Viale Vicenza, 14 - 36063 Marostica VI Italy
Tel. +39 0424 488 600 - Fax (Export) +39 0424 488 709
www.vimar.com
Eikon
20549
Arké
19549
Idea
16989
Plana
14549
Control device with three rocker switches and MASTER dimmer actuator 230
V~ 50 Hz for incandescent lamps 40-300 W, electronic transformers 40-200
VA, CFL 10-120 W, LED lamps 3-120 W, fuse, to be completed with inter-
changeable buttons with 1 or 2 modules - 3 modules.
Device provides a synchronism signal to SLAVE dimmers (max 3) and can directly control the
load. Device to be used as three single buttons or one single and one double, depending on the
button chosen. The buttons can be configured independently from the SLAVE dimmer piloting
portion too. The buttons can be pressed both at the top and at the bottom.
IMPORTANT: Lamps controllable from a single master or slave dimmer must all be the
same. All controllable loads must be declared DIMMERABLE by the manufacturer. Check
the type of compatible dimmering on the lamp package: LE (Leading Edge) or TE (Trailing
Edge). If it is not specified, the lamp can operate in both modes (chosen at the discretion
of the installer).
CHARACTERISTICS.
• Rated supply voltage TP Busbar: 29 V
• Rated supply voltage mains: 230V~
• Absorption from TP Busbar: 16 mA
• Combinable buttons: 1 double, 1 single or 3 single
• Terminals:
S
synchronism,
L
phase,
N
neutral,
load, TP busbar
• Fuse with high breaking capacity type F2.5AH incorporated
• Possible functions of the buttons:
- ON/OFF switch
- Roller shutters control
- Dimmer control
- Activation of 2 scenarios
• Possible functions of the dimmers:
- Switching on, off and dimmering
- Changing absolute brightness
- Actuating/saving scenarios
- “Flash start” mode
- "Ramp" operation
- Switch-off delay and warning function
- Phase cutting: LE/TE
• Protection against short-circuits when powering up
• Thermal protection.
• MASTER function: paying attention not to exceed maximum power controllable by each
dimmer. A MASTER device can have up to 3 universal SLAVE dimmers (art. 01871, 20137,
14137, 19137, 16604) for a maximum total load of 1800 W (VA) corresponding to 500 W/VA
max connected to each of the 3 SLAVE dimmers and 300W to the master dimmer
•
Not compatible with By-me control panels with 2 modules and flush-mounted (art.
20510, 16950 and 14510).
CONFIGURATION.
FOR THE OPERATIONS OF INSTALLATION AND CONFIGURATION, SEE THE BY-ME
SYSTEM INSTRUCTIONS MANUAL ATTACHED TO THE CONTROL UNIT.
Configuration must be done with the device without the key to be able to press the central
configuration button.
• Functional units: 4 (3 buttons, 1 dimmer actuator), each functional block can belong to at most
4 groups.
• Selection of the functional unit in the configuration phase:
- Press the configuration button and wait for 3s to select the dimmer functional unit;
- Press the configuration button and then the desired button to select
the relevant button functional unit.
The configuration starts when the red LED comes on and ends when it goes out.
When the device is not configured, the actuator is controlled by the left-hand button.
Controllable loads
LE
TE
40 to 300 W
40 to 200 W
10 to 60 W
(Max 3 lamps)
10 to 120 W
(Max 6 lamps)
3 to 60 W
(Max 3 lamps)
3 to 120 W
(Max 6 lamps)
Electronic transformers
for halogen lamps
40 to 100 W
(Max 1 transformer type
L
)
40 to 200 W
(Max 3 transformers type
C
)
Dimmering with Leading Edge mode
Dimmering with Trailing Edge mode
• If the device must be configured as a double and one single button you must:
- Press the left button if you want the double button on the left;
- Press the middle button if you want the double button on the right.
It is recommended to configure the device with the load OFF.
INSTALLATION RULES.
Installation should be carried out in compliance with the current regulations regarding the instal
-
lation of electrical systems in the country where the products are installed.
• The lamps connected to the master or slave must all be the same.
• Not suitable for controlling motors (e.g. fans, ventilators).
• The rated power level should never be exceeded.
• If installing 2 dimmers in a single box, the loads that can be controlled by each dimmer must be reduced
so that their total does not exceed the maximum power that can be controlled by a single device.
• Overloading, power surges and short-circuits may irreparably damage dimmers. Before
installation check the circuit carefully and eliminate any of the above causes.
• The dimmer does not have a mechanical circuit breaker in the main circuit and so is not
galvanically separated. The circuit load should be considered always powered.
For further instructions see the manual enclosed with the control panel.
For all details on possible installation architectures, please refer to SI-Connection dia-
grams for the relevant item code at www.vimar.com -> Products -> Product catalogue.
STANDARD CONFORMITY.
LV directive
EMC directive
Standards EN 50428, EN 50491.
TP Bus terminals
FRONT AND REAR VIEW
Configuration button
LED
S
40-300W LE
40-200W TE
L
N
S L N
CONNECTIONS
L
N
Bus
S
40-300W LE
40-200W TE
L
N
20549
19549
16989
14549
20137
19137
16604
14137
20137
19137
16604
14137
20416
19416
16460
14416
20416
19416
16460
14416
Maximum length of cables connecting universal MASTER dimmer and universal SLAVE dimmer: 100 m
Connect at least the minimum load required to the universal master dimmer.
MASTER and SLAVE must be configured in the same operating mode.
SLAVE
SLAVE
Fuse carrier
MASTER
Fuse carrier
L
N
Bus
S
40-300W LE
40-200W TE
L
N
20549
19549
16989
14549