SENSOR INDICATORS

INSTALLATION - DROP CEILING WITH EXISTING OUTLET* 
(WHOLE ROOM UNIT/BATH UNIT WITH 2’ X 2’ ADAPTER)

1. 

Remove the existing ceiling tile.  

2.  Plug the S.A.G.E. power cord into outlet.
3.  Position the S.A.G.E. unit onto ceiling grid.
4. 

Insert cut-to-size ceiling tile to sit flush against the 

S.A.G.E. unit.  See instructions below for cutting 

tile to size.

*If there is no existing outlet, install a 110V, 15 
Amp outlet.  This may be subject to applicable 

permitting.  Please consult with a licensed 
electrician.

Whole Room Units

1.  Measure and mark a 5 3/4” section on the ceiling tile. 
2. 

Use a box cutter or other appropriate tool to cut off the 5 3/4” section of the tile. 

Micro Units with Adapter Plates

If installing the Micro unit with 2’ x 2’ adapter, no cuts are required.

For hard-ceiling installation, contact Violet Defense for additional guidance.

To install in a 24” x 48” grid, cut the ceiling tile to fit using a box cutter or appropriate 

tool.

CUTTING CEILING TILE TO SIZE

Each S.A.G.E. UV unit comes standard with mounting holes for standard VESA bracket.  

This enables a variety of installation methods, including wire suspension and wall 
mounts.  The VESA holes also allow for integration with a variety of mobile stands, such 

as tripods or bases with caster-wheels.  

The Micro units can also be used with base stand to position in various rooms on 
tabletops, desks, counter tops, etc.  

(Brackets and stands sold separately)

OTHER DEPLOYMENT OPTIONS

INS

TALLA

TION

© Copyright 2020 Violet Defense, LLC All Rights Reserved SUV-GEN2-UM2020

11

Summary of Contents for S.A.G.E. UV

Page 1: ...USER MANUAL WARRANTY S A G E UV Whole Room Unit S A G E UV Micro Violet Defense LLC www violetdefense com 407 433 1104 S A G E UV S A G E UV by Violet Defense by Violet Defense ...

Page 2: ...OPERATION 2 STANDARD UNITS OPERATIONAL GUIDELINES 3 BUILDING AUTOMATION ENABLED UNITS OPERATIONAL GUIDELINES 4 RECOMMENDED CLEANING PROTOCOLS 7 TROUBLESHOOTING 8 INSTALLATION 9 UV SAFETY OVERVIEW 10 WARRANTY 12 TABLE OF CONTENTS ...

Page 3: ...y when the room is unoccupied There are redundant safety systems to ensure the unit does not activate while the room is occupied as the UV light is not recommended for excessive exposure If the sensor in the system fails the system will shut down Do not look directly at the unit due to the brightness of the light UV light does not significantly penetrate standard glass therefore incidental exposur...

Page 4: ...ycle Exit the space within 60 seconds for optimal functioning of the unit 4 The unit s redundant safety systems will stop the unit from operating if motion is detected in the space The unit will resume operation approximately 60 seconds unless alternate motion timeout was selected after room is unoccupied and no additional motion is detected 5 The unit will run a safety test to ensure unit is func...

Page 5: ...nit will automatically activate once the space is unoccupied and continue disinfection on a regular schedule adjusting frequency based on level of activity in the space based on the motion sensor Users may select the timeout time which determines how long the unit will wait until resuming operation after motion is detected Scheduled Mode In this mode the unit will activate at selected time s of da...

Page 6: ...he unit will operate disinfection cycles similar to that of manual mode However the unit will have to be activated from within your building automation system software NOTE By default this mode will have safety features deactivated With the building automation capabilities of the S A G E UV Whole Room Unit users have the ability to adjust the following Operational Modes Settings Select operating m...

Page 7: ...an alternate connection method Verify each step carefully If it is still not responding try rebooting the unit or using the reset button to restore the default memories 2 The unit s network configuration can be reset to factory default by holding the reset button in for at least 2 seconds and then releasing This will clear all configured IP settings and reset the unit to preferring a DHCP assigned...

