Chapter 3 Deployment
Manual VIPA TM-E
3-4
HB39E - TME - RE_900-1E630 - Rev. 09/11
•
Connect your CPU to the TM-E module via MPI.
•
Switch on the power supply of the CPU and switch the CPU to RUN.
•
Open the Web page of the corresponding TM-E module.
•
Open with
Configuration
>
I/O server config.
the page for adjusting an
I/O server. Set as I/O server "S73&400".
•
To access the VIPA PLC enter the following parameters:
MPI destination node
:
2
(standard)
Baud rate
:
187500
Reply timeout
: 3000
(Standard)
MPI address
: 0
(Standard)
Highest MPI station address
: 31
(Standard)
Topic A
:
enabled
Global device address
:
MPI, # (with #: MPI address CPU)
Poll rate
:
2000 MS (Standard)
•
To confirm click at [Update config].
Now the CPU may be accessed via the TM-E module.
In a
Tag
the storage areas of you PLC may be defined. These storage
areas may R/W accessed by the Tag.
•
To establish a Tag open at the Web page the page "Tag setup" and click
at "Create new Tag ...".
•
Enter the following parameters:
Tag name
:
Test
Server name
: S73&400
Topic name
:
A
Address
:
MW0
Type
:
Boolean
•
Otherwise leave the standard setting and click at [Add/Update...].
•
Switch with
Main menu
>
View I/O
to the Tag list.
•
Enter a new value for the Tag "Test" and click at [Update]. Now this
value is set and may be transferred to the CPU with clicking to [Update]
in the head line.
•
If the new value is accepted by the CPU, so the communication between
the TM-E module and the CPU is secured.
These steps are more described at the following pages.
Access to the
VIPA PLC
Establish a Tag