![VIPA System 200V Series Manual Download Page 35](http://html.mh-extra.com/html/vipa/system-200v-series/system-200v-series_manual_1029197035.webp)
Manual VIPA System 200V
Chapter 2 Hardware description
HB97E - CPU - RE_21x-2BM03 - Rev. 14/44
2-9
Order no.
214-2BM03
Type DP
Type of interface
RS485
Connector
Sub-D, 9-pin, female
Electrically isolated
9
MPI -
MP²I (MPI/RS232)
-
DP master
yes
DP slave
-
Point-to-point interface
-
Functionality MPI
Number of connections, max.
16
PG/OP channel
9
Routing -
Global data communication
9
S7 basic communication
9
S7 communication
9
S7 communication as server
9
S7 communication as client
-
Transmission speed, min.
19.2 kbit/s
Transmission speed, max.
187.5 kbit/s
Functionality PROFIBUS master
PG/OP channel
9
Routing -
S7 basic communication
-
S7 communication
-
S7 communication as server
-
S7 communication as client
-
Activation/deactivation of DP slaves
9
Direct data exchange (slave-to-slave communication) -
DPV1 -
Transmission speed, min.
9.6 kbit/s
Transmission speed, max.
12 Mbit/s
Number of DP slaves, max.
64
Address range inputs, max.
1 KB
Address range outputs, max.
1 KB
User data inputs per slave, max.
244 Byte
User data outputs per slave, max.
244 Byte
Datasizes
Input bytes
0
Output bytes
0
Parameter bytes
4
Diagnostic bytes
0
Housing
Material
PPE / PA 6.6
Mounting
Profile rail 35 mm
Mechanical data
Dimensions (WxHxD)
50.8 x 76 x 80 mm
Weight 150
g
Environmental conditions
Operating temperature
0 °C to 60 °C
Storage temperature
-25 °C to 70 °C
Certifications
UL508 certification
yes