background image

                                                       

 

                       

 

- 19 -

I

n case there is excessive frost, the parameters

 FnC 

=

 

C-y

, idF 

=

  4

 and 

MdF 

=

 

20

 

can be used to avoid frost. 

 
9. How to adjust the humidity  
 

The parameter 

Fon 

is used to adjust the humidity in the wine cellar. Higher 

Fon 

results in higher relative humidity.

  Use a separate hygrometer to monitor the 

humidity. 

 
10. How to set alarm call  
 

1) S

peech notice will be sent to your phones when the cellar temperature is 

ALU

 

higher or 

ALL

 lower than the set-point 

Set

.

  

2) In order to test the call function, set parameters 

Ald 

= 0 and 

dAO 

= 0.  After 

testing, set 

Ald 

= 60 and 

dAO 

= 23. 

 

11. How to set low cellar temperature heater 

 

The heater turns on at 

SAA

 minus 

Shy; 

the heater turns off at 

SAA

NOTES:  

  Use a forced air heater to warm up the wine cellar. 

  If there is a thermostat on the heater, bypass it or set the thermostat at the 

highest level.   

If the heater runs more than 10 A current, use a 120VAC coil contactor. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for WM-1520HZD

Page 1: ...ne em ma at te e c co om m Wine Cooling System WM 1520HZD WM 2520HZD WM 3520HZD WM 4520HZD WM 6520HZD WM 8520HZD Installation Use Care Manual w ww ww w v vi in no ot te em mp p c co om m Read and save these instructions ...

Page 2: ...rtant Safety Information NOTES Do not plug in until 24 hours after delivery Do not use a ground fault interrupter GFI A dedicated 10 AMP circuit for WM 1520 2520HZD and 15 AMP for WM 3520 8520HZD are required ...

Page 3: ... 2 Table of Contents Features Specifications 3 Installation Instructions 6 Temperature Humidity 16 Care Guide 20 Troubleshooting 21 Electrical Diagrams 24 Customer Support 26 Warranty 27 ...

Page 4: ...intain humidity ranges within 50 70 RH These temperature and humidity ranges are optimized for long term storage of wine Temperature is controlled and humidity is adjusted using patented technology Horizontal cold air supply is optimized for use in the wide cabinets or wine rooms The unit is self contained ready for easy installation and use Fig 1 1 WM 1520 2520HZD FEATURE DESCRIPTIONS ...

Page 5: ... 4 Fig 1 2 WM 3520 8520HZD FEATURE DESCRIPTIONS Fig 1 3 WM 1520 2520HZD DIMENSIONS ...

Page 6: ...requency and current specified on the label at the cooling unit The rated capacity is determined under the cellar and ambient temperatures of 55 F and 75 F with R13 interior and R19 exterior insulations Any lower cellar temperature higher ambient temperature and less insulation will cause reducing capacity and may not maintain 55 F The ambient temperatures for WM 1520HZD shall not be higher than 7...

Page 7: ...length 1 General Instructions The cooling unit produces cooling supplied into the cellar meanwhile it also generates heat that must be exhausted outside the cellar So the cold air supply with return air intake side and the hot air exhaust with ambient air intake side must be separated and sealed Through wall installations can separate these two sides Furthermore the condenser of cooling unit must ...

Page 8: ... 1 4 ID wood thread inserts at the ceiling see Fig 2 1 2 2 Place the gaskets 1 2 foam tape on the mounting lip sides see Fig 2 3 If top exhaust installation place another gaskets along the top exhaust at the top of the cooling unit see Fig 2 4 Move the cooling unit towards the mounting sides and push to press the gaskets see Fig 2 5 Use 2 brackets and screws with 7 16 wrench to secure the cooling ...

Page 9: ... 8 Fig 2 2 THREAD INSERT Fig 2 3 REAR GASKET ...

Page 10: ... 9 Fig 2 4 TOP EXHAUST GASKET Fig 2 5 COOLING UNIT MOUNTING ...

Page 11: ... 10 Fig 2 6 SECURING BRACKET SCREW ...

Page 12: ... 11 Fig 2 7 CABINET GRILLE ...

Page 13: ...t Construct a shelf as shown The shelf must be capable of supporting the weight of the cooling unit and preventing it from moving Place the cooling unit on the shelf with the back of the unit flush with the outside of the wall Seal the clearance between the cooling unit and opening with a high quality weather stripping polyurethane spray foam or foam tape Cover the seal with molding and attach the...

Page 14: ...an be installed with the front of the unit flush with the inside of the wall Construct a shelf outside the room accordingly Fig 2 9 THROUGH WALL INSTALLATION OUTSIDE WALL FLUSH Fig 2 10 THROUGH WALL INSTALLATION INSIDE WALL FLUSH ...