Page 8: ...on page 6 AI Manual Overnight Four Hour BMS Cleaning Internal Runtime STPT Set the amount of time in minutes the unit cleans for in manual mode Range 10 minutes to 30 minutes Motion Timeout STPT Sets the number of seconds for which the unit will pause when it detects motion Range 15 seconds to 1800 seconds Enable Cleaning CMD Manually turn the unit on off 0 Unit is off 1 Unit is on Enable Safeties...

Page 9: ... can be set here Subnet Mask CNFG If DHCP is disabled a static subnet mask can be set here Gateway CNFG If DHCP is disabled a static gateway can be set here Device MAC Address CNFG The ethernet s MAC address UDP Port CNFG The UDP port that BACnet uses Default value 47808 MSTP MAC Address CNFG Use this to set the MSTP MAC address Each device on the network must have a unique MAC address Default val...

Page 10: ...month Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Hour when time changes in 24 hour format A dash separator must be used between the start rule and end rule For example in the United States DST starts on the Second Sunday of March at 02 00AM and ends on the First Sunday of November at 02 00AM The DST rule would therefore be SecondSunMar02 FirstSunNov02 The DST rule for Germany would be LastSun...

Page 11: ...refore UV light may be used to help protect staff before and after traditional cleaning protocols for your facility 1 Activate S A G E UV unit prior to commencing any cleaning procedures If the blood has already dried apply hydrogen peroxide solution prior to running the unit 2 Utilize normal procedures including appropriate safety protocols to clean the space including removal of blood and bodily...

Page 12: ... indicator lights that help you determine the status of the unit CLEANING THE UNIT Do not use abrasive cleaners to clean the unit To clean the unit wipe down the metal plates with stainless steel polish using a microfiber cloth TROUBLESHOOTING Copyright 2020 Violet Defense LLC All Rights Reserved SUV GEN2 UM2020 10 Color of Light Meaning Flashing Green Unit is ready to begin cleaning when room bec...

Page 13: ... Units with Adapter Plates If installing the Micro unit with 2 x 2 adapter no cuts are required For hard ceiling installation contact Violet Defense for additional guidance To install in a 24 x 48 grid cut the ceiling tile to fit using a box cutter or appropriate tool CUTTING CEILING TILE TO SIZE Each S A G E UV unit comes standard with mounting holes for standard VESA bracket This enables a varie...

Page 14: ...e actual exposure to UV if there were no other safety systems in place would be no more than two seconds of exposure Motion Detection Each S A G E UV unit has built in passive infrared PIR sensor used to detect motion in a space The sensor is programmed to detect individuals walking into the deployment space The unit will not resume operation of the cleaning cycle until it has successfully detecte...

Page 15: ... cause photokeratitis or cataracts National Institute for Occupational Safety and Health NIOSH The National Institute for Occupational Safety and Health NIOSH recommends limits to exposure determined by the wavelength of UV light and intensity NIOSH recommends that the time of exposure to an intensity of 100 microwatts per square centimeter at wavelength 254 nm not exceed 1 minute Per the programm...

Page 16: ...IES SET FORTH HEREIN SOME STATES COUNTRIES PROVINCES AND OTHER JURISDICTIONS DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY OR CONDITION MAY LAST SO THE LIMITATION DESCRIBED ABOVE MAY NOT APPLY TO YOU WHO MAY USE THIS WARRANTY Violet Defense extends this Warranty only to the end user purchaser who originally purchased the Product from Violet Defense or a Violet Defense authorized distrib...

Page 17: ...e nonconforming Product s may be required to be returned to Violet Defense for inspection and verification of the nonconformity Violet Defense will not be responsible for any costs and expenses incurred in connection with shipment of the nonconforming Product s or part s thereof to Violet Defense however Violet Defense shall bear the expenses of shipping the replacement Product s or part s thereof...

Page 18: ...TM 189 S Orange Avenue Suite 1400 Orlando FL 32801 ...

Reviews: