Chapter 3 Deployment
Manual VIPA TM-E
3-28
HB39E - TME - RE_900-1E630 - Rev. 09/11
•
Here enter the following parameters:
- "TM-E PPP server IP address": 202.0.0.240
- "PPP client IP address": 202.0.0.1
•
Accept the remaining default settings and click at [Update].
Configure your PC modem so that it may establish a connection to the TM-
E module. Here establish a DFÜ connection. More about this may be found
in the manual of your PC operating system.
Here please regard that User name and Password are identical to the
access data in you TM-E module.
Call your TM-E module via the PC modem.
Open as soon as the TM-E module reacts a DOS command window and
send a ping to the IP address 202.0.0.240. You should now get a response.
Else check your settings.
Information how to integrate your TM-E modules to your PLC may be found
at "TM-E - Project integration - PG/PC interface".
If you have just integrated your TM-E module into your PLC project, at the
TM-E station of NetPro the routing is accordingly be adapted.
•
Open NetPro with your project.
Test the telephone
connection
Configure routing
in PLC project