Use of the adjustable low pressure control
Cut out = 5 psig; Cut in = 25 psig; Differential = 20 psig
Fig. 2.8 Adjustable Low Pressure Control
9. Condensing Unit Troubleshooting
Unit not running
a. Incorrect power supply
b. Incorrect or loose wirings
c. Failed
components
d. Liquid refrigerant in the compressor
e. Low pressure switch shutting down the unit
a. Check for proper voltage
b. Check all wirings and connections
c. Check start relay, start capacitor, overload
protector, compressor.
d. Call service for OEM information
e. Check for system restriction or low
refrigerant