Manual VIPA System SLIO
Chapter 3 Deployment
HB300E - FM - RE_050-1BB30 - Rev. 10/30
3-7
Diagnostic data
So this module does not support process interrupts, the diagnostics data
serve for information about this module.
DS = Record set for access via CPU, Profibus and ProfiNET. The access
happens by DS 01h. Additionally the first 4 bytes may be accessed by DS
00h.
IX = Index for access via CANopen. The access happens by IX 2F01h.
Additionally the first 4 bytes may be accessed by IX 2F00h.
SX = Subindex for access via EtherCAT.
Name
Bytes Function
Default
DS
IX
SX
ERR_A 1
reserved
00h
01h
2F01h 02h
MODTYP 1 Module
information
18h
03h
ERR_C 1
reserved
00h 04h
ERR_D 1
reserved
00h 05h
CHTYP 1
Channel
type
76h
06h
NUMBIT
1
Number diagnostics bits per
channel
00h
07h
NUMCH
1
Number channels of the module
02h
08h
CHERR 1
reserved
00h
09h
CH0ERR…
CH7ERR
7 reserved
00h
0Ah ... 11h
DIAG_US 4 µs
ticker
00h
12h
Byte Bit 7 ... 0
0
Bit 3 ... 0: Module class
1000b: Function module
Bit 4: set at channel information present
Bit 7 ... 5: reserved
Byte Bit 7 ... 0
0
Bit 6 ... 0: Channel type
76h: Counter module
Bit 7: reserved
Byte Bit 7 ... 0
0
Number of diagnostics bits of the module per channel (here 00h)
Byte Bit 7 ... 0
0
Number of channels of the module (here 02h)
Byte Bit 7 ... 0
0 ... 3 Value of the µs ticker at the moment of the diagnostic
Byte Bit 7 ... 0
0 reserved
Overview
MODTYP
Module information
CHTYP
Channel type
NUMBIT
Diagnostic bits
NUMCH
Channels
DIAG_US
µs ticker
ERR_A/C/D
CHERR, CHxERR
reserved
Summary of Contents for SLIO FM 050-1BB30
Page 1: ...VIPA System SLIO FM 050 1BB30 Manual HB300E_FM RE_050 1BB30 Rev 10 30 July 2010...
Page 4: ...Contents Manual VIPA System SLIO ii HB300E FM RE_050 1BB30 Rev 10 30...
Page 8: ...Safety information Manual VIPA System SLIO 4 HB300E FM RE_050 1BB30 Rev 10 30...
Page 40: ...Chapter 3 Deployment Manual VIPA System SLIO 3 8 HB300E FM RE_050 1BB30 Rev 10 30...