Pompa a vuoto
INSTALLING THE OUTDOOR UNIT
Location
Use bolts to secure the unit to a flat, solid floor.
When mounting the unit on a wall or the roof, make
sure the support is firmly secured so that it cannot
move in the event of intense vibrations or a strong
wind.
Do not install the outdoor unit in pits or air vents
Installing the pipes
Use suitable connecting pipes and equipment for the
refrigerant R410A.
The refrigerant pipes must not exceed the maximum
lengths given in the technical data table.
Lag all the refrigerant pipes and joints.
Tighten the connections using two wrenches working
in opposite directions.
Install the drain fitting and the drain hose (for
model with heat pump only)
Condensation is produced and flows from the outdoor unit
when the appliance is operating in the heating mode. In order
not to disturb neighbours and to respect the environment,
install a drain fitting and a drain hose to channel the conden-
sate water. Install the drain fitting and rubber washer on the
outdoor unit chassis and connect a drain hose to it as shown
in the figure.
Do not install the outdoor unit where it is exposed
to sunlight.
INSTALLER
Direzione del fluido refrigerante
Valvola a 2 vie
(6) Aprire di 1/4 di giro
Cappuccio della valvola
(1) Girare
(8) Fissare
(2) Girare
Valvola a 3 vie
(8) Fissare
(1) Girare
(7) Girare per
aprire completamente
(7) Girare per aprire
completamente
(8) Fissare
Entrata
utile
Connettere all’
unità interna
UNITA’ INTERNA
Cappuccio
della valvola
Humid air left inside the refrigerant circuit can cause com-
pressor malfunction. After having connected the indoor
and outdoor units, bleed the air and humidity from the
refrigerant circuit using a vacuum pump.
(1) Unscrew and remove the caps from the 2-way and 3-
way valves.
(2) Unscrew and remove the cap from the service valve.
(3) Connect the vacuum pump hose to the service valve.
(4) Operate the vacuum pump for 10-15 minutes until an
absolute vacuum of 10 mm Hg has been reached.
(5) With the vacuum pump still in operation, close the
low-pressure knob on the vacuum pump coupling. Stop
the vacuum pump.
(6) Open the 2-way valve by 1/4 turn and then close it
after 10 seconds. Check all the joints for leaks using
liquid soap or an electronic leak device.
(7) Turn the body of the 2-way and 3-way valves. Discon-
nect the vacuum pump hose.
(8) Replace and tighten all the caps on the valves.
BLEEDING
INSTALLER
INDOOR
UNIT
Refrigerant fluid direction of flow
3-way valve
2-way valve
Service
inlet
(2) Turn
(8) Secure
(7) Turn to open fully
(2) Turn
(8) Secure
Valve cap
(6) Open by 1/4 turn
(7) Turn to open fully
(2) Turn
(8) Secure
Valve cap
Connect to the
indoor unit
Vacuum pump
6
Summary of Contents for ACP-18COFM50GEI
Page 2: ......
Page 3: ...HR BiH Upute za uporabu ACP 18COFM50GEI RoHS ...
Page 12: ......
Page 13: ...SR Korisničko uputstvo ACP 18COFM50GEI RoHS ...
Page 22: ......
Page 23: ...CG Upute za uporabu ACP 18COFM50GEI RoHS ...
Page 32: ......
Page 33: ...SLO Navodila za uporabo ACP 18COFM50GEI RoHS ...
Page 42: ......
Page 43: ...AL Udhëzime për përdorim ACP 18COFM50GEI RoHS ...
Page 52: ......
Page 53: ...MAK Упатства за употреба ACP 18COFM50GEI RoHS ...
Page 62: ......
Page 63: ...User manual ENG ACP 18COFM50GEI RoHS ...
Page 72: ......
Page 73: ...NOR Bruksanvisning ACP 18COFM50GEI RoHS ...
Page 82: ......
Page 86: ...3 4 ACP 18COFM50GEI ...
Page 89: ...3 4 ACP 18COFM50GEI ...
Page 101: ...3 4 3 4 3 4 ACP 18COFM50GEI ACP 18COFM50GEI ACP 18COFM50GEI ...
Page 106: ......
Page 107: ......
Page 108: ......