background image

                                                       

 

                       

 

- 11 -

3)  Both discharge and suction valves must be in the middle positions during 

evacuating and charging.  

4)  Charge the system after pipe brazing, leak testing and evacuating. Liquid 

must always be charged into the hide side. 

5)  The subcooling at the condensing unit shall be around 10

°

F. The charge 

may be complete when there are no more bubbles forming in the liquid 
indicator. 

6) Head pressure range: 125 ~ 150 psig at 70 ~ 90 

°

F condensing unit 

ambient temperature. 

7)  The evaporator’s constant pressure expansion valve is set around 30 ~ 35 

psig (35 ~ 40

°

F) at factory. This pressure setting gives a dew point to 

maintain the humidity for storing wine. 

8)  The temperature split across the evaporator shall be 8 ~ 10

°

F at 55

°

wine room temperature. 

9)  Again, must verify if the superheat at the evaporator unit is around 9 ~ 

18

°

F at 50 ~ 65 

°

F wine room temperature with a normal condensing unit 

ambient temperature. 

10) If the superheat is high, check the subcooling first to know if the refrigerant 

charge is sufficient. If the charge is not sufficient, add more refrigerant. If 
the charge is good, then increase the evaporator suction pressure by 
turning the hex nut (5/16”) clockwise.  

11) If the superheat is low, then decrease the evaporator suction pressure by 

turning the hex nut (5/16”) counter-clockwise. 

12) Both discharge and suction valves must be in the back positions before 

disconnecting evacuating and pressure gauges. 

 

 

 

Fig. 10 Expansion Valve 

 
The line sizes and refrigerant charges are listed as follows. 
 

MODEL 

REFRIGERATION 

LINES 

LIQUID 

LINE 

SUCTION 

LINE 

DRAIN 

LINE 

CHARGE 

VINO-1500SSL 

<= 50 FT 

1/4" OD 

3/8” OD 

1/2” OD 

R134a/15 OZ 

VINO-2500SSL 

<= 50 FT 

1/4" OD 

3/8” OD 

1/2” OD 

R134a/19 OZ 

VINO-4500SSL 

<= 50 FT 

1/4" OD 

1/2” OD 

1/2” OD 

R134a/26 OZ 

VINO-6500SSL 

<= 50 FT 

1/4" OD 

1/2” OD 

1/2” OD 

R134a/32 OZ 

Summary of Contents for WINE-MATE VINO-1500SSL

Page 1: ...TE Split System Installation Operation Care Manual VINO1500SSL VINO2500SSL VINO4500SSL VINO6500SSL V Vi in no ot te em mp p I In nt te er rn na at ti io on na al l C Co or rp p w ww ww w v vi in no ot te em mp p c co om m READ AND SAVE THESE INSTRUCTIONS ...

Page 2: ...t Safety Information 2 Features Specifications 3 Cellar Construction 7 Installer s Instruction 8 Electrical Wiring 15 Temperature Control Humidity Adjustment 19 Care Guide 22 User Troubleshooting 23 Customer Support 26 Warranty 27 ...

Page 3: ... 2 Important Safety Information WARNING DO NOT USE A GROUND FAULT INTERRUPTER GFI A DEDICATED 20 OR 30 AMP CIRCUIT IS REQUIRED 1500 4500SSL OR 6500SSL ...

Page 4: ...lows MODEL EVAP UNIT W xD xH COND UNIT L xD xH Btu h CFM 55 90 F CAPACITY 55 75 F REFRIGERANT ELECTRICAL EVAP UNIT COND UNIT WEIGHT lb EVAP UNIT COND UNIT VINO 1500SSL WM 15SFCL 16 75x14 5 x4 75 WM 150SCU 18x12x14 1500 180 150 cu ft R134a 115V 60HZ 0 4A 115V 60HZ 3 1A 15 30 VINO 2500SSL WM 25SFCL 31 75x14 5 x4 75 WM 250SCU 18x12x14 2500 275 250 cu ft R134a 115V 60HZ 0 4A 115V 60HZ 5 7A 30 40 VINO ...