Page 15: ...l have a vapor barrier and a minimum of R13 insulation All exterior walls and ceiling shall have a vapor barrier and a minimum of R19 insulation The vapor barrier shall be installed on the warm side of the insulation All joints door frames electrical outlets or switches and any pipes or vents that go through the cellar shall be sealed to prevent air and moisture leakage into the cellar Concrete ro...

Page 16: ...ill not be able to maintain the proper temperature if fresh moisture laden air is constantly being introduced to the cellar Symptoms of this condition are cooling unit runs all the time with only a slight reduction in temperature and or water overflows from the unit Because of the temperature difference between the inside and outside very small cracks can allow large amounts of outside air to ente...

Page 17: ...ck the keypad SET To enter in the programming mode SET To return to the temperature display 2 Lock and unlock the keys To lock the keys press up down keys until POF is displayed to unlock the keys press up down keys until PON is displayed 3 Display During normal operating conditions the display shows the value measured by the air temperature probe In case of active alarm the temperature flashes al...

Page 18: ...re at 55 F for the optimum aging of wine On initial start up the time required to reach the desired temperature will vary depending on the quantity of bottles temperature setting and surrounding temperature Allow 24 hours to stabilize the temperature for each new temperature setting operation 3 How to see temperature set point 1 Press and immediately release the SET key the display will show the s...

Page 19: ... temperature unit F C F Fahrenheit rES display resolution in integer dLy temperature display delay min 1 ot probe calibration 0 LS minimum set point 50 US maximum set point 65 idF defrost cycle interval time hour 12 MdF defrost cycle endurance time min 30 ALC temperature alarm type rE relative to set point ALU high temperature alarm 10 ALL low temperature alarm 10 AFH alarm recovery differential 5...

Page 20: ...e will be sent to your phones when the cellar temperature is ALU higher or ALL lower than the set point Set 2 In order to test the call function set parameters Ald 0 and dAO 0 After testing set Ald 60 and dAO 23 11 How to set low cellar temperature heater The heater turns on at SAA minus Shy the heater turns off at SAA NOTES Use a forced air heater to warm up the wine cellar If there is a thermost...

Page 21: ...e if it is accumulated on the cooling unit in high humidity conditions 3 Removing Unit When you remove the cooling unit beware water may come out of the unit 4 Installing Drain Line WM 3520 8520HZD units are equipped with an additional drain fitting In case of extreme humidity there is a drain line needed remove the drain plug on the bottom left at the rear then remove the connection plug and fit ...

Page 22: ...e is mainly controlled by the average air temperature If the set point is 55 F with the differential 4F the cooling unit turns on at 59 F of air temperature It may be higher than 59 F if it is in anti short cycle or defrost cycle and turns off at 55 F of air temperature The average air temperature is 57 F and then the wine temperature is around 57 0 5 F The air is light enough to change so quickly...

Page 23: ...installation location d Leave minimum 3 feet clearance for the hot air exhaust side and leave minimum 1 foot clearance for the fresh air intake side e Clean condenser f Check for fan and air short circulation 8 Fan motor running but compressor not running a Post compressor fan running mode b Incorrect or loose wirings c Failed components d Liquid refrigerant in the compressor a Check fan running t...

Page 24: ...ng excessive condensate c Evaporator air flow restriction d Water passages restricted e Drip tray leak No water overflow but water leak a Check for air leak b Use drain line c Check supply air flow or air TD d Clean the drip tray e Seal the leak using silicone sealant 15 Excessive condensate in wine cellar a Air leak in the wine cellar causing excessive condensate b High humidity causing excessive...

Page 25: ... 24 Electrical Wiring Diagrams Fig 6 1 WM 1520 2520HZD WIRING DIAGRAM Fig 6 2 WM 1520 2520HZD WIRING DIAGRAM ALARM CALL ...

Page 26: ... 25 Fig 6 3 WM 3520 8520HZD WIRING DIAGRAM Fig 6 4 WM 3520 8520HZD WIRING DIAGRAM ALARM CALL ...

Page 27: ...26 Customer Support If you need further assistance please contact us at Vinotemp International 17631 South Susana Road Rancho Dominguez CA 90221 Tel 310 886 3332 Fax 310 886 3310 Email info vinotemp com ...

Page 28: ...f the VINOTEMP with respect to its products and is in lieu of all other warranties express or implied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any modification or unauthorized repair of VINOTEMP products shall void this warranty Service under Warranty This service is provided to customers within the co...

Page 29: ...MAGES BASED UPON INCONVENIENCE LOSS OF USE OF THE UNIT LOSS OF TIME OR COMMERCIAL LOSS ANY OUTER DAMAGES WHETHER INCIDENTAL CONSEQUENTIAL OR OTHERWISE THIS WARRANTY IS EXCLUSIBE AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR INPLIED INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE While great effort has been made to provide accurate guidel...

Reviews: