Operating status, fault diagnosis, trouble-shooting
Indication
Operating status
Possible cause
Remedy
LED "Pow" out of function Not operative
Power supply defect or inter-
rupted
Check power supply
LED "Halt" out of function
"Stop“ – relay open Slack cable or passage door
switch opened or faulty
Check all switches and wiring
LED "Edge 1" and/or
"Edge 2" out of function
"OSE“–relays
(33/34) open
The respective safety edge is
open or defective
Resp. switch setting wrong
Check respective safety edge.
Check switch setting (8k2/OSE)
LED "Edge 1" and "Edge
2" blink fast (2Hz)
Error-detection
mode.
"OSE“–relays
(33/34) open
Technical defect in external
control unit
Reset unit by disconnecting power supply.
In case of identical error, change external control
unit
LED “Edge 1” and/ or
“Edge 2” blink slowly
(1Hz)
"OSE“–relays
(33/34) open
Cable break of wiring 8k2
safety edge, safety edge defect
or switch setting wrong
Check wiring and safety edge.
Check switch setting (8k2 / OSE)
Security advice
Only instructed persons are allowed to open the housing!
High voltage inside!