Page 5: ...included Condensing Unit discharge and suction valves installed Liquid Filter Liquid Indicator Evaporator Unit liquid line solenoid valve and expansion valve installed Temperature Controller 4 5 LX4 5 WX3 75 D Air Sensor Fig 1 WM15 25SFCL Evaporator Unit Fig 2 WM45 65SFCL Evaporator Unit ...

Page 6: ... 5 Fig 3 WM150 450SCU Condensing Unit Fig 4 WM 650SCU Condensing Unit ...

Page 7: ... 6 Fig 5 Liquid Filter Fig 6 Liquid Indicator ...

Page 8: ...rature surrounding the enclosure shall not exceed the temperature of the enclosure by more than 25 F No enclosure wall shall receive direct sun or strong wind Lighting shall be of low wattage with a timer to insure lights are not left on when the enclosure is not occupied The cooling system will not be able to maintain the proper temperature if fresh moisture laden air is constantly being introduc...

Page 9: ...ation and proper operation of the system must be warranted by the installer Installation of the system must be done in accordance with all state and local building and electrical codes The condensing unit and evaporator unit are connected by a liquid line and an insulated suction line that are supplied by the installer These lines must be properly sized for the distance between the two units After...

Page 10: ...for the exhaust side and leave minimum 1 foot clearance for the fresh air intake side CAUTION IF THE CONDENSING UNIT IS EQUIPPED WITH A LOW AMBIENT CONDITION KIT DO NOT TURN ON THE COMPRESSOR UNTIL THE CONDENSING UNIT HAS BEEN POWERD FOR 24 HOURS 2 Discharge Suction Valve Operation Condensing unit Back Position Normal operation process and manometer port closed Front Position Liquid suction line c...

Page 11: ...ded 5 Piping Evacuating Charging and Starting CAUTION ALWAYS USE THE SUPERHEAT AND SUBCOOLING PRESSURE READINGS TO CHARGE REFRIGERANT PROPERLY THE LISTED CHARGES ARE FOR REFERENCE ONLY CHARGE 15 MORE REFRIGERANT IN THE SUMMER IF THE UNIT IS EQUIPPED WITH A LOW AMBIENT CONDITION KIT NOTES THE LINE CONNECTION SIZES OF LIQUID FILTER INDICATOR THE VALVE CONNECTION SIZES OF CONDENSING UNIT AND THE LINE...

Page 12: ...orator unit is around 9 18 F at 50 65 F wine room temperature with a normal condensing unit ambient temperature 10 If the superheat is high check the subcooling first to know if the refrigerant charge is sufficient If the charge is not sufficient add more refrigerant If the charge is good then increase the evaporator suction pressure by turning the hex nut 5 16 clockwise 11 If the superheat is low...

Page 13: ...5 psig Cut in 25 psig Differential 20 psig Head pressure setting Cut out 230 psig Cut in 150 psig Differential 80 psig It may need to adjust the setting in the field to get the right cycle time A P70 Single Dual Control Fig 11 Adjustable Pressure Control B PS2 Dual Control Fig 12 Adjustable Pressure Control ...

Page 14: ...IDDLE POSITIONS TO READ PROPERLY Complaint Possible Causes a High suction pressure and low head pressure Zero superheat and zero subcooling b High suction pressure and low head pressure Low superheat and low subcooling c High suction pressure and high head pressure Low superheat and high subcooling d High to normal suction pressure and high head pressure Low subcooling e High suction pressure and ...

Page 15: ...h head pressure Normal to high superheat and high subcooling receiver solenoid valve restricted i Suction line restricted j Air restricted at evaporator evaporator iced k Evaporator restricted l Expansion valve restricted m Both evaporator and condenser restricted liquid and suction lines connected wrong n Liquid line restricted before receiver o Condenser restricted 11 Condensing Unit Troubleshoo...

Page 16: ... 15 Electrical Wiring CAUTION USE MINIMUM 14 GAUGE WIRES FOR POWER LINES IF EQUIPPED WITH LOW AMBIENT CONDITION KIT USE LOW AMBIENT TEMPERATURE WIRING DIAGRAMS Fig 14 VINO1500 4500SSL Wiring Diagram ...

Page 17: ... 16 Fig 15 VINO6500SSL Electrical Wiring Diagram ...

Page 18: ... 17 Fig 16 Low Ambient Temperature VINO1500 4500SSL Electrical Wiring Diagram ...

Page 19: ... 18 Fig 17 Low Ambient Temperature VINO6500SSL Electrical Wiring Diagram ...

Page 20: ... point in programming mode it selects a parameter or confirm an operation DEF To start a manual defrost UP To see the maximum stored temperature in programming mode it browses the parameter codes or increases the displayed value DOWN To see the minimum stored temperature in programming mode it browses the parameter codes or decreases the displayed value To turn on off the power to the unit To lock...

Page 21: ...y stop a few seconds after the probe restarts normal operation Check connections before replacing the probe Temperature alarms HA LA automatically stops as soon as the temperature returns to normal value Alarm CA with i1F PAL recovers only by switching off and on the instrument 4 Temperature Set Point 4 1 How to see the set point 1 Press and immediately release the SET key the display will show th...

Page 22: ...temperature display delay min 1 ot probe calibration 0 US maximum set point 65 LS minimum set point 50 idF defrost cycle interval time hour 24 MdF defrost cycle endurance time min 30 ALC temperature alarm type rE relative to set point ALU high temperature alarm 10 ALL low temperature alarm 10 AFH alarm recovery differential 5 ALd temperature alarm delay min 120 FnC fan operating mode C n on with c...

Page 23: ...y need to be cleaned at least every 6 months Unplug the system or disconnect power Use a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty Plug cooling system or reconnect power 2 Moisture Removing Remove the extra condensate if it is accumulated in the wine cellar at high ambient temperature and humidity ...

Page 24: ... to change so quickly that it maintains relatively constant average temperature that would prevent wine bottle temperature from varying 3 Temperature high but displaying temperature low unit stopping and starting with short running time a air sensor contacting the evaporator b Short circuit of air flow between supply and return air c Setting too high d Failed temperature controller and air sensor ...

Page 25: ... location or increase setting e Clean condenser 7 Evaporator freezing up a Evaporator air flow restriction b Unit not stopping due to air leak high ambient temperature or low setting c Low ambient temperature d Bad thermostat or sensor e Refrigerant low or leak f Expansion valve blockage a Check for fans CFM b Check for seal door opening ambient temperature and setting c Defrost the unit d Check f...

Page 26: ... high ambient temperatures or airflow restriction d Malfunctioning components a Add support to improve installation b Check fans cabinet washers tubing contact and loose screws c Check for airflow blockage d Call service for checking Internal loose inadequate lubrication and incorrect wirings ...

Page 27: ... 26 Customer Support If you still have problems please contact us at Vinotemp International 17631 South Susana Road Rancho Dominguez CA 90221 Tel 310 886 3332 Fax 310 886 3310 Email info vinotemp com ...

Page 28: ...nties express or implied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any modification of VINOTEMP products shall void this warranty Service under Warranty This service is provided to customers within the continental UNITED STATES only VINOTEMP cooling units are warranted to produce the stated number of BT...

Page 29: ...F USE OF THE UNIT LOSS OF TIME OR COMMERCIAL LOSS ANY OUTER DAMAGES WHETHER INCIDENTAL CONSEQUENTIAL OR OTHERWISE THIS WARRANTY IS EXCLUSIBE AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR INPLIED INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE While great effort has been made to provide accurate guidelines VINOTEMP cannot warrant its unit...

Reviews: