Air Handler
7
The heating mode temperature rise is dependent upon the system airflow, the supply voltage,
and the heater kit size (KW) selected. Use Tables 8-10 to determine the temperature rise(ºF).
table 8
CFM
HEATER KIT NOMINAL KW
5
8
10
15
20
600
28
41
56
800
21
31
42
1000
17
25
34
50
1200
14
21
28
42
56
1400
12
18
24
36
48
1600
10
15
21
31
42
1800
9
14
19
28
37
230/1/60 Supply Voltage-Temperature Rise Table ºF
table 9
CFM
HEATER KIT NOMINAL KW
5
8
10
15
20
600
27
39
52
800
20
30
40
1000
16
24
32
48
1200
13
20
27
40
53
1400
11
17
23
34
46
1600
10
15
20
30
40
1800
9
13
18
27
36
220/1/60 Supply Voltage-Temperature Rise Table ºF
table 10
CFM
HEATER KIT NOMINAL KW
5
8
10
15
20
600
25
37
50
800
19
28
38
1000
15
22
30
46
1200
13
19
25
38
56
1400
11
16
22
33
48
1600
9
14
19
28
42
1800
8
12
17
25
37
208/1/60 Supply Voltage-Temperature Rise Table ºF
Note:
For installations not indicated above the following formula is to be used:
TR=(kW*3412)*(Voltage Correction)*1.08/CFM
Where:TR=Temperature Rise
KW=Heater Kit Actual kW
3412=Btu per kW
Voltage Correction= 0.96(230 Supply Volts)
0.92(220 Supply Volts)
0.87(208 Supply Volts)
1.08=Constant CFM=Measured Airflow