- 21 - 

 

 

            BACK POSITION                     FRONT POSITION                       MIDDLE POSITION 

 

Fig. 10 ROTALOCK Valve Operation 

 

 

 
            BACK POSITION                         FRONT POSITION                    MIDDLE POSITION 

 

Fig. 11 Base Valve Operation 

 

Back Position

: Normal operation, manifold port is closed.  

Front Position

:  Storage operation, liquid or suction line connection is closed.  

Middle Position

: Installation operation, all ports are open.

 

 

NOTE 

The  recommended  initial  charges  are  used  for  reference  only, 
always  use  the  superheat,  subcooling  and  pressure  readings  to 
charge refrigerant properly. 
If the unit is equipped with a low ambient condition kit and installed 
in the summer, add 15% more refrigerant. 

If  the  low  ambient  condition  kit  is  used,  turn  off  the  compressor 
before  power  the  condensing  unit.  Only  turn  on  the  compressor 
after the condensing unit has been powered for 12 hours.

 

 
1)  Turn both discharge and suction valves in the middle positions.  
2)  Connect  the manifold high  or  low  pressure  hose  to  the  discharge  or  suction 

valve and connect it to a vacuum pump. 

3)  Open the manifold high and low pressure valves to evacuate the system. 
4)  Close the manifold high and low pressure valves and switch it to a charging 

scale. 

Summary of Contents for WINE-MATE WM-12000SSD

Page 1: ...D WM 6500SSD LA WM 8500SSD WM 8500SSD LA WM 12000SSD WM 12000SSD LA w ww ww w v vi in no ot te em mp p c co om m R Re ea ad d a an nd d s sa av ve e t th he es se e i in ns st tr ru uc ct ti io on ns...

Page 2: ...1 Important Safety Information...

Page 3: ...2 Table of Contents Cellar Construction Guide 3 Features Specifications 4 Temperature Humidity 6 Care Guide 10 User Troubleshooting 11 Installer s Instructions 14 Electrical Wirings 27 Warranty 30...

Page 4: ...temperature surrounding the cellar shall not exceed the temperature of the cellar by more than 25 F No cellar walls shall receive direct sun or strong wind Lighting shall be of low wattage with a tim...

Page 5: ...storage of wine like that in natural caves SSD evaporator units can be installed on the ceiling in the center of a wine cellar The evaporator units provide two way air supply for better operation SSD...

Page 6: ...temperatures or lower insulations will cause reducing capacity and the cellar temperature may not be maintained at 55 F The specifications are listed as follows Model No Capacity Btu h Airflow CFM Ma...

Page 7: ...ock the keypad SET To enter in the programming mode SET To return to the temperature display 2 Lock and unlock the keys To lock the keys press up down keys until POF is displayed to unlock the keys pr...

Page 8: ...nstrument 2 Temperature Setting Set the temperature at 55 F for the optimum aging of wine On initial start up the time required to reach the desired temperature will vary depending on the quantity of...

Page 9: ...e regulation differential 4 AC anti short cycle delay min 10 hidden Con compress on with probe faulty min 15 CoF compress off with probe faulty min 30 CF temperature unit F C F Fahrenheit rES display...

Page 10: ...ative humidity Use a separate hygrometer to monitor the humidity 10 How to set alarm call 1 Speech notice will be sent to your phones when the cellar temperature is ALU higher or ALL lower than the se...

Page 11: ...ng Clean the condenser coil regularly Coil may need to be cleaned at least every 6 months Use a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty 2 Condensate Remo...

Page 12: ...oling unit turns on at 59 F of air temperature It may be higher than 59 F if it is in anti short cycle or defrost and turns off at 55 F of air temperature The average air temperature is 57 F and then...

Page 13: ...rt capacitor overload protector compressor c Call service 9 Compressor running but condenser fan not running a Fan blade stuck b Incorrect or loose wirings c Failed motors d Fan cycle control a Check...

Page 14: ...cessive condensate b High humidity causing excessive condensate c Drain restricted a Check for any air leak b Use drain line c Clean the drip tray and drain line 17 Condensate inside ducts a Drain lin...

Page 15: ...Installation of the system must be done in accordance with all state and local building and electrical codes The condensing unit and evaporator unit are connected by a liquid line and an insulated suc...

Page 16: ...WM 45SFCD 23 x 17 1 2 x 10 1 2 WM 450SCUR 18 x 14 x 12 115V 60HZ 1A 115V 60HZ 6A 20A 25 60 WM 4500SSD LA WM 45SFCD 23 x 17 1 2 x 10 1 2 WM 450SCUR LA 18 x 14 x 12 115V 60HZ 1A 115V 60HZ 7A 20A 25 60...

Page 17: ...16 Fig 3 Temperature Controller 4 5 L X 4 5 W X 3 75H Fig 4 WM 25 45SFCD Evaporator Unit...

Page 18: ...17 Fig 5 WM 65 120SFCD Evaporator Unit Fig 6 WM 250 450SCUR Condensing Unit...

Page 19: ...llar but the air probe must be located inside 2 The air probe shall be located in the wine cellar 5 ft above the floor or the air return area but it shall not be located in the air supply area or othe...

Page 20: ...ll be below 50 F 1 Place the condensing units WM 250 1203SCUR in a properly ventilated location Otherwise heat exhausted by the condensing unit will build up and the cooling system will not operate pr...

Page 21: ...ft long use both inverted U trap and suction accumulator to prevent liquid from flooding back to the compressor 3 If the condensing unit is located below the evaporator unit use inverted U trap to pr...

Page 22: ...ings to charge refrigerant properly If the unit is equipped with a low ambient condition kit and installed in the summer add 15 more refrigerant If the low ambient condition kit is used turn off the c...

Page 23: ...cking pressure control settings I The encapsulated pressure control if applicable Suction pressure setting fixed Cut in 32 psig Cut out 10 psig Fig 12 Fixed Pressure Control II The adjustable pressure...

Page 24: ...e compressor and shall be turned on all the time The heater is self regulated B The condenser fan control The condenser fan control is installed at the high side It closes on rise of pressure It is ne...

Page 25: ...k the subcooling first to see if the refrigerant charge is sufficient If the charge is not sufficient add more refrigerant Liquid must always be charged into the hide side when the compressor runs If...

Page 26: ...al head pressure High superheat and normal to high subcooling 12 Low suction pressure and normal head pressure High superheat and normal subcooling 13 Low suction pressure and high head pressure High...

Page 27: ...d components 4 Low pressure switch shutting down the system 5 high pressure switch shutting down the system 1 Check for proper voltage 2 Check all wirings and connections 3 Check start relay start cap...

Page 28: ...he field wirings Use minimum 14 gauge wires for power lines If equipped with low ambient condition kit use low ambient temperature wiring diagrams A safety switch is always recommended for the condens...

Page 29: ...28 Fig 17 WM 2500 4500SSD LA Electrical Wiring Diagram Fig 18 WM 6500 12000SSD Electrical Wiring Diagram...

Page 30: ...29 Fig 19 WM 6500 12000SSD LA Electrical Wiring Diagram...

Page 31: ...ties express or implied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any modification of VINOTEMP products...

Page 32: ...USE OF THE UNIT LOSS OF TIME OR COMMERCIAL LOSS ANY OUTER DAMAGES WHETHER INCIDENTAL CONSEQUENTIAL OR OTHERWISE THIS WARRANTY IS EXCLUSIBE AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR INPLIED...

Reviews: