20
5.5 Function control
Check the functions every 6 months.
1) Press the OFF-key to determine if buzzer, indicators and LCD-display are
operating normally or not. Refer for that to section «4.1 Operation modes».
2) Press the ON-key, check indicators, LCD-display and inverter of the UPS. Assure
yourself, that they are all operating normally.
3) To ensure that the battery is in good condition, perform a battery test when the
UPS is operating in normal condition.
Appendix 1 Specifications
Capacity
6KVA/5.4W
10KVA/9KW
Type
6KVA
;
10KVA
Input
Input mode
Three phase +N+ Ground
Power factor
≥0.99
rating voltage
380/400/415VAC or 220/230/240VAC
rating frequency
50Hz/60Hz
(
auto sensing
)
Voltage range
208~478VAC
Frequency range
45~55Hz/54~66Hz
Bypass voltage range
220Vac max
:
10%
,
15%
,
20% or 25%
,
default
:
25%
230Vac max
:
10%
,
15% or 20%
,
d20%
240Vac max
:
+10% or 15%
,
d15%
min
:
20%, 30% or 45%, default 45%
Bypass frequency range
±1%
、
±2%
、
±4%
、
±5%
、
±10%
THDI
≤
3%
(
100% linear load
,
input THDV
≤1%
)
≤
5%
(
100% non-linear load
,
input THDV
≤1%
)
B
at
tery
Battery number
16/18/20pcs
(
can be set
)
Battery type
VRLA
Charge model
Boost charge or float charge auto switch
Charge time
Boost charge up to 20Hr(Max)
Charge current (A)
1A
(
S
)
/10A
(
H
)
O
ut
pu
t
Output type
Single phase + Ground
Output precision
1.0%
;
Voltage distortion
(
THD
)
≤
2% at 100% linear load
≤
5% at 100% non-linear load
Rating voltage
220/230V /240V
Frequency precision
±0.1%