ENGLISH - 3
1. Installation Gas Stop
Apply to authorized technicians for all
installation and any routine and non-rou-
tine maintenance operation as well as for
the replacement of the detector at the
end of its life-time.
The LPG/methane detector must be
installed in a position in which air circu-
lates freely,
at a distance of no more
than 3-4 m from boilers, water heat-
ers, stoves and gas canisters and at
20-30 cm above floor level (figure 1
- Gas Stop GPL) or 20-30 cm from the
ceiling (figure 2 - Gas Stop Metano).
1,5 m min
30 cm max
1 m min - 4 m max
1 m min - 4 m max
Fig. 1
Gas Stop GPL
For the installer