9.7  OnOff/PID setting

This menu lets you select the way in which the ambient temperature will be controlled.

Via 

 and 

 you can select the following options:

•  

 (OnOff control)

: this is the traditional "threshold" control so that, on exceeding the set tem-

perature increased by 

 (vice versa for air-conditioning), the heating is switched off to then be turned 

back on when the room temperature drops below the set temperature. 
The 

 value can be set directly via the submenu that follows this selection.

•  

 

(P.I.D. control)

: this is an evolved algorithm that is able to keep the temperature in the envi-

ronment more stable, increasing comfort; this algorithm switches the system on and off appropriately so 
there will be a gradual increase or decrease in the thermal (or refrigerating) power of the system itself. 
To take full advantage of its performance it needs to be suitably calibrated according to the type of envi-
ronment and heating system; in the light of this, the following parameters must be set via the submenus 
that follow this selection:

  

 (breadth of adjustment range)

: starting from the set temperature, Tb is the temperature range 

in which the heating power goes from 0% to 100%.

For example: with the temperature (for heating) set to 20.0°C and Tb=4.0°C, the thermostat acti-
vates the heating system on 100% when T.ambient is <= 16.0°C; as this temperature increases, the 
system power is consequently lowered down to 0% when the ambient temperature reaches 20°C.

The value of Tb must be set consistently with the thermal capacity of the system; in general, it is 
recommended to use small values   of Tb for environments with a good level of thermal insulation 
and vice versa.

•  

 (system cycle time)

: this is the time in which a cycle of regulation is completed; the shorter this 

time, the better the regulation but the temperature control system is under greater stress.
This parameter setting is thus the result of a compromise between the accuracy of the regulator 
and the load on the system; in general, the rule is that Tb can be that much higher (and therefore 
put fewer demands on the system), the slower the system or the larger the environment to regulate.

Tap 

 to confirm your choice.

Summary of Contents for 2905

Page 1: ...Instructions manual Thermostat 02905 Installer Manual ...

Page 2: ......

Page 3: ...er menu type and resetting default parameters 15 9 Settings of the normal menu 16 9 1 Operating mode setting 16 9 2 Unit of measurement setting 16 9 3 Heating air conditioning setting 17 9 4 Temperature set point setting 17 9 4 1 Comfort temperature 17 9 4 2 Away temperature 18 9 4 3 Antifreeze temperature 18 9 4 4 Nighttime reduction thermal delta 18 9 4 5 User settable thermal delta 18 9 4 6 Hys...

Page 4: ...interface thanks to special views facilitates system management helping the user to oper ate while maintaining a state of energy saving 3 Installation The appliance must be installed on a wall at a height of 1 5 m off the floor in a suitable position for correctly detecting the ambient temperature It must not be installed in niches behind doors and curtains or in areas affected by sources of heat ...

Page 5: ... a dry contact vice versa if they are open the input is off The contact must be SELV and free of potential The typical wiring diagram is the following NO NC C Fig 3 Connecting the multi function input Activation type dry contact Type of conductor 1 single wire or 1 multi wire cable conductor MAX 1 5 mm2 Length of the conductor max 100 m between the 2 terminals FUNCTIONS Remote nighttime reduction ...

Page 6: ...1 5V AA batteries CAUTION In case of replacement dispose of batteries in the specific differentiated collection bins Fig 4 Changing batteries The battery charge status is shown as follows no icon battery charged flashing icon battery almost flat replace it fixed on icon battery flat the device will go OFF and it is no longer possible to switch to operation ...

Page 7: ...g buttons and icons I H G F E D C A B L Fig 5 Graphical interface and buttons A Battery charge status B Operating mode C Away D Confirm E F Menu navigation and setting parameters G Back H Nighttime reduction I Settings menu L Ring indicating consumption level and energy savings indicator ...

Page 8: ...it After each confirmation the display shows the icon for approximately 1 s In addition if the timer thermostat is connected to the probe 02960 via the circuit board 02915 it will also be possible to enable its acoustic signal back or cancel exits the current screen menu and returns to the previous one without saving any changes In menus with changes to multiple digits it lets you go back to chang...

Page 9: ...e conventional average consumption vice versa if the level exceeds half the expected consumption will be higher than the conventional average The energy saving indicator indicates whether the currently set setpoint will allow obtaining savings with respect to the conventional average consumption 6 4 Locking the interface via PIN The thermostat lets you set a password see par 8 9 which inhibits any...

Page 10: ...s been suitably configured you can remotely activate the following modes Remote reduction conceptually similar to nighttime reduction it acts on the comfort set point instead of the one set locally in manual mode Remote activation lets you activate the system remotely by setting the comfort set point Summer Winter switching the multi function input automatically switches the thermostat onto air co...

Page 11: ... changed via or In the course of setting the set point flashes and the circular ring fills up accordingly this gives an indica tion of the expected consumption as a function of the set point you are setting Fig 10 Manual set point setting The selection is confirmed by touching The and icons in the lower right corner indicate whether the system is operating in heating or air conditioning mode respe...

