background image

                                                       

 

                       

 

- 16 -

Troubleshooting 

 

This Troubleshooting Chart is not prepared to replace the training required for a 
professional refrigeration service person, not is it comprehensive

 

 

Complaint Possible 

Causes 

Response 

1. Unit not 

running

 

a.  Power cord unplugged 
b.  No power to unit 
c. Setting higher than ambient 

temperature 

d.  Differential too high 
e.  Incorrect or loose wirings 
f. Low 

voltage 

g. Defrost 

light 

blinking 

h.  Compressor light blinking 

a.  Check for power cord plug 
b.  Check power at receptacle & fuses 
c. Lower 

temperature 

setting 

 
d.  Decrease the value as to 4 

°

e.  Check all wirings and connections 
f. 

Contact an authorized electrician  

g.  Unit is under defrost mode 
h.  Unit waits for anti-short cycle delay 

2. Cabinet  

temperature  
high,  unit 
stopping 
and starting 
with short 
running time 

a. 

air sensor touching the 
evaporator coil, displaying 
temperature ok 

b.  Short circuit of air flow between 

supply and return air  

c.  Setting too high 
d. Failed temperature controller 

and thermistor 

 

a.  Move the air sensor away from the 

evaporator 

 
b.  Deflect the supply air down 
  
c. Lower 

setting 

d.  Call service for diagnosis 
 

3. Temperature  

high, 
compressor 
stopping 
and starting 
but very 
short 
running time

 

a. Incorrect 

voltage 

b. Failed 

thermistor 

 
c. Failed 

components 

 
d. Improper 

condenser 

airflow 

e. Dirty 

condenser 

f. 

Overcharge of refrigerant 

g.  Discharge or suction pressure 

too high 

a.  Check for voltage 
b.  Check thermistor by placing it in ice 

water and measuring resistance 

c.  Check compressor windings, start 

relay and overload protector. 

d.  Check for condenser fan  
e. Clean 

condenser 

f. 

Call service for removing refrigerant 

g.  Call service for OEM information 
 

4. Temperature 

high or not 
cooling and 
running 
continually; 
“HA” alarm 
blinking and 
beeping   

a.  Improper room insulation & seal 
 
b.  Room too large 
c.  Ambient temperature too high 
d.  Exhaust restricted  
 
 
 
e. Malfunctioning 

fans 

 
f. 

Improper evaporator or 
condenser airflow 

g. Dirty 

Condenser 

h. Iced 

evaporator 

i. Refrigeration 

system 

restriction 

 
j. Refrigerant 

leak 

 
k.  Undercharge or overcharge 
 

a.  Check for insulation, gasket and 

door opening 

b.  Check for excessive size   
c.  Check for installation location 
d.  Leave minimum required clearance 

for the exhaust side and leave 
minimum required clearance for the 
fresh air intake side  

e. Check for both evaporator and 

condenser fans  

f.  Check for air restrictions, air short-

circulation, grille directions 

g. Clean 

condenser 

h.  Defrost and reset temperature 
i. 

Call service for checking  
restrictions 

j.  Call service for checking loss of 

refrigerant 

k.  Call service to add or remove 

refrigerant 

Summary of Contents for WINE-MATE WM1500 HTD

Page 1: ...t Use Care Manual WM1500 HTD HTD TE WM2500 HTD HTD TE V Vi in no ot te em mp p I In nt te er rn na at ti io on na al l C Co or rp p w ww ww w v vi in no ot te em mp p c co om m w ww ww w w wi in ne em...

Page 2: ...1 Important Safety Information DO NOT PLUG IN UNTIL 24 HOURS AFTER DELIVERY DO NOT USE A GROUND FAULT INTERRUPTER GFI A DEDICATED 20 AMP CIRCUIT IS REQUIRED...

Page 3: ...2 TABLE OF CONTENTS Features Specifications 3 Installation Instruction 5 Temperature Control Humidity Adjustment 11 Care Guide 14 Troubleshooting 16 Wiring Diagram 19 Customer Support 20 Warranty 21...

Page 4: ...emperature digital control using patent pending technology Optimized air flow for most even temperatures in wine cabinets Exchangeable supply grille for front back and down cold air distribution Multi...

Page 5: ...120 90 115V 60Hz 4A 55 2500htd Rear Exhaust 180 200 115V 60Hz 5A 60 2500htd te Top Exhaust 180 200 115V 60Hz 5A 60 NOTES See the voltage frequency and current specified on the label at the cooling un...

Page 6: ...front if left and right sides obstructed 3 Top Exhaust Location Leave min 12 from the top to the ceiling Leave min 2 clearance from the rear to the wall Leave min 2 clearance from the left and right s...

Page 7: ...t lips see Fig 2 4 If top exhaust place another gaskets along the top exhaust at the top of the cooling unit see Fig 2 9 Move the cooling unit towards the mounting sides and push to press the gaskets...

Page 8: ...7 Fig 2 2 TOP EXHAUST CUTOUT Fig 2 3 CUTOUT AND HOLE DIMENSIONS...

Page 9: ...8 Fig 2 4 GASKET AND SCREW INSERT Fig 2 5 COOLING UNIT MOUNTING EXPLODED...

Page 10: ...9 Fig 2 6 COOLING UNIT MOUNTING COMPLETED Fig 2 7 COOLING UNIT MOUNTING REAR EXHAUST Fig 2 8 COOLING UNIT MOUNTING TOP EXHAUST...

Page 11: ...nst the use of an extension cord However if you still elect to use an extension cord it is absolutely necessary that it will be a UL LISTED 3 wire grounding type appliance extension cord having a 3 bl...

Page 12: ...programming mode it selects a parameter or confirm an operation DEF To start a manual defrost UP To see the maximum stored temperature in programming mode it browses the parameter codes or increases t...

Page 13: ...seconds after the probe restarts normal operation Check connections before replacing the probe Temperature alarms HA LA automatically stops as soon as the temperature returns to normal value Alarm CA...

Page 14: ...isplay delay min 1 ot probe calibration 0 US maximum set point 65 LS minimum set point 50 idF defrost cycle interval time hour 24 MdF defrost cycle endurance time min 30 ALC temperature alarm type rE...

Page 15: ...14 Care Guide I Component Identification Fig 4 1 Exploded View...

Page 16: ...y need to be cleaned at least every 6 months Unplug the unit or disconnect power Use a condenser brush or a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty Plug...

Page 17: ...time a Incorrect voltage b Failed thermistor c Failed components d Improper condenser airflow e Dirty condenser f Overcharge of refrigerant g Discharge or suction pressure too high a Check for voltage...

Page 18: ...ck all wirings and connections d Check start relay start capacitor overload protector compressor e Call service for OEM information 7 Compressor running but fan not running a Fan blade stuck b Incorre...

Page 19: ...vaporator air flow restriction c Water passages restricted d Drip tray leak e High humidity a Check for any air leak b Check air flow or air TD crossing evaporator c Clean the drip tray d No water ove...

Page 20: ...19 Wiring Diagram Fig 6 1 WIRING DIAGRAM...

Page 21: ...20 Customer Support If you still have problems please contact us at Vinotemp International 17631 South Susana Road Rancho Dominguez CA 90221 Tel 310 886 3332 Fax 310 886 3310 Email info vinotemp com...

Page 22: ...the VINOTEMP with respect to its products and is in lieu of all other warranties express or implied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any...

Page 23: ...AGES BASED UPON INCONVENIENCE LOSS OF USE OF THE UNIT LOSS OF TIME OR COMMERCIAL LOSS ANY OUTER DAMAGES WHETHER INCIDENTAL CONSEQUENTIAL OR OTHERWISE THIS WARRANTY IS EXCLUSIBE AND IS IN LIEU OF ALL O...

Reviews: