for heat pump systems.

OFF

HEAT

OFF

COOL

A6

OFF

OFF

2H2C

2

STAGES

Tech Setup Steps

Adjustment Options

Default

LCD Will Show

Technician Setup Menu

This feature allows the installer 

to change the calibration of the 

room temperature display. For 

example, if the thermostat reads 

70˚ and you would like it to read 

72˚ then 2.

OFF

This feature will flash a reminder 

after the elapsed run time to 

remind the user to change the 

filter. A setting of  “OFF” will 

disable this feature.

Filter Change

Reminder

You can adjust the filter 

change reminder from “OFF” 

to 2000 hours of runtime in 

50 hour increments.

Tech Setup Steps

Room

Temperature

Calibration

0˚F

This feature allows the installer 

to select the minimum run 

time for the compressor. For 

example, a setting of 4 will force 

the compressor to run for at 

least 4 minutes every time the 

compressor turns on, regardless 

of the room temperature.

You can set the minimum 

compressor run time to “OFF”, 

“3”, “4”, or “5” minutes. If 3,4 

or 5 is selected, the 

compressor will run for 

at least the selected time 

before turning off.

Minimum 

Compressor 

On Time

OFF

You can adjust the room 

temperature display to read 

up to 4˚above or below the 

factory calibrated reading.

Adjustment Options

Default

LCD Will Show

OFF

SE

CAL

0

O

F

OFF

Technician Setup Menu

This thermostat has a technician setup menu for easy installer 

configuration. To set up the thermostat for your particular application:

1.  Press the 

MENU

 button.

2.  Press and hold the  

TECH SETUP

 button for 3 seconds. This 3 

     second delay is designed so that homeowners do not accidentally 

     access the  installer settings.

3. Configure the installer options as desired using the table below.

      Use the             or               keys to change settings and the 

NEXT 

      STEP

 or 

PREV

 

STEP

 key to move from one step to another.  

      

Note:

 Only press the 

DONE

 key when you want to exit the 

      Technician Setup options.

4. Press the 

DONE

 key to exit.

Keypad Lockout Note:

 The selected keypad lockout functionality must 

be activated after exiting tech setup. If you do not perform this 

procedure, all keys will function freely. To lock the keypad hold down 

the        and        keys for 3 seconds.  You will see a lock in the display. To 

unlock the display hold down the         and         keys for 3 seconds.

The compressor short cycle delay 

protects the compressor from 

“short cycling”. This feature will 

not allow the compressor to be 

turned on for 5 minutes after it 

was last turned off.

Compressor

Short Cycle

Delay

ON

Selecting “ON” will not allow 

the compressor to be turned 

on for 5 minutes after the 

last time the compressor was 

on. Select “OF” to remove 

this delay.

CO

ON

OF

Tech Setup Steps

Adjustment Options

Default

LCD Will Show

Keypad 

Lockout

Keypad lockout allows you to 

configure the thermostat so that 

some or all of the keys don’t 

function.

OF= keypad lockout has been 

disabled.

PA= partial keypad lockout, 

which locks all the keys except 

the         or          keys.

FU= full keypad lockout, 

which locks out all the keys.

OF

See Keypad Lockout Note

PA

The swing setting often called 

“cycle rate”, “differential” or

“anticipation” is adjustable. A 

smaller swing setting will cause 

more frequent cycles and a larger 

swing setting will cause fewer 

cycles.

Cooling 

Swing

The cooling swing setting 

is adjustable from 0.2˚ to 

2˚. For example: A swing 

setting of 0.5˚ will turn the 

cooling on at approximately 

0.5˚ above the setpoint 

and turn the cooling off at 

approximately 0.5˚ below 

the setpoint.

The swing setting often called 

“cycle rate”, “differential”, or 

“anticipation” is adjustable. A 

smaller swing setting will cause 

more frequent cycles and a larger 

swing setting will cause fewer 

cycles.

Heating 

Swing

0.5

dFCO

0.5˚

The heating swing setting is 

adjustable from 0.2˚ to 2˚. 

For example: A swing setting 

of 0.5˚ will turn the heating 

on at approximately 0.5˚ 

below the setpoint and turn 

the heating off at 0.5˚ above 

the setpoint.

0.4˚

0.4

dFHE

Swing Setting Tip

The second stage will turn on at 2x the swing setting.  The second stage 

will turn off when 1x the swing is reached. For example, if the swing 

setting is .5 degrees for heating and the thermostat is set at 70

˚

F, the first 

stage will turn on at approximately 69.5

˚

F.  The second stage will turn on 

at 69

˚

F. The second stage will turn off at 69.5

˚

F and the first will turn off 

at 70.5

˚

F.  If the third stage is used, it will turn on at 68.5

˚

F and turn off at 

approximately 69

˚

F.

Technician Setup Menu

HEAT
OFF
COOL

You can configure the thermostat 

for one of three remote sensor 

applications: 0 No Sensor, 1 

Indoor, 2 Outdoor, 3 Floor.

Remote 

Sensor 

Operation

0

REMOTE 
MODE

Local Temp 

Sensor

You can disable the sensor on the 

T855S thermostat. At least one 

R251S indoor remote sensor must 

be connected to disable the local 

T855S sensor. 

Note:

 Will only 

show if remote sensor is set to 1.

ON enables local T855S sensor. 

OFF disables local T855S 

sensor.

ON

LOCAL 
TEMP

1

Use the         or         keys to 

select one of three options.

View the S1/S2 terminal chart 

on next page for an 

explanation of these options.

ON

Number 

of Indoor 

Remotes

Enables the use of up to sixteen 

indoor sensors R251S.

Note:

 Will only show Remote 

Sensor is set to 1 and Local Temp 

Sensor is set to on.

You can use 1, 4, 9, or 16 

indoor sensors. Refer to the 

R251S Install Manual for 

detailed connection 

information.

ON

NUMBER 
OF 
REMO

1

A Note about IAQ Mode

This programmable/selectable mode will operate the fan 1-4 cycles per hour, 

1-45 minutes per cycle. Once programmed in tech setup, to enable this mode 

select “IAQ” with the fan key.  Disable this mode by selecting “ON” or “AUTO” with 

the fan key.

This allows you to select the

minimum number of minutes 

that the fan will run per IAQ mode 

cycle. The thermostat will keep 

track of fan runtime from normal 

heat and cool operation. If addi-

tional fan runtime is needed, the 

thermostat will run the fan to 

satisfy the IAQ mode minutes.

IAQ Mode 

Minutes

Select 1, 5, 10, 15, 20, 30 or 

45 minutes.
When IAQ fan mode is 

enabled, it will ensure the 

fan runs at least the selected 

number of minutes per IAQ 

Mode Cycle. 

This step will not appear if 

previous step is set to “OFF”.

1

IAQ 
MODE
MINUT

COMP DELAY

COOL SWING

HEAT SWING

KEY LOCK

CALIBRATE

MAIN COMP

HEAT PUMP

SYSTEM SET

GAS AUX

OFF

OFF

1

Summary of Contents for TP-S-855CR

Page 1: ...res should be pushed into the wall Installation Tips The thermostat should be installed approximately 4 to 5 feet above the floor Select an area with average temperature and good air circulation Close to hot or cold air ducts That are in direct sunlight With an outside wall behind the thermostat In areas that do not require conditioning Where there are dead spots or drafts in corners or behind doo...

Page 2: ...per can be installed between E and W2 to turn thermostat into a single stage control for Emergency Heat Operation Thermostat Quick Reference The low battery indicator is displayed when the AA battery power is low If the user fails to replace the battery within 21 days the screen will only show the low battery indicator but maintain all functionality If the user fails to replace the batteries after...

Page 3: ...em TypicalHeatOnlySystemWithFan TypicalCool OnlySystem HEAT RELAY RC RH Y C W E G C R L2 L1 HOT FAN RELAY HEAT RELAY RC RH Y C W E G C R L2 L1 HOT FAN RELAY COMPRESSOR RELAY C R L2 L1 HOT RC RH Y C G Power supply Factory installed jumper Remove only when installing on 2 transformer systems Use either O or B terminals for changeover valve Optional24VACcommonconnectionwhenthermostatisusedinbatterypo...

Page 4: ...nt to exit the Technician Setup options 4 Press the DONE key to exit Keypad Lockout Note The selected keypad lockout functionality must be activated after exiting tech setup If you do not perform this procedure all keys will function freely To lock the keypad hold down the and keys for 3 seconds You will see a lock in the display To unlock the display hold down the and keys for 3 seconds The compr...

Page 5: ...periods per day 4 time periods areWake Leave Return Sleep 2C time periods are Occupied Unoccupied 4C time periods are Occupied 1 Unoccupied 1 Occupied 2 Unoccupied 2 Use the or key to select 4 2c or 4c time periods per day 4 OFF OFF dL If ON is selected the beep will sound If OFF is selected there is no sound 4 OFF OFF ON b Tech Setup Steps Adjustment Options Default LCDWillShow Contractor Call Nu...

Page 6: ...XT 7 Minutes are now flashing Use the or key to select current minutes 8 Press DONE when completed All our programmable thermostats are shipped with an energy saving default program You can customize this default program by following the instructions in the set program schedule section starting on page 24 Programming Your thermostat can be programmed to have each day of the week programmed uniquel...

Page 7: ...5 Press NEXT 6 The setpoint temperature is flashing Use the or key to make your setpoint selection for that day s WAKE OCC1 period 7 Press NEXT 8 Repeat steps 4 through 7 for that day s LEAVE UNOCC1 time period for that day s RETURN OCC2 time period and for that day s SLEEP UNOCC2 time period To customize your 7 day 4 time period Program schedule follow these steps Monday Repeat steps 4 through 8 ...

Page 8: ...nent holds Temporary Permanent Hold Feature Programming A Note About Programmable Fan The programmable fan feature will run the fan continuously during any time period it is programmed to be on This is the best way to keep the air circulated and to eliminate hot and cold spots in your building If using IAQ mode set fan to IAQ for any time period 1 Select HEAT or COOL with the SYSTEM key Note You h...

Reviews: