background image

 

-3- 

Cellar  Construction  Guide 

This is only a guide and shall be considered as the minimum requirements. 

 

All interior walls, ceilings and floors shall have a vapor barrier and a minimum of 
R13  insulation.  All  exterior  walls  and  ceiling  shall  have  a  vapor  barrier  and  a 
minimum of R19 insulation. The vapor barrier shall be installed on the warm side 
of insulation. All joints, door frames, electrical outlets or switches and any pipes 
or  vents  that  go  through  the  cellar  shall  be  sealed  to  prevent  air  and  moisture 
leaking  into  the  cellar.  Concrete,  rock,  and  brick  are  not  insulations  or  vapor 
barriers. Doors shall be of a minimum size, insulated to at least R13 and tightly 
sealed with high quality weather stripping. Be sure to seal the bottom of the door 
and fill gap between the 

door’s frame and wall before installing the cap molding. 

 

In order to maintain 55 °F in the wine cellar, the ambient  temperature surrounding 
the  cellar  shall  not  exceed  the  temperature  of  the  cellar  by  more than 25 °F. 
No cellar walls shall receive direct sun or strong wind. 

 

Lighting shall be of low wattage, with a timer to insure lights are not left on when 
the cellar is not occupied. 

 

The  cooling  system  will  not  be  able  to  maintain  the  proper  temperature  if  fresh 
moisture-laden air is constantly being introduced to the  cellar. Symptoms of this 
condition  are;  cooling  unit  runs  all  the  time  with  only  a  slight  reduction  in 
temperature  and/or  water  overflows  from  the  cooling  unit.  Because  of  the 
temperature  difference  between  the  inside  and  outside,  very  small  cracks  can 
allow large amounts of outside air to enter into the cellar. Please be aware that 
moisture  can  pass  through  solid  concrete,  paint  and  wood.  Often  a  newly 
constructed  cellar  contains  fresh  wood,  paint,  concrete  and  other  building 
materials. These materials contain large amounts of moisture. When placed into 
operation in this type of environment, the system will work harder to remove this 
extra moisture resulting in increased 

“run” time. 

Summary of Contents for WINE-MATE WM-2500SSIWC

Page 1: ...stem Operation Care Installation Manual WM 2500SSIWC WM 4500SSIWC www vinotemp com Read and save these instructions Vinotemp International Corp 732 South Racetrack Road Henderson NV 89015 Tel 800 777...

Page 2: ...cle installed by a qualified electrician DO NOT UNDER ANY CIRCUMSTANCES REMOVE THE POWER CORD GROUNDING PRONG A separate adequately fused and grounded circuit should be available for this appliance Do...

Page 3: ...2 Table of Contents Cellar Construction Guide 3 Features Specifications 4 Temperature Humidity 6 Care Guide 10 User Troubleshooting 11 Installer s Instructions 14 Electrical Wirings 25 Warranty 26...

Page 4: ...temperature surrounding the cellar shall not exceed the temperature of the cellar by morethan 25 F No cellar walls shall receive direct sun or strong wind Lighting shall be of low wattage with a time...

Page 5: ...units can be recessed and flushed in the ceiling in a wine room The evaporator units provide 6 low profile and whisper quiet operation SSIWC cooling systems consist of a remote condensing unit and an...

Page 6: ...sing unit ambient temperature with R13 interior and R19 exterior insulations Higher ambient temperatures or lower insulations will cause reducing capacity and the cellar temperature may not be maintai...

Page 7: ...ock the keypad SET To enter in the programming mode SET To return to the temperature display 2 Lock and unlock the keys To lock the keys press up down keys until POF is displayed to unlock the keys pr...

Page 8: ...nstrument 2 Temperature Setting Set the temperature at 55 F for the optimum aging of wine On initial start up the time required to reach the desired temperature will vary depending on the quantity of...

Page 9: ...e regulation differential 4 AC anti short cycle delay min 10 hidden Con compress on with probe faulty min 15 CoF compress off with probe faulty min 30 CF temperature unit F C F Fahrenheit rES display...

Page 10: ...ative humidity Use a separate hygrometer to monitor the humidity 10 How to set alarm call 1 Speech notice will be sent to your phones when the cellar temperature is ALU higher or ALL lower than the se...

Page 11: ...aning To clear any sediment that may accumulate the water regulating valve may be manually flushed Insert screwdrivers under both sides of the valve spring guide and lift upwards to flush 2 Condensate...

Page 12: ...F the cooling unit turns on at 59 F of air temperature It may be higher than 59 F if it is in anti short cycle or defrost and turns off at 55 F of air temperature The average air temperature is 57 F a...

Page 13: ...otector compressor c Call service 11 Temperature low a Low temperature setting b Low ambient temperature c Air probe fault d Temperature controller fault a Raise the setting b Move to another location...

Page 14: ...ion b Use dehumidifier c Increase air flow or raise temperature setting 17 Circuit tripping a Incorrect fuse or breaker b Incorrect wirings c Failed components a Check for proper fuse or breaker b Che...

Page 15: ...nician has properly installed the system Proper installation is critical Vinotemp can only warrant the quality of the components The installation and proper operation of the system must be warranted b...

Page 16: ...for electrical wiring and refrigeration piping Model No Evap Unit L x W x H A Cond Unit L x W x H Electrical Rating Evap Unit Cond Unit Min Circuit Ampacity A Weight lb Evap Unit Cond Unit WM 2500SSI...

Page 17: ...16 Fig 4 WM 25 45SFCI Evaporator Unit...

Page 18: ...ocated in the wine cellar 5 ft above the floor or the air return area but it shall not be located in the air supply area or other areas where air is not circulated 3 Air probe can be pulled out of the...

Page 19: ...ector sizes of liquid filter and indicator the valve connector sizes of condensing unit or the line connector sizes of evaporator unit may not be the same as the listed refrigeration line sizes If the...

Page 20: ...er is fed from the discharge side of the pump Model No Condensing Unit Water Flow 75 F inlet gal min Water in Connecti on Water out Connecti on Water Pressur e Drop PSI WM 2500SSIWC WM 250SCUR WC 0 2...

Page 21: ...high or low pressure hose to the discharge or suction valve and connect it to a vacuum pump 3 Open the manifold high and low pressure valves to evacuate the system 4 Close the manifold high and low p...

Page 22: ...stable Pressure Control 3 A fan speed control may be used to adjust the air flow to achieve the specified CFM The fan will run from the minimum speed to full speed with thecontrol knob at the lowest a...

Page 23: ...e evaporator shall be 8 10 F at 55 F wine cellar temperature 8 Again you must verify if the superheat at the evaporator unit is 9 18 F at 55 F 65 F wine cellar temperatures 9 If the superheat is high...

Page 24: ...normal head pressure High superheat and high subcooling 9 Low suction pressure and low head pressure Normal to high superheat and low subcooling 10 Low suction pressure and low head pressure Low super...

Page 25: ...ted beforereceiver 15 Condenser restricted 11 Condensing Unit Troubleshooting Unit not running 1 Incorrect power supply 2 Incorrect or loose wirings 3 Failed components 4 Low pressure switch shutting...

Page 26: ...e field wirings Use minimum 14 gauge wires for power lines If equipped with low ambient condition kit use low ambient temperature wiring diagrams A safety switch is always recommended for the condensi...

Page 27: ...lied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any modification of VINOTEMP products shall void this war...

Page 28: ...BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE While great effort has been made to provide accurate guidelines VINOTEMP cannot warrant its units to proper...

Reviews: