-9- 

7. How to calibrate the air probe 

 

If the actual cellar temperature differs from the setting temperature,  set parameter 

ot 

= actual cellar temperature minus set-point. 

 

8. How to adjust defrost settings 

 

I

n case there is excessive frost, the parameters 

FnC 

= C-y

, idF 

and 

MdF 

20 can be used to avoid frost. 

 

9. How to adjust the humidity 

 

The parameter 

Fon 

is used to adjust the humidity in the wine cellar. Higher 

Fon 

results  in  higher  relative  humidity. 

Use  a  separate  hygrometer  to  monitor  the 

humidity. 

 

10. How to set alarm call 

 

1) S

peech notice will be sent to your phones when the cellar temperature is 

ALU 

higher or 

ALL 

lower than the set-point 

Set

2)  In order to test the call function, set parameters 

Ald 

= 0 and 

dAO 

= 0.  After 

testing, set 

Ald 

= 60 and 

dAO 

= 23. 

 

11. How to set cellar heater 

 

The heater turns on at 

SAA 

minus 

Shy

; the heater turns off at 

SAA

 

NOTE 

 

Use a forced air heater to warm up the wine cellar. 
If  there  is  a  thermostat  on  the  heater,  bypass  it  or  set  the 
thermostat at the highest level. 
If the heater runs more than 10 A current, use a 120VAC coil 
contactor. 

 

 

Summary of Contents for WINE-MATE WM-2500SSIWC

Page 1: ...stem Operation Care Installation Manual WM 2500SSIWC WM 4500SSIWC www vinotemp com Read and save these instructions Vinotemp International Corp 732 South Racetrack Road Henderson NV 89015 Tel 800 777...

Page 2: ...cle installed by a qualified electrician DO NOT UNDER ANY CIRCUMSTANCES REMOVE THE POWER CORD GROUNDING PRONG A separate adequately fused and grounded circuit should be available for this appliance Do...

Page 3: ...2 Table of Contents Cellar Construction Guide 3 Features Specifications 4 Temperature Humidity 6 Care Guide 10 User Troubleshooting 11 Installer s Instructions 14 Electrical Wirings 25 Warranty 26...

Page 4: ...temperature surrounding the cellar shall not exceed the temperature of the cellar by morethan 25 F No cellar walls shall receive direct sun or strong wind Lighting shall be of low wattage with a time...

Page 5: ...units can be recessed and flushed in the ceiling in a wine room The evaporator units provide 6 low profile and whisper quiet operation SSIWC cooling systems consist of a remote condensing unit and an...

Page 6: ...sing unit ambient temperature with R13 interior and R19 exterior insulations Higher ambient temperatures or lower insulations will cause reducing capacity and the cellar temperature may not be maintai...

Page 7: ...ock the keypad SET To enter in the programming mode SET To return to the temperature display 2 Lock and unlock the keys To lock the keys press up down keys until POF is displayed to unlock the keys pr...

Page 8: ...nstrument 2 Temperature Setting Set the temperature at 55 F for the optimum aging of wine On initial start up the time required to reach the desired temperature will vary depending on the quantity of...

Page 9: ...e regulation differential 4 AC anti short cycle delay min 10 hidden Con compress on with probe faulty min 15 CoF compress off with probe faulty min 30 CF temperature unit F C F Fahrenheit rES display...

Page 10: ...ative humidity Use a separate hygrometer to monitor the humidity 10 How to set alarm call 1 Speech notice will be sent to your phones when the cellar temperature is ALU higher or ALL lower than the se...

Page 11: ...aning To clear any sediment that may accumulate the water regulating valve may be manually flushed Insert screwdrivers under both sides of the valve spring guide and lift upwards to flush 2 Condensate...

Page 12: ...F the cooling unit turns on at 59 F of air temperature It may be higher than 59 F if it is in anti short cycle or defrost and turns off at 55 F of air temperature The average air temperature is 57 F a...

Page 13: ...otector compressor c Call service 11 Temperature low a Low temperature setting b Low ambient temperature c Air probe fault d Temperature controller fault a Raise the setting b Move to another location...

Page 14: ...ion b Use dehumidifier c Increase air flow or raise temperature setting 17 Circuit tripping a Incorrect fuse or breaker b Incorrect wirings c Failed components a Check for proper fuse or breaker b Che...

Page 15: ...nician has properly installed the system Proper installation is critical Vinotemp can only warrant the quality of the components The installation and proper operation of the system must be warranted b...

Page 16: ...for electrical wiring and refrigeration piping Model No Evap Unit L x W x H A Cond Unit L x W x H Electrical Rating Evap Unit Cond Unit Min Circuit Ampacity A Weight lb Evap Unit Cond Unit WM 2500SSI...

Page 17: ...16 Fig 4 WM 25 45SFCI Evaporator Unit...

Page 18: ...ocated in the wine cellar 5 ft above the floor or the air return area but it shall not be located in the air supply area or other areas where air is not circulated 3 Air probe can be pulled out of the...

Page 19: ...ector sizes of liquid filter and indicator the valve connector sizes of condensing unit or the line connector sizes of evaporator unit may not be the same as the listed refrigeration line sizes If the...

Page 20: ...er is fed from the discharge side of the pump Model No Condensing Unit Water Flow 75 F inlet gal min Water in Connecti on Water out Connecti on Water Pressur e Drop PSI WM 2500SSIWC WM 250SCUR WC 0 2...

Page 21: ...high or low pressure hose to the discharge or suction valve and connect it to a vacuum pump 3 Open the manifold high and low pressure valves to evacuate the system 4 Close the manifold high and low p...

Page 22: ...stable Pressure Control 3 A fan speed control may be used to adjust the air flow to achieve the specified CFM The fan will run from the minimum speed to full speed with thecontrol knob at the lowest a...

Page 23: ...e evaporator shall be 8 10 F at 55 F wine cellar temperature 8 Again you must verify if the superheat at the evaporator unit is 9 18 F at 55 F 65 F wine cellar temperatures 9 If the superheat is high...

Page 24: ...normal head pressure High superheat and high subcooling 9 Low suction pressure and low head pressure Normal to high superheat and low subcooling 10 Low suction pressure and low head pressure Low super...

Page 25: ...ted beforereceiver 15 Condenser restricted 11 Condensing Unit Troubleshooting Unit not running 1 Incorrect power supply 2 Incorrect or loose wirings 3 Failed components 4 Low pressure switch shutting...

Page 26: ...e field wirings Use minimum 14 gauge wires for power lines If equipped with low ambient condition kit use low ambient temperature wiring diagrams A safety switch is always recommended for the condensi...

Page 27: ...lied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any modification of VINOTEMP products shall void this war...

Page 28: ...BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE While great effort has been made to provide accurate guidelines VINOTEMP cannot warrant its units to proper...

Reviews: