Chapter 3 Deployment CPU 21x-2BM03
Manual VIPA System 200V
3-12
HB97E - CPU - RE_21x-2BM03 - Rev. 14/44
Enter the time intervals in ms, in which the watchdog interrupt OBs should
be processed. The start time for the clock is when the operating mode
switch is moved from STOP to RUN.
Enter the delay time in ms for current execution for the watch dog interrupt.
This should be performed if several watchdog interrupts are enabled.
Phase offset allows to distribute processing time for watchdog interrupts
across the cycle.
This parameter is not supported.
Here 1 of 3 protection levels may be set to protect the CPU from
unauthorized access.
Protection level 1 (default setting):
•
No password adjustable, no restrictions
Protection level 2 with password:
•
Authorized users: read and write access
•
Unauthorized user: read access only
Protection level 3:
•
Authorized users: read and write access
•
Unauthorized user: no read and write access
Execution
Phase offset
Process image
partition
Protection
Level of protection