background image

Man-1131_Hydrosense_HSCP_01 

     Page 18 of 18

 

 

22.2.2 The + and - terminals inside the connection box must be connected to the Z+ and Z terminals 
at the control panel. 

 

22.2.3 The end of line resistors at the control panel should be discarded. 

 
22.2.4 It is advisable to leave off the lid of the connection box, until all testing is complete. 

 

22.3 Remote Lamp Connection  

22.3.1 In some installations, particularly in floor voids, it is desirable to identify the area in which 

water has been detected, with a remote indicator unit mounted above the void. 

 
22.3.2 This can be achieved by wiring a K2103 remote lamp unit to the - and rem. terminals in the 

K2106 connection box. 

 

22.3.3 Only one remote lamp unit should be connected to each connection box. 
 

22.4 Testing  

22.4.1 Once all terminations have been made and the system is powered, the Hydrowire is ready 
for testing. 

 

22.4.2 Testing is best done by dipping the thumb and forefinger into a cup of tap water, shaking off 

the excess drips and then gripping the Hydrowire firmly whilst rolling it slowly. This should 
produce an immediate indication at the control panel. 

 

22.4.3 Over wetting the Hydrowire should be avoided as a great deal of time can be wasted by 
waiting for it to dry out. 

 

 

22.5 General Checklist  

22.5.1 Avoid excessive wetting. 

 

22.5.2 Observe polarity of all connections. 
 

22.5.3 Long lengths of Hydrowire may be susceptible to high levels of electrical noise. Keep 

lengths short wherever possible and do not install close to other cables. 
 

22.5.4 Do not twist, bend sharply, stretch, stand on or crush the Hydrowire. 

 

22.5.5 Do not expose to surface temperatures above 70°C. 
 

22.5.6 Use only recommended Hydrowire system components. 

 

23. Hydrosense Probe Commissioning 

 

This is best achieved by dipping the tips of the probe pins into a cup of tap water. 

 

This should produce an immediate reaction at the control panel, the LED mounted on top of the probe and, if 

fitted, the remote lamp unit and or sounder.

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for Hydrosense HSCP

Page 1: ...Hydrosense HSCP Conventional Water Detection Control Panel Operation and Maintenance Manual Man 1131 Issue 01 November 2009 www acornfiresecurity com www acornfiresecurity com...

Page 2: ...Panel operation 11 15 Configuration options 12 16 Watchdog reset switch 14 17 Processor reset switch 14 18 Internal indications troubleshooting 14 18 1 Mains fail 14 18 2 Batt fail 14 18 3 CPU fault...

Page 3: ...lass 1 construction As such it must be connected to a protective earthing conductor in the fixed wiring of the installation and a readily accessible double pole disconnect device meeting the requireme...

Page 4: ...Maximum ratings not to be exceeded Zone quiescent current 1 6mA maximum See table 4 for detector types Terminal capacity 0 5mm2 to 2 5mm2 solid or stranded wire Number of detectors per zone 20 Depende...

Page 5: ...hand side of the PCB The fascia of the control panel is held in place by countersunk screws Undo the two screws and lift the fascia gently away from the box towards you With the fascia removed there...

Page 6: ...e enclosure and turning it over The software version will have a number such as Sig27 hex and it is this number which will determine which features the panel has installed and its compatibility with H...

Page 7: ...Any unused zones must have the 6K8 resistor in place When using Probes the 6K8 Resistor must be placed across the terminal wiring as illustrated in the diagram below Detection zone circuits must be w...

Page 8: ...ailable for powering sounders with a maximum load of 0 41 Amps on any one circuit 9 Connection to remote control terminals Some functions of the control panel can be controlled externally from the pan...

Page 9: ...n any of the zones or pressing of the sound alarm button on the front panel The relay will remain activated until the alarm is silenced or the panel is reset This relay will not operate upon activatio...

Page 10: ...boards share the same address Apply power to main panel and all ancillary boards then briefly press the PROCESSOR RESET button on the main panel wait for a few seconds and the main panel will show th...

Page 11: ...and Sounder Fault LEDs to light indicating a fault on the wiring to the sounder circuits 14 7 Power fault Failure of the mains power disconnection of the standby battery or high impedance in the char...

Page 12: ...een sounders disabled and sounders enabled 15 Configuration options The HYDROSENSE HSCP range of control panels has many configuration options which can be set at the time of commissioning to suit the...

Page 13: ...AYED 36 ZONE 6 ALARM FROM DETECTOR DELAYED 37 ZONE 7 ALARM FROM DETECTOR DELAYED 38 ZONE 8 ALARM FROM DETECTOR DELAYED Sounder outputs will be delayed by time set at options 0 9 when selected zone s t...

Page 14: ...n the control panel fails to carry out its operation correctly it will attempt to restart itself This process is called a watchdog and the control panel must record and indicate these events If a watc...

Page 15: ...ary board Check for comms fault at all repeaters and ancillary boards to identify the source of the problem 19 Power supply The control panel requires a 230V 10 15 50 60Hz AC mains power supply which...

Page 16: ...Detection System will identify any malfunction of the control panel and any malfunction should be reported to the alarm maintenance company immediately Should the control panel become faulty the comp...

Page 17: ...ugh the construction is quite sturdy the cable may be damaged by crushing or excessive bending A bend radius of 150 mm is recommended as a minimum 22 1 5 The end of the Hydrowire must be terminated wi...

Page 18: ...thumb and forefinger into a cup of tap water shaking off the excess drips and then gripping the Hydrowire firmly whilst rolling it slowly This should produce an immediate indication at the control pan...

Reviews: