Manual VIPA System 200V
Chapter 6 DeviceNet
HB97E - IM - Rev. 06/29
6-9
Specifying baudrate and DeviceNet address
You may set the baudrate as well as the DeviceNet address when the
power has been turned off. These will be transferred into the module when
you turn the respective power supply on.
All stations connected to the bus communicate at the same baudrate. You
may define the required rate by means of the address selector.
•
Turn off the power supply
•
Set the address selector to the wanted baudrate
Setting
baudrate in kBaud
90
125
91
250
92
500
•
Turn on the power supply
The selected transmission rate is saved to the EEPROM.
At this point your DeviceNet coupler is set to the correct baudrate.
When the baudrate has been saved successfully, the RD-LED (green) will
be turned on.
When the baudrate was selected incorrectly, the ER-LED will be turned on.
All stations connected to the bus must have a unique DeviceNet address.
The address can be defined by means of the address selector when the
supply has been turned off.
•
Turn off the power supply
•
Set the address selector to the required address.
Please ensure that the address is unique in the system and that it
is located between 0 and 63.
•
Turn on the power supply
The selected addressis saved to the RAM.
Note!
Any changes to the addressing will only become effective after a POWER
ON or an automatic reset. Changes to settings are not recognized during
normal operations.
When the address is not valid or if it already exists the ER-LED (red) will be
turned on after power on.
Setting the
baudrate
LED-indicator
RD-LED
ER-LED
Setting the
DeviceNet
address
LED indicator
ER-LED
Summary of Contents for System 200V IM Series
Page 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Page 2: ...Lerrzeichen...
Page 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Page 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Page 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Page 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Page 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Page 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...