22
A45
BATT CR OPEN
Battery Circuit Breaker is open
A47
INV RX T-OUT
Communication between the inverter and the front panel is lost
A48
REC RX T-OUT
Communication between the rectifier and the front panel is lost
All alarms except VSEC NOT OK are minor.
MEASUREMENTS MENU
MEASUREMENT
DEFINITION
LD
= XXX,XXX,XXX % Ratio of the actual inverter active power of each line to its nominal
value
*
1
Vsc = XXX,XXX,XXX V Output line/neutral voltages
*
1
Isc
= XXX,XXX,XXX A Output line currents
*
1
Fo
= XX.X
Hz Frequency of output line/neutral voltages
Vby = XXX,XXX,XXX V Bypass line/neutral voltages
*
1
Vin = XXX,XXX,XXX V Input line/neutral voltages
Iin
= XXX,XXX,XXX A Rectifier Input Current
Fin
= XX.X
Hz Frequency of input line/neutral voltages
Vdc = XXX,XXX
V Positive and negative DC bus voltages
Vbat = XXX,XXX
V Positive and negative battery branch voltages
Ibat = ±XXX,±XXX
A Positive and negative battery branch currents
Positive during charge, negative during discharge
Tbat = XXX
°C Ambient temperature
COMMANDS MENU
PRIORITY
= INVRTR/BYPASS Selects the priority of normal and bypass operation modes
Push ENTER to switch between INVRTR and BYPASS
START B. TEST
Push ENTER to start battery test
BUZZER
= ENBLD/DSBLD Enable or disable the buzzer
Push ENTER to switch between ENBLD and DSBLD
COMM
= RS232/RS422
Push ENTER to switch between RS232/RS422
communication
EXTCMNDS
Push ENTER 3 times to enter this submenu
EXTRA COMMANDS SUBMENU
RECTFR
= ENBLD/DSBLD Enable or disable operation of the rectifier block
Push ENTER to switch between ENBLD and DSBLD
= BLCKD
*
2
Can be seen only when the rectifier is blocked
Push ENTER to remove the blockage and enable the rectifier
INVRTR
= ENBLD/DSBLD Enable or disable the operation of the inverter block
Push ENTER to switch between ENBLD and DSBLD
= BLCKD
*
2
Can be seen only when the inverter is blocked
Push ENTER to remove the blockage and enable the inverter
BYPASS
= ENBLD/DSBLD Enable or disable the operation of the bypass thyristors
Push ENTER to switch between ENBLD and DSBLD
*
1
There is only one measurement value at 1ph output models