Page 12: ...ay temperature setpoint see para 9 4 2 The Away mode can only be activated in manual mode by touching The display will show the away temperature setpoint for approximately 2 seconds Fig 11 Input in away mode showing the away temperature Activation of this mode is identified by the icon above the temperature indicator Fig 12 Away Mode To exit and return to Manual mode touch the button again ...

Page 13: ... Manual mode by degrees see par 9 4 4 Nighttime reduction is activated starting from Manual mode by touching or remotely via the multi function input if enabled The display will show the nighttime reduction setpoint for approximately 2 seconds Fig 13 Input in Nighttime Reduction mode showing the reduction set point Activation of this mode is identified by the icon above the temperature indicator F...

Page 14: ...ue setpoint to avoid damage to the pipework or to keep it from falling below a certain safety level when you are away for lengthy periods in the winter The antifreeze mode is activated directly from the Settings menu see par 9 1 Once activated antifreeze mode is identified by the icon above the temperature indicator Fig 15 Antifreeze mode ...

Page 15: ...on of the configured multifunction input is considered solely when the thermostat is in Manual mode In remote reduction mode the device sets the temperature to a value equal to Tcomfort see para 9 4 In this condition the display and its buttons have limited functions access to the settings menu is disabled and you can only change the temperature setpoint within a limited range if configured The Re...

Page 16: ...y if it has been suitably configured by the installer see par 9 6 In remote activation mode the device sets the temperature to a value equal to Tcomfort see para 9 4 In this condition the display and its buttons have limited functions access to the settings menu is disabled and you can only change the temperature setpoint within a limited range if configured The Remote activation mode is identifie...

Page 17: ...sired temperature set point can be set without the need to confirm the entered value Normal menu Within 3 secs touch and using and select EASY and then NO confirming with both choices The thermostat will restart showing the normal operating mode N B When replacing the batteries the set menu will automatically start when the thermostat is switched back on without having to repeat the above procedur...

Page 18: ...5 calibration setting 6 and multi function input setting 7 OnOff PID temperature control algorithm setting 8 device info 9 lock unlock PIN setting Touching opens the submenu and then the flashing highlights the parameters of the submenu 9 1 Operating mode setting This menu is used to select the operating mode of the device Manual Off Antifreeze only if the thermostat is set on heating Using and se...

Page 19: ...nOff adjustment mode CAUTION Depending on the mode the thermostat is in heating or air conditioning setting this setpoint acts only on the value associated with the current mode highlighted by the or icon for example T comfort of heating mode After then changing the setpoints of the current mode in succession change the mode and set all the setpoints corresponding to it 9 4 1 Comfort temperature T...

Page 20: ... reduction is activated by the display or to Tcomfort when nighttime reduction is acti vated by the multi function input the thermal delta value is identical both in heating mode and in air conditioning mode with the only difference being that in the former case it causes a decrease in the set point while in the latter one it determines an increase The nighttime reduction mode can be activated eit...

Page 21: ...n enabled automatically sets the Tcomfort temperature as the setpoint In this context the user can only change the temperature within a narrow range and cannot carry out any further operations on the device with the multi function input disabled the default mode is Antifreeze or OFF if on air conditioning and the user can manage the thermostat completely remote nighttime reduction the multi functi...

Page 22: ... be set via the submenus that follow this selection breadth of adjustment range starting from the set temperature Tb is the temperature range in which the heating power goes from 0 to 100 For example with the temperature for heating set to 20 0 C and Tb 4 0 C the thermostat acti vates the heating system on 100 when T ambient is 16 0 C as this temperature increases the system power is consequently ...

Page 23: ... in season to differentiate between heating and air conditioning by pressing and holding the button displays the software version of the device 9 9 Lock unlock PIN setting This menu lets you add change the password to inhibit use of the thermostat Using and set the three digits of the PIN one at a time and then confirm each set digit with If you wish to have free access to the thermostat so withou...

Page 24: ...roportional band PID Band 0 5 5 C 0 1 C 1 C Adjustment period PID Period 10 30 minutes 1 min 20 min Unit of measurement tem perature Temperature unit C F C Temperature offset TE Offset temp 0 3 C 0 1 C 0 C Adjustment limit range Offset δU 0 2 C 0 C 0 5 C PIN number PIN 000 999 1 000 Temperature set point T0 Away Heat TG 10 35 C 0 1 C 16 C T2 Comfort Heat 10 35 C 0 1 C 20 C T0 Away Aircon 10 35 OFF...

Page 25: ...void using aggressive products Clean the display with a special cloth for cleaning lenses 12 Installation rules Installation should be carried out in compliance with the current regulations regarding the installation of electrical systems in the country where the products are installed 13 Regulatory compliance LV directive EMC directive Standards EN 60730 2 9 